Laserfiche WebLink
SAN J U A Q U I N Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ARCO AMPM 2056 CRESTWOOD AVE, MANTECA June 30, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 203 CCR 2712(b)(1-2)Failure to maintain monitoring records for 36 months and maintenance records for 60 months. <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site. <br /> -Overfill prevention test results. <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2)monitoring equipment calibration and maintenance <br /> records; (3)results of any visual observations; (4)results of sample analysis performed a lab or in the field; (5)logs <br /> of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6)results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the <br /> last three years on site and submit copies to the EHD. <br /> This is a minor violation. <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The designated operator failed to check and note the correct test dates for the last monitoring <br /> system certification on the monthly visual designated operator inspection reports. The incorrect date stated was <br /> 07/27/2020,the correct date is 06/05/2020. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> This is a minor violation. <br /> 209 CCR 2715(c)(3), 2715(c)(4) Failure to maintain a copy of the"Facility Employee Training Certificate"on-site. <br /> OBSERVATION: The Facility Employee Training Certificate dated 01/26/2021 left the date of assuming <br /> responsibility as a facility employee blank. <br /> REGULATION GUIDANCE:All site employees must be trained prior to taking responsibility as a facility employee if <br /> after October 1, 2018, or within 30 days of hire if prior to October 1, 2018. The Facility Employee Training <br /> Certificate shall contain accurate information for all employees trained. <br /> CORRECTIVE ACTION: Update the Facility Employee Training Certificate to contain the accurate information and <br /> submit a copy of the updated form to the EHD. <br /> This is a minor violation. <br /> FA0024277 PR0542283 SCO01 06/30/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />