U <br /> J <br /> J <br /> Z POWER PLAN GENERAL NOTEStl W Z <br /> oWA <br /> - <br /> o A . ALL RECEPTACLES ON COMMON WALLS SHALL BE SEPARATE BOXES AND OFFSET 12" D <br /> z MINIMUM. FIRE RATED WALLS SHALL HAVE AN OFFSET OF 24" MINIMUM. COORDINATE o Z <br /> w w/ ARCH'L FIRE RATED WALL DETAILS. O <br /> B. ALL PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE PROTECTED FROM THE (858) 733-2445 <br /> 0 SPREAD OF FIRE w/ AN APPROVED FIRE5TOP SYSTEM EQUAL OR GREATER THAN <br /> Z THE FIRE RATING OF THE WALL. designed by: <br /> 0 <br /> C. HEIGHT OF ALL RECEPTACLES ETC., SHALL BE VERIFIED w/ OWNER PRIOR TO <br /> • ROUGH-IN. PROVIDE GF.C.I. TYPE RECEPTACLE WITHIN 6 FEET OF ANY SINK <br /> J D. ALL UNDERGROUND CONDUITS SHALL BE PVC SCHED. 40,MINIMUM 3/4"C. RUN CODE <br /> SIZE INSULATED EQUIPMENT GROUND CONDUCTOR REVISIONS: <br /> Z <br /> tl <br /> D E. EACH AND EVERY 15 AND 20 AMP, 120 VOLT RECEPTACLE IN KITCHEN,FOOD NO DATE DESCRIPTION <br /> C/) PREPARATION, BAR AREAS AND RE5TROOM5 SHALL BE GFCI TYPE PROTECTION. <br /> 0 <br /> Z F. (l)3/4" G.O.FOR EACH THERMOSTAT BACK TO EACH CORRESPONDING HVAC UNIT AND <br /> BETWEEN MECHANICAL UNITS AS NEEDED FOR CONTROLS. REFER t0 MECHANICAL <br /> o DRAWINGS FOR EXACT QUANTITY AND LOCATION. <br /> J <br /> U_ <br /> U_ <br /> G. (1) 1-1/4" C.O. HOME RUN FOR EACH TELE/DATA OUTLET 6" IN THE CEILING SPACE, U.N.O. <br /> o H. COORDINATE EXACT MECHANICAL EQUIPMENT LOCATIONS AND REQUIREMENTS w/ <br /> MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN. <br /> • <br /> I. FOR 120 VOLT RECEPTACLE WIRING, PROVIDE *10 AWG NEUTRAL CONDUCTORS MINIMUM. <br /> J <br /> c� 101A J. NOTE: SYMBOL INCLUDES EQUIPMENT GROUND CONDUCTOR (NOT INDICATED). <br /> Z <br /> D <br /> 1 K ALL WIRING IS TO BE COPPER <br /> 0 2 L. INSTALL DATA LINES IN CONDUIT TO BOXES INSTALLED BY LOW VOLTAGE CONTRACTOR <br /> Z A-IS A-20b FOR CAMERA INSTALLATION. <br /> U) M. THE WATTAGE OF LOW VOLTAGE DEVICE WITH PERMANENTLY INSTALLED OR REMOTELY <br /> o INSTALLED TRANSFORMERS SHALL BE THE INPUT WATTAGE RATING OF THE <br /> D DEVICE/TRANSFORMER COMBINATION. <br /> 0 <br /> N. COORDINATE WITH OWNER AND LOW VOLTAGE CONTRACTOR FOR ALL REQUIREMENTS <br /> o RELATED TO LOW VOLTAGE DEVICES AND CONNECTIONS. <br /> • O 0. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND MAKE ALL CONNECTIONS IN <br /> COMPLIANCE WITH LOCAL CODES. <br /> D <br /> P. ELECTRICAL CONTRACTOR SHALL VERIFY ACTUAL CIRCUITS IN PANELBOARD. <br /> ----CD <br /> Z _ 1 Q. ALL EQUIPMENT SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING <br /> 0 LABORATORY. <br /> Z R ALL LOW VOLTAGE SYSTEM DEVICES ARE TO BE EQUIPPED WITH INTEGRAL <br /> o TRANSFORMER UNLESS OTHERWISE NOTED. <br /> 0 DININGA-33 <br /> Cn NICASHI <br /> 101 5. PROVIDE BUCK BOOST TRANSFORMER FOR ESPRESSO MACHINE AND CREPE MAKER IF <br /> 102 22b 9 REQUIRED. COORDINATE WITH MANUFACTURER FOR EXACT REQUIREMENTS. <br /> ILL <br /> z 2 10 11 12 T. ALL EXTERIOR DEVICES SHALL BE WEATHERPROOF. <br /> A-20a U. ALL RECEPTACLES LOCATED AT FOOD SERVICE, BEVERAGE COUNTERS SHALL BE <br /> 0 <br /> • 0 -12 30 PROTECTED WITH GFCI TYPE BREAKERS IN PANEL BOARDS. <br /> 4 13 V. ALL EMPTY CONDUITS SHALL BE PROVIDED WITH PULL STRINGS. <br /> 101 B A-3 A 31 W. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EQUIPMENT CONNECTIONS,MOUNTING <br /> Z 3l HEIGHTS AND CORD REQUIREMENTS WITH EQUIPMENT MANUFACTURER PRIOR TO <br /> INSTALLATION. <br /> U) <br /> -2 <br /> Z <br /> 0 X. MAKE NECESSARY INSPECTIONS OF EXISTING SITE, POWER SUPPLY LOCATION, ROUTING, <br /> 0 ®ltY J <br /> 29 5 _4 AND POWER COMPANY SERVICE AS REQUIRED AND MAKE ALLOWANCE FOR EXISTING <br /> U) O CONDITIONS BEFORE SUBMITTING BID. <br /> _C) <br /> 0 <br /> LL A-24 P. 17 <br /> z1 A- <br /> A-30,32,34 F W.P. <br /> H POWER PLAN KEYNOTES <br /> 4oAF 6 18 <br /> • 40A O I1 0 J-BOX FOR STORE SIGN IF APPLICABLE. COORDINATE WITH OWNER FOR EXACT LOCATION. <br /> qG 17 ,15 ( PROVIDE SHOW WINDOW RECEPTACLE. COORDINATE WITH OWNER/TENANT FOR EXACT z <br /> Z LOCATION. 0 <br /> N19 <br /> D EXISTING ( PROVIDE 4'xVx3/4" PLYWOOD FOR TELEPHONE BACKBOARD, <br /> Cl)19 PAINTED TO MATCH WALL SURFACE. FIELD VERIFY ALL EX16TINC-S LU <br /> 0 123 CONDITIONS. MAKE ALL CONNECTIONS IN COMPLIANCE WITH LOCAL <br /> 0 A-8 CODES. LU <br /> W A g2l KITCHE <br /> 103 ® PROVIDE CONVENIENCE OUTLET PER OWNER'S DIRECTION. COORDINATE WITH 0 <br /> U_ OWNER/TENANT FOR EXACT LOCATION. <br /> o '8k3e 26 ( VERIFY EXACT LOCATION OF EXISTING "M551". w z <br /> 10 11 12 ® CONTROLLED OUTLET. 0 J <br /> • A-22b J <br /> OO PROVIDE WEATHERPROOF GFI OUTLET WITHIN 25 FT OF NEW ROOFTOP EQUIPMENT. 0 <br /> J <br /> J �� �� � 20 (GEC 210-63, 210-S(b)3). z <br /> Z A 25 Q <br /> J 24 W <br /> 0 17 <br /> Z Q <br /> 0 <br /> U <br /> U) 104 �� �� '8k U <br /> 36 °� O <br /> >e 21 DENOTES RELATED EQUIPMENT, REFER t0 EQUIPMENT SCHEDULE ON SHEET <br /> o F� 28 e O E03 FOR MORE INFORMATION. � (� .J <br /> z <br /> A-26a Q <br /> o CC W N U <br /> • 11 12 27 26 \ <br /> STROO A-26a <br /> N <br /> 104 lN)PANEL "A" -26b A- 2b W O a <br /> Z <br /> J <br /> O w > � < U <br /> 0 3 W 22 W <br /> U <br /> J z J <br /> o11M,51511 <br /> aC o2 � W <br /> 0 103 23 (E) O w re <br /> N <br /> O <br /> LL oC o <br /> 0 O <br /> Z <br /> o LL `:I- Cn <br /> • Z <br /> ELECTRICAL ROOF - POWER PLAN ELECTRICAL FLOOR - POWER PLAN z 11110110 <br /> tl O SCALE: 1/4"=1'-0" O SCALE: 1/4"=1'-0" <br /> J � Frozen Yogurt,Ice-Cream and More... <br /> Z <br /> Z Z Z <br /> O <br /> U <br /> Z <br /> 0 <br /> co <br /> ��eROPHER/ON9l DATE 11 /6/2020 <br /> �� SCALE NOTED <br /> CD E 18921 rn <br /> • * Exp. 12/31/21 * DRAWN AE <br /> U <br /> X1 <br /> `Py 'CTR\OP��P JOB # <br /> J <br /> Z <br /> FOF ca��F° 2013 <br /> 11/06/20 <br /> SHEET NO. <br /> Cn ;, AUNG ENGINEERS <br /> HVAC . Electrical . Plumbing . Energy <br /> 0 7111 Garden Grove Blvd,Suite 108 <br /> Garden Grove,CA 92841 El • <br /> 2 <br /> U_ Ph:(714)349-9181 <br /> z <br /> Email:info@aungengineers.com <br /> Z Web :www.aungengineers.com <br />