Laserfiche WebLink
Test Date: <br />LEAK DETECTOR TESTING <br />Facility ID: <br />Street Address: Technician: <br />ICC #: <br />Test Information <br />Product <br />Manufacturer <br />Model <br />New Leak Detector <br />(Yes/No) <br />Serial Number <br />Electronic LD <br />(Yes/No) <br />Calibrated Test Leak <br />Rate: (189 mil/min <br />@ 10 PSI) (Yes/No) <br />Check Valve Holding <br />PSI <br />Resiliency <br />(Bleed Back MIL) <br />Slow Flow <br />Metering PSI / (N/A) <br />Turbine Shut Down <br />Electronic LD <br />(Yes/No/NA) <br />Slow Flow At Nozzle <br />(Yes/No/NA) <br />Opening Time <br />(Seconds) <br />Pass/Fail <br />This letter certifies that the annual leak detector tests were performed at the above referenced facility <br />according to the equipment manufacturers procedures and limitations and the results as listed are to my <br />knowledge true and correct. The leak detector test pass/fail is determined using a low flow threshold trip <br />rate of 3 gph at 10 PSI. <br />Technician Signature: Date: <br />City: <br />Zip Code / State:/ <br />Client Name: <br />Manufacturer Cert #: <br />7.5.2019 <br />Check If Action Item(s) Are Present <br />PGE095 Pacific Gas and Electric Company <br />4040 West Ln.Craig Feezell <br />Stockton 8374133 <br />95204 CA A23508 <br />Unleaded Diesel <br />09/20/2019 <br />09/20/2019 <br />Veeder-Root Veeder-Root <br />PLLD PLLD <br />No No <br />119293 119295 <br />Yes Yes <br />Yes Yes <br />22.242 21.703 <br />n/a n/a <br />n/a n/a <br />Yes Yes <br /> n/a n/a <br />n/a n/a <br />Pass Pass