Laserfiche WebLink
FIRMSTul s s K,7410 DATE: 12/16/2016 <br /> Tulsa S. <br /> 1-1" <br /> ACUREN 918-998-0862 TECH: Gregory Fann <br /> EQUIP.#: Emergancy Generator A Fuel Tank <br /> COMPANY: Owens Brockway <br /> PLANT: Tracy Ca <br /> AREA: NA <br /> DATA SHEET External 0-REFERENCE: South West Comer <br /> 1" 1' 2' 3' 1' <br /> To <br /> 1" .240" .241" .247" .251" .248" <br /> 1' .246" .248" .247" NA .251" <br /> 2' .242" NA NA NA .247" <br /> ill .238" NA NA NA .249" <br /> West End <br /> No access <br /> East End <br /> 11. .235" <br /> North Side <br /> 1" .231" .232" .234" .235" .235" <br /> 2" 232" .233" .235" .232" .234" <br /> 11" .231" .231" .231" .231" .228" <br /> South Side <br /> 1" .235" .232" .235" .231" .231" <br /> 2" .235" .232" .232" .232" .233" <br /> 11" .233" .231" .233" .228" .228" <br /> CODES:HC=HEAVY CORROSION!NZ=NOZZLE/MW=MANWAY/NA=NO ACCESS/TR=TOO ROUGH/SI=STRUCTURAL INTERFERENCE <br /> NOTE INTERNAL OR EXTERNAL INSPECTION PER COMPONENT <br /> TECHNICIAN COMMENTS <br /> All readings acuired started at the west end(1")at zero(top)rotating north. <br />