Laserfiche WebLink
5208 S.Lawton <br /> Tulsa OK,74107 <br /> W'-::Z w—.dddj 918-998-0862 Date: 12/15/2016 <br /> ACU R E N Location: Owens Brockway Tray CA <br /> Equip.#: Fire Water Pump B Fuel Tank <br /> Cert.Level: API-653#36530 <br /> Inspector: Gregory Fann <br /> Examination Report <br /> scone: <br /> 1)External visual inspection. <br /> 2)Ultrasonic thickness examination of shell,roof and floor. <br /> Summary: <br /> The subject 180 gallon capacity atmospheric storage tank was inspected per the above scope and evaluated per the specified STI SP-001. <br /> Further details may be referenced in the attached Checklist,Calculation sheet,TML report,Image sheet,or Drawing. <br /> Results: <br /> 1)Coating Failure,up to 50%of the shell and ends. <br /> 2)Light local corrosion at coating failures.No measurable scale or pitting. <br /> 3)Fuel oil leak with dust build up.(seepage and dirt) <br /> 4)In-adequate support bracing for earth quake zone. <br /> 5)Heavy corrosion of support base. <br /> Recommendations: <br /> 1)Clean and re-coat tank shell to prevent further corrosion. <br /> 2)Clean and re-coat tank shell to prevent further corrosion. <br /> 3)Clean oil and dirt from shell,assess leak point and consider repair/replacement. <br /> 4)Add addequate bracing or replace to prevent swaying. <br /> 5)Replae corroded sections of support base. <br /> 6)Continue scheduled inspection program per STI SP-001 and O-I company policies and procedures. <br />