Laserfiche WebLink
5208 S.Lawton <br /> Tulsa OK, <br /> 918-998-086 07 <br /> - Date: 12/15/2016 <br /> A C U R E N Location: Owens Brockway Tray CA <br /> Equip.#: 450 Gallon Salvage Oil Tank <br /> Cert.Level: API-653#36530 <br /> Inspector: Gregory Fann <br /> Examination Report <br /> Scope: <br /> 1)External visual inspection. <br /> 2)Ultrasonic thickness examination of shell,roof and floor. <br /> Summary: <br /> The subject 450 gallon capacity atmospheric storage tank was inspected per the above scope and evaluated per the specified STI SP-001. <br /> UT examination was limited due to contamination of product and debis.Further details may be referenced in the attached Checklist,Calculation sheet, <br /> TML report,Image sheet,or Drawing. <br /> Results: <br /> 1)Oil spillage covering entire tank from oil skimmer. <br /> 2)Minor random coating failure. <br /> 3)Insufficient containment. <br /> Recommendations: <br /> I)Clean tank thuroughly,adjust skimmer to prevent further spillage. <br /> 2)Clean and recoat or monitor for corrosion. <br /> 3)Install curbs around tank or replace with double wall tank. <br /> 4)Continue scheduled inspection program per STI SP-001 and O-I company policies and procedures. <br />