GENERAL NOTE POWER PLAN NOTES SHEET NOTES <br /> 1. REUSE EXISTING ELECTRICAL PANELS AND RECONNECT THE A. FURNISH AND INSTALL A COMPLETE AND OPERATING SYSTEM. O PROVIDE CONNECTION FOR POS BANK. FIELD COORDINATE FOR <br /> RELOCATED LOADS AS REQUIRED. IF NEW LOADS ARE ADDED, ALL ITEMS ARE NOT NECESSARILY SHOWN. 1 <br /> USE AVAILABLE SPARE CIRCUITS. EXACT LOCATION AND REQUIREMENT. EXTEND EXISTING WIRING <br /> B. ELECTRICAL CONTRACTOR RESPONSIBLE FOR SITE FOR PREVIOUSLY USED THE SAME TYPE OF EQUIPMENT IN 17' <br /> 2. FIELD VERIFY THE RATINGS OF THE EXISTING PANELS AND INVESTIGATION PRIOR TO START OF WORK TO REVEAL FULL EXISTING DEMO LOCATION TO THIS NEW LOCATION. CONNECT <br /> AVAILABLE SPARE CAPACITIES. IF NEW LOADS ARE ADDED TO SCOPE OF WORK. TO CIRCUIT AS SHOWN. <br /> THE PANEL DO NOT EXCEED THE RATING OF THE PANEL <br /> INCLUDING THE RATINGS OF THE UPSTREAM SERVING C. DIMENSIONS ARE TO FINISH FACE UNLESS OTHERWISE NOTED. O PHONE LINE. FIELD COORDINATE EXACT LOCATION. <br /> FEEDER AND CIRCUIT BREAKER. <br /> 3. ALL CIRCUIT NUMBERS SHOWN HERE ARE BASED ON D. REFER <br /> MOUNTING ODETAIL H HEIGHTS OFTELECCTREXACT RICAL DEVICES. <br /> AND O EXAOVIDE CT LOCATION AND NFOR REGISTER. FIELD COORDINATE <br /> REQUIREMENT. EXTENDEX STING WIRING <br /> PROVIDEDRECORD DRAWING. IF THE ACTUAL EXISTING CIRCUIT FOR PREVIOUSLY USED THE SAME TYPE OF EQUIPMENT IN ©2017STARBUCKS COFFEE COMPANY <br /> NUMBERS ARE DIFFERENT THAN THE ONES SHOWN HERE, USE E. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR EXISTING DEMO LOCATION TO THIS NEW LOCATION. CONNECT <br /> THE ACTUAL NUMBERS AND PROVIDE UPDATED TYPEWRITTEN CONFIRMING ALL VOLTAGE REQUIREMENTS ON ALL TO CIRCUIT AS SHOWN. <br /> SCHEDULE IN ALL PANELS USED IN THIS PROJECT. EQUIPMENT AND PROVIDING BUCK-BOOST TRANSFORMERS ASMAY BE NEEDED FOR PROPER STARBUCKS COFFEE <br /> EQUIPMENT. ALL ARE NOT NECESSARILY OPERATION NDCATED. O LOCAT ONE PROVIDE UPDATED LECTRICAL PANEL OYP WRITTEN SCHEDULE UPON <br /> COMPANY <br /> COMPLETION OF THIS PROJECT. SEE PANEL SCHEDULE ON <br /> F. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH SHEET E-601. MAINTAIN 36" CLEARANCE IN FRONT OF PANELS. 2401 UTAH AVENUE SOUTH <br /> PLUMBING AND HEATING, VENTILATING, AND AIR SEATTLE, WASHINGTON 98134 <br /> CONDITIONING (HVAC) CONTRACTORS FOR ANY ADDITIONAL O EXISTING POS TO BE RELOCATED HERE AND RE-CONNECTED TO (206) 318-1575 <br /> EQUIPMENT NEEDING POWER. EXISTING CIRCUIT PREVIOUSLY USED FOR SAME EQUIPMENT. <br /> G. ANY EQUIPMENT NOTED AS 'FUTURE' SHALL BE PROVIDED O ALL 120V RECEPTACLES IN WORKROOM AND BAR AREA SHALL BE THESE DRAWINGS AND SPECIFICATIONS ARE <br /> WITH APPROPRIATE RECEPTACLES AND WIRING TO ENABLE GFCI RATED. AND ALL SINGLE PHASE RECEPTACLES RATED 150 CONFIDENTIAL AND SHALL REMAIN THE SOLE <br /> FUTURE OPERATION. VOLTS TO GROUND OR LESS, 50A OR LESS AND THREE PHASE PROPERTY OF STARBUCKS CORPORATION, <br /> RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100A OR WHICH IS THE OWNER OF THE COPYRIGHT IN <br /> H. GROUND FAULT CIRCUIT INTERRUPTER(GFCI) BREAKERS (NOT LESS INSTALLED IN THE FOLLOWING LOCATIONS SHALL HAVE THIS WORK. THEY SHALL NOT BE <br /> RECEPTACLES)SHALL BE UTILIZED WHERE REQUIRED BY GROUND FAULT CIRCUIT INTERRUPTER PROTECTION FOR REPRODUCED (IN WHOLE OR IN PART), SHARED <br /> CODE AND AT ANY FLOOR BOXES. PROVIDE DEDICATED PERSONNEL. <br /> WITH THIRD PARTIES OR USED IN ANY MANNER <br /> NEUTRAL WIRE FOR ALL THESE CIRCUITS. ON OTHER PROJECTS OR EXTENSIONS TO THIS <br /> O EXISTING BREWER SOFT HEAT SERVER/SINGLE WARMING PROJECT WITHOUT THE PRIOR WRITTEN <br /> I. DISCONNECT AND REMOVE EXISTING ELECTRICAL DEVICES STAND TO BE RELOCATED HERE. FIELD COORDINATE EXACT CONSENT OF STARBUCKS CORPORATION. <br /> FOR EXISTING EQUIPMENT TO BE REMOVED. REROUTE LOCATION AND REQUIREMENT. IF POSSIBLE, EXTEND THE THESE DRAWINGS AND SPECIFICATIONS ARE <br /> CONDUIT AND CONDUCTORS AROUN WALLS AND CEILING EXISTING CIRCUIT PREVIOUSLY USED FOR THE SAME LOAD IN INTENDED TO EXPRESS DESIGN INTENT FOR A <br /> AFFECTED BY REMODEL SO THAT DOWN STEAM DEVICES TO THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, PROVIDE NEW PROTOTYPICAL STARBUCKS STORE (WHICH IS <br /> REMAIN STAY POWERED. REMOVE PORTIONS NO LONGER CONNECTION TO IT. SUBJECT TO CHANGE AT ANYTIME)AND DO <br /> REQUIRED BACK TO NEAREST JUNCTION BOX OR TO SOURCE. NOT REFLECT ACTUAL SITE CONDITIONS. <br /> TRACE ALL CIRCUITS IN THE AFFECTED AREAS PRIOR TO O EXISTING BREWER SOFT HEAT DUAL TO BE RELOCATED HERE. NEITHER PARTY SHALL HAVE ANY OBLIGATION <br /> CONSTRUCTION AND RE-LABEL PANELS ACCORDINGLY. FIELD COORDINATE EXACT LOCATION AND REQUIREMENT. IF NOR LIABILITY TO THE OTHER (EXCEPT STATED <br /> POSSIBLE, EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED ABOVE) UNTIL A WRITTEN AGREEMENT IS <br /> J. WORKING CLEARANCES SHALL BE MAINTAINED AND ARE FOR THE SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS FULLY EXECUTED BY BOTH PARTIES. <br /> SUBJECT TO FIELD VERIFICATION PER NEC 110.16. AVAILABLE, PROVIDE NEW CONNECTION TO IT. <br /> K. GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL O EXISTING GRINDER TO BE RELOCATED HERE. FIELD COORDINATE ARCHITECT OF RECORD <br /> BEINSTALLED IN KITCHENS PER NEC 210.8(B)(2). SUBJECT TO EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, EXTEND THE mcg architecture <br /> FIELD VERIFICATION. EXISTING CIRCUIT PREVIOUSLY USED FOR THE SAME LOAD IN o a a 410 THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, PROVIDE NEW <br /> L. GROUND-FAULT CIRCUIT-INTERRUPTER SHALL BE INSTALLED — <br /> O O IN A READILY ACCESSIBLE LOCATION PER NEC 210.8. SUBJECT CONNECTION TO IT. C <br /> TO FIELD VERIFICATION. 10 EXISTING UNDERCOUNTER FRIDGE TO BE RELOCATED HERE. N <br /> M. SIGNS AND OUTLINE LIGHTING SYSTEM EQUIPMENT FOR WET FIELD COORDINATE EXACT LOCATION AND REQUIREMENT. IF <br /> LOCATION USE, OTHER THAN LISTED WATERTIGHT TYPE, POSSIBLE, EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED 15635 Alton Parkway, Suite 100, Irvine, CA 92618 <br /> SHALL BE WEATHERPROOF AND HAVE DRAIN HOLES, AS FOR THE SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS P: 949.553.1117 F:949.474.7056 <br /> NECESSARY, IN ACCORDANCE WITH THE FOLLOWING: DRAIN AVAILABLE, PROVIDE NEW CONNECTION TO IT. <br /> HOLES SHALL NOT BE LARGER THAN 1/2 INCH OR SMALLER <br /> THAN 1/4 INCH. EVERY LOW POINT OR ISOLATED SECTION 11 EXISTING ESPRESSO MACHINE TO BE RELOCATED HERE. FIELD <br /> COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, ti VVV111 <br /> SHALL HAVE AT LEAST ONE DRAIN HOLE; DRAIN HOLES SHALL EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED FOR THEAC I rr»oQROFESStp�q�tLt= <br /> HAVE NO EXTERNAL OBSTRUCTIONS. <br /> 5 <br /> SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, ] <br /> ENGINEERING <br /> (2) N. CALIFORNIA ELECTRICAL CODE REQUIRES THE SERVICE PROVIDE NEW CONNECTION TO IT. c+yz <br /> 400 N McCarthy Blvd. <br /> EQUIPMENT'S MAIN DISCONNECT SWITCH AND FUSE, OR THE Suite 250,Milpitas,CA 95035 <br /> PROVIDE CONNECTION FOR NEW FOOD CASE. FIELD E <br /> Np t, %�� Al <br /> SHORT-CIRCUIT CURRENT VALUE.ALL NEW <br /> CIRCUIT BREAKER, TO BE RATED AT THE AVAILABLE 1� ph:(408)522-5255 ?t *r <br /> COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, _ tz F rr <br /> INDUSTRIAL AND ANUFAC MANUFACTURING ARE SUPPLIED BY AN EXTEND <br /> EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED FOR THE tXfino@acesne60 tttt�1'1FOF CA�Fo` ter <br /> O INDIVIDUAL SERVICE DROP OR LATERAL RATED AT 225 AMPS SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, Copyright©2021 <br /> OR MORE ARE REQUIRED TO HAVE A FAULT CURRENT LETTER PROVIDE NEW CONNECTION AND CONNECT TO CIRCUIT AS <br /> PROVIDED BY PG&E OR THE ELECTRICAL SERVICE PROVIDER SHOWN. <br /> 14 E 20011 E 12508 1 O. EQUIPMENT INTENDED TO BREAK CURRENT AT FAULT LEVELS 13 PROVIDE CONNECTION FOR NEW HOT WATER DISPENSER. FIELD <br /> SHALL HAVE AN INTERRUPTING RATING SUFFICIENT FOR THE COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, <br /> 0 ® ® ❑ SYSTEM VOLTAGE AND THE CURRENT WHICH IS AVAILABLE AT EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED FOR THE <br /> 3 1 4 THE LINE TERMINALS OF THE EQUIPMENT. THERE ARE TWO SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, <br /> o WAYS TO SATISFY THE CODE REQUIREMENT: EITHER SERIES PROVIDE NEW CONNECTION AND CONNECT TO CIRCUIT AS <br /> B-27 B 2311-11 A-V RATED OR FULLY RATED.ANY NEW BREAKERS OR SHOWN. <br /> 10 SUB-PANELS MUST MEET THIS REQUIREMENT. <br /> 14 PROVIDE CONNECTION FOR NEW NITRO FRIDGE. FIELD <br /> P. GC TO NOTIFY SBUX CM + DM IF THERE ARE ANY(E) FLOOR COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, <br /> OUTLETS THAT NEED TO BE RELOCATED OR REMOVED. EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED FOR THE <br /> B- <br /> B- <br /> -21 - 5,27 SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, <br /> 18 � <br /> B- <br /> 4128 I Q ELECTRICAL SYSTEM. FURNISH AND INSTALL ALL NECESSARY PROVISHOWN. NEW CONNECTION AND CONNECT TO CIRCUIT AS •� <br /> 13 P 15749 CONDUIT, WIRE, CONNECTIONS, RECEPTACLES AND <br /> OVERCURRENT PROTECTION NECESSARY TO ENSURE THE (� <br /> III -21 EQUIPMENT FUNCTIONS PROPERLY AND COMPLIES WITH ALL <8> PROVIDE CONNECTION FOR NEW BLENDER. FIELD COORDINATE 0 <br /> O 0° ® ® ® 10 APPLICABLE LOCAL AND NATIONAL CODES. COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, EXTEND THE > Q <br /> 11 EQUIPMENT REQUIREMENTS WITH MANUFACTURER CUT EXISTING CIRCUIT PREVIOUSLY USED FOR THE SAME LOAD IN Q CO <br /> 0 <br /> SHEET PRIOR TO ROUGH-IN. THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, PROVIDE NEW <br /> CONNECTION AND CONNECT TO CIRCUIT AS SHOWN. U W LO <br /> R. ALL FRONT BAR J-BOXES AND OUTLETS SHALL BE SURFACE LIJ 0 L (3) U) <br /> MOUNTED. PROVIDE CONDUITS AS NEEDED AND ONE (1) W 16 PROVIDE CONNECTION FOR NEW UNDERCOUNTER FRIDGE. Q 0 Q <br /> 1 3 2 6 ADDITIONAL SPARE CONDUIT BETWEEN ALL J-BOXES FOR FIELD COORDINATE EXACT LOCATION AND REQUIREMENT. IF Z Q > U O <br /> 1 E 16239 B-2FUTURE ELECTRICAL REQUIREMENTS. ALL J-BOXES SHALL BE POSSIBLE, EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED <br /> POSITIONED TO AVOID OBSTRUCTION OF ANY EQUIPMENT <br /> E 1261 16 SUCH AS REFRIGERATORS AND DISHWASHERS. FOR THE SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS W U W U <br /> AVAILABLE, PROVIDE NEW CONNECTION AND CONNECT TO ­3 M U <br /> B-(30,32) CIRCUIT AS SHOWN. 0 0 <br /> _24 S. REFERENCE LANDLORD WORK LETTER FOR DIVISION OF <br /> 2#10+1#10G 18 0 � C0 L <br /> ELECTRICAL SCOPE U WORK AND COORDINATE WITH PROVIDE CONNECTION FOR NEW WARMING OVEN. FIELD d Lo U <br /> 3/4"C• STARBUCKS CONSTRUCTION MANAGER. 17 <br /> 2 COORDINATE EXACT LOCATION AND REQUIREMENT. IF POSSIBLE, <br /> B-( <br /> A-(29,31) � T. DATA CABLING LOCATED ABOVE HEAD SHALL BE PLENUM. EXTEND THE EXISTING CIRCUIT PREVIOUSLY USED FOR THE STORE #: $981 <br /> 5 B-(34 36) (2) SAME LOAD IN THIS AREA. IF NO SUCH CIRCUIT IS AVAILABLE, <br /> o B-24 a E 20032 1 U.UDATA CABLING LOCATED UNDERGROUND SHALL BE RATED PROVIDE NEW CONNECTION AND CONNECT TO CIRCUIT AS PROJECT #: 23870-070 <br /> FOR BELOW GROUND USE. SHOWN. <br /> 9 PROFILE TYPE: <br /> 8 p B 34,36 18 PROVIDE CONNECTION FOR FUTURE MOBILE ORDER, PAY& ISSUE DATE: 03-05-2021 <br /> ® p 7 0 -2 10+1 10G I PRINT LABELER. FIELD COORDINATE EXACT LOCATION AND PROGRAM MANAGER: <br /> + 4"C. REQUIREMENT. <br /> 1 ® STORE DESIGNER: JESSICA RAMOS <br /> LEED®AP: N/A <br /> ® 2618 16 CHECKED BY: <br /> (2) MCG PROJECT#: <br /> MCG PROJ. MANAGER: HT <br /> (2) MCG PROJ. SPECIALIST: TG <br /> (2) <br /> Revision Schedule <br /> 0 0 <br /> Rev Date By Description <br /> 0 0 <br /> PANEL A" <br /> )q> <br /> PANEL"B" <br /> SHEET TITLE: <br /> ELECTRICAL <br /> POWER DESIGN <br /> 1 Power Plan SCALE: AS SHOWN <br /> Scale: 1/4" = 1'-0" SHEET NUMBER: <br /> E-103 <br />