My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2021
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
C
>
CHEROKEE
>
610
>
2300 - Underground Storage Tank Program
>
PR0521866
>
COMPLIANCE INFO_2021
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
12/29/2021 10:00:02 AM
Creation date
9/1/2021 8:43:09 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2021
RECORD_ID
PR0521866
PE
2371
FACILITY_ID
FA0014852
FACILITY_NAME
California Tracy Connect Inc
STREET_NUMBER
610
Direction
S
STREET_NAME
CHEROKEE
STREET_TYPE
Ln
City
LODI
Zip
95240
APN
04745039
CURRENT_STATUS
01
SITE_LOCATION
610 S CHEROKEE Ln
P_LOCATION
02
P_DISTRICT
004
QC Status
Approved
Scanner
SJGOV\kblackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
35
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SAN J O A R N Environmental Health Department <br /> -:a U ;� i _# �V AMENDED <br /> 11/4/2021 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> CALIFORNIA TRACY CONNECT INC* 610 S CHEROKEE Ln, LODI October 29, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 207 CCR 2716(f)Failure to maintain designated operator inspection reports and all attachments on site for 36 months. <br /> OBSERVATION: Monthly designated operator reports were found on site for 06/25/2021 through 10/15/2021 only. <br /> Per Julio Rose, California Tracy Connect Inc became the new operator on 06/22/2021 and the previous operator did <br /> not provide any past records to them. <br /> REGULATION GUIDANCE: Designated operator inspection reports prior to October 1, 2018 shall be retained on <br /> site for twelve months. Designated operator inspection reports on or after October 1, 2018 shall be retained on site <br /> for thirty-six months. <br /> CORRECTIVE ACTION: Locate and ensure that copies of the previous thirty-six months of designated operator <br /> inspection reports are maintained on site. Submit copies of the missing reports to the EHD. <br /> This is a Class II violation. <br /> 307 HSC 25290.1(c3), 25290.2(c3) Failure to keep water out of the secondary containment system (post-Jul 2003). <br /> OBSERVATION: Liquid was found in the 87 and 91 grade fill sumps. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: Immediately remove this liquid, make a hazardous waste determination per Title 22 <br /> hazardous waste regulations, and manage accordingly. Immediately contact a properly licensed, trained, and <br /> certified contractor to address the water intrusion into the 87 and 91 fill sump under permit and inspection of the <br /> EHD, if needed. <br /> This is a Class II violation. <br /> 319 CCR 2635, 2637.2,2665, 2712 Failure to comply with overfill prevention equipment requirements. <br /> OBSERVATION: Overfill prevention testing was last conducted on 10/16/2018. Overfill prevention testing was due <br /> October 2021 and has not been conducted as of 11/04/2021. <br /> REGULATION GUIDANCE: Overfill prevention equipment inspections were required to be conducted by October <br /> 13, 2018, and every 36 months thereafter, and within 30 days of completion of a repair. <br /> CORRECTIVE ACTION: Immediately schedule this testing and provide 48 hours notification to the EHD. Ensure all <br /> future testing is conducted within required time frames. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> An inspection report was provided to the facility operator on the day of inspection. The inspection report was <br /> amended on 11/04/2021 and replaces the initial report. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> FA0014852 PR0521866 SCO01 10/29/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 8 of 9 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />
The URL can be used to link to this page
Your browser does not support the video tag.