Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Ins ection Report Form <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (One OPE per column) 87 91 DSL <br /> Are both vent and tank riser piping E Yes E Yes E Yes ❑ Yes <br /> secondarily contained? ❑ No ❑ No ❑ No ❑ No <br /> OPE Model OPW OPW OPW <br /> Tank Manufacturer Xerxes Xerxes Xerxes <br /> E Shuts off E Shuts off E Shuts off ❑ Shuts off <br /> Flow Flow Flow Flow <br /> What is the OPE response when ❑ Restricts ❑ Restricts ❑ Restricts ❑ Restricts <br /> activated? Flow Flow Flow Flow <br /> (Check a//that app/y) F1Audible ❑ Audible ❑ Audible ElAudible <br /> Alarm Alarm Alarm Alarm <br /> ❑Visual ❑Visual ❑Visual ❑Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent <br /> E] Yes E] Yes ❑ Yes El Yes <br /> piping that may interfere with the OPE <br /> operation? E No E No E No E] No <br /> At what level in the tank is the OPE set to 106 1/4 105 3/4 105 — - <br /> activate? (Inches from bottom of tank) <br /> What is the percent capacity of the tank in 95% 95% 95% <br /> which the OPE activates? <br /> Is the OPE in proper operating condition <br /> to respond when the stored substance ® Yes ® Yes ® Yes ❑ Yes <br /> reaches the designated regulatory level? ❑ No ❑ No ❑ No ❑ No <br /> 7. SUMMARY OF TESTING RESULTS _ <br /> OPE Inspection Results ® Pass ® Pass E Pass s F- Pass <br /> ❑ Fail ❑ Fail ❑ Fail ❑ Fail <br /> 8. COMMENTS <br /> j <br /> Page 2 of 2 <br />