Laserfiche WebLink
LINE & LEAK DETEC -i TEST REPORT <br /> Site: BAGLEY—SAN JOAQUIN REGIONAL TRANSIT <br /> Identify Time Log of Test Procedures VOLUME REMARKS <br /> Each Line (Military) Ambient Temperature psi READING NET <br /> Weather, Etc. BEFORE AFTER BEFORE AFTER CHANGE Conclusions, Repairs,Comments <br /> DIESEL 0900 PRE-STRETCH -- 70 -- .0630 -- <br /> I <br /> LIME l 0920 -- 60 -- .0580 -- <br /> 0935 58 60 .0580 .0565 -.0015 <br /> 0950 60 60 .0550 .0550 .0000 -.0015 PASS (-.0030) <br /> B. B. 60 0 _0000 .0490 <br /> LINE 2 0921 -- 60 -- 0565 -- <br /> 0936 58 60 .0565 .0550 -.0015 <br /> 0951 60 60 .0550 .0550 .0000 -.0015 PASS (-.0030) <br /> B. B. 60 0 .0000 .0495 <br /> I <br /> I <br /> I <br /> Page 2 of 2 <br />