MECHANICAL SPECIFICATIONS MECHANICAL SYMBOL LEGEND REVISIONS BY <br /> PART 1 - GENERAL PART 2 - PRODUCTS PART 3 - EXECUTION MECHANICAL DUCTWORK MECANICAL ABBREVIATIONS <br /> 1.1 GENERAL CONDITIONS 2.1 DUCTWORKFLEXIBLE SUPPLY AIR DUCT ABV ABOVE <br /> 3.1 SYSTEM BALANCE AND ADJUSTMENT FLEXIBLE RETURN AIR DUCT -------- AD/AP ACCESS DOOR/ACCESS PANEL <br /> 1. THE CONTRACTOR SHALL FURNISH ALL PLANT, LABOR, EQUIPMENT, AND SHALL PERFORM ALL 1. MATERIAL EXPOSED WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME SPREAD RATING OF NOT MORE 1. GENERAL: AFF ABOVE FINISH FLOOR <br /> OPERATIONS IN CONNECTION WITH THE AIR CONDITIONING SYSTEMS(S) AS OUTLINED IN THE THAN 25 AND A SMOKE PRODUCTION OF NOT MORE THAN 50. A. THE HEATING AND AIR CONDITIONING CONTRACTOR SHALL BALANCE THE COMPLETE SYSTEM BEL BELOW <br /> DRAWINGS AND IN STRICT ACCORDANCE WITH THE CONDITIONS OF THE CONTRACT. ANY A. ALL SHEET METAL DUCTWORK SHALL BE MADE OF COMMERCIAL GRADE GALVANIZED STEEL. AND SHALL SUBMIT TWO (2) COPIES OF THE BALANCING REPORT TO THE ENGINEER FOR RIGID SUPPLY AIR DUCT CFH CUBIC FEET PER HOUR (1000 BTU) <br /> INCIDENTAL WORK NOT SHOWN OR SPECIFIED WHICH CAN REASONABLY BE TAKEN OR B. BROKEN PIECES IN COATING MADE IN FORMING SHALL BE COMPLETELY SOLDERED OVER. EVALUATION AND APPROVAL. _ CFM CUBIC FEET PER MINUTE ■ <br /> INFERRED AS BELONGING TO THE WORK AND NECESSARY TO PROVIDE THE SYSTEM DESCRIBED C. WEIGHTS OF SHEETS SHALL NOT BE LESS THAN THE FOLLOWING: B. THIS REPORT SHALL INCLUDE AS A MINIMUM, BUT NOT BE LIMITED TO, THE FOLLOWING DESIGN -- <br /> OR SHOWN SHALL BE THE CONTRACTOR'S RESPONSIBILITY, THE WORK SHALL BE COMPLETE AND SIZE OF DUCTS US GAUGE GALV IRON AND ACTUAL INFORMATION: HORSEPOWER, BRAKE HORSEPOWER, REVOLUTIONS PER MINUTE, RIGID RETURN AIR DUCT _ CLG CEILING <br /> READY FOR SERVICE AS SHOWN AND/OR SPECIFIED, AND BE SATISFACTORY TO THE ARCHITECT. 0"TO 12" 26 ACTUAL AMPERAGE AND FULL LOAD RATED CURRENT OF ALL MOTORS AND FANS; CUBIC FEET r CONC. CONCRETE <br /> 2. REFER TO ARCHITECTURAL SPECIFICATIONS FOR CORRELATIONS AND GENERAL REQUIREMENTS. 13"TO 30" 24 PER MINUTE, STATIC PRESSURE AND OUTLET VELOCITY AND CUBIC FEET PER MINUTE OF EACH (E) EXISTING <br /> 31"TO 54" 22 OUTLET OF EACH UNIT OR ZONE; AIR TEMPERATURES OF ALL ROOMS SERVICED BY AIR MECHANICAL SYMBOLS <br /> GPM GALLONS PER MINUTE 2 <br /> 1.2 WORK INCLUDED 55"AND LARGER 20 <br /> DISTRIBUTION SYSTEM, AND ALL OTHER INFORMATION REQUIRED TO ESTABLISH COMPLETELY MBH THOUSANDS OF BTU'S PER HOUR <br /> BALANCED SYSTEM. VOLUME DAMPER I ❑ <br /> 1. THE SYSTEMS TO BE INSTALLED CONSIST ESSENTIALLY OF THE FOLLOWING: 2.2 INSULATED FLEXIBLE DUCT 2. ALLOWANCE SHALL BE MADE FOR AIR FILTER RESISTANCE A THE TIME DUCT DROP/RISE (N) NEW <br /> A. EXHAUST FANS AND DUCTWORK. 3. STATIC PRESSURE READINGS SHALL BE TAKEN WITH AN INCLINED MANOMETER; AIR VELOCITY ,"l NIMC NOT IN MECHANICAL CONTRACT UJ tO <br /> B. SUPPLY AND RETURN DUCTWORK, AND CEILING OUTLETS. 1. FLEXIBLE DUCT MAY BE USED ON SUPPLY& RETURN DUCTS 18" & SMALLER AND SHALL BE READINGS SHALL BE TAKEN WITH INSTRUMENTS OF RECENT CALIBRATION. THE FINAL VELOCITY OSA OUTSIDE AIR L <br /> C. TESTING AND ADJUSTING OF THE COMPLETE SYSTEM. THERMAFLEX MODEL MK-E CONSISTING OF AN INNER CORE, INSULATION AND AN OUTER READINGS SHALL BE TAKEN WITH AN ALNOR VELOMETER, ANEMOTHERN, OR A VANE TYPE ANEMETER EXHAUST FAN <br /> 2. <br /> POC POINT OF CONNECTION V <br /> 2. OTHER ITEMS AS MAY BE SPECIFIED OR SHOWN ON THE DRAWINGS. MOISTURE BARRIER. THE INNER CORE SHALL BE CONSTRUCTED OF A CHLORINATED CALIBRATED PRIOR TO THE TEST AND RECALIBRATED AT THE END OF THE TEST. m CO <br /> POLYETHYLENE (CPE) BONDED TO THE COATED WIRE HELX FOR MAXIMUM STRENGTH AND 4. TESTS SHALL BE RUN WIT SUPPLY, RETURN, AND EXHAUST SYSTEMS OPERATING WITH ALL DOORS, SMOKE DETECTOR SD W Ln �TCP TEMPERATURE CONTROL PANEL i <br /> 1.3 WORK NOT INCLUDED DURABILITY. AN INSULATING BLANKET WOVEN OF FIBERGLASS SHALL ENCASE THE INNER CORE AND WINDOWS, ETC., CLOSED OR UNDER REGULAR TRAFFIC. UC 1" DOOR UNDERCUT <br /> SHALL BE SHEATHED WITH AN OUTER VAPOR BARRIER OF METALLIZED POLYESTER FILM. THE VAPOR 5. CONTRACTOR SHALL ADJUST DEFLECTION OF ALL SUPPLY OUTLETS TO INSURE PROPER AND UNIFORM THERMOSTAT OT V VALVE L's <br /> 1. THE FOLLOWING IS NOT INCLUDED IN THIS PARTICULAR WORK: BARRIER SHALL BE .05 PERM PER ASTM E96, PROCEDURE A. THE FLEXIBLE DUCT SHALL BE RATED FOR AIR DISTRIBUTION THROUGHOUT THE AREAS SERVED BY SUCH OUTLETS. I <br /> A. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LINE VOLTAGE WIRING, AND ALL LINE VOLTAGE A MAXIMUM WORKING VELOCITY OF 5500 FPM AND SHALL BE CERTIFIED BY THE UNDERWRITERS CONDENSATE DRAIN LINE - CD <br /> CONDUIT, DISCONNECTS, MANUAL STARTERS, AND CONNECT UP ALL MOTORS COMPLETE. AIR LABORATORIES UNDER THEIR UL 181 STANDARDS AS CLASS 1 DUCT, AND BEAR UL STAMP. 3.2 TEST AND ADJUSTMENT U Q .. <br /> CONDITIONING CONTRACTOR TO PROVIDE WIRING DIAGRAM AS REQUESTED. 2. FLEXIBLE DUCTS SHALL BE SUPPORTED AT 4"-0"O.C. WITH 3"WIDE 28 GAUGE STEEL HANGER MECHANICAL REGISTERS <br /> COLLAR ATTACHED TO THE STRUCTURE WITH AN APPROVED DUCT HANGER. COLLARS SHALL HAVE 1. UPON COMPLETION OF THE WORK, ALL EQUIPMENT AND SYSTEMS SHALL BE OPERATED AND V <br /> 1.4 WORKMANSHIP HEMMED EDGES TO PREVENT CUTTING OF FLEXIBLE DUCT. INSTALLATION SHALL MINIMIZE SHARP TESTED FOR A PERIOD OF AT LEAST THREE (3) CONSECUTIVE DAYS TO DEMONSTRATE THEIR uj Q ❑ <br /> RADIUS TURNS OR OFFSETS. SATISFACTORY OVERALL OPERATION. ON THE LAST DAY OF THIS PERIOD, THE CONTRACTOR SHALL SUPPLY AIR REGISTER ® n ❑ N <br /> WHERE OTHER INSTRUCTIONS ARE NOT GIVEN, EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE A. DUCT MATERIAL SHALL HAVE A MINIMUM 'R' VALUE OF 8. ARRANGE FOR AN ACCEPTANCE TEST AND FINAL INSPECTION TO BE CONDUCTED BY THE ENGINEER IN .. <br /> 1 <br /> WITH THE RECOMMENDATIONS OF THE MANUFACTURER AND THE BEST STANDARD PRACTICE FOR B. FLEXIBLE DUCTS MAY BE USED TO CROSS SEISMIC JOINTS WITHOUT OFFSETS. THE PRESENCE OF THE CONTRACTOR OR HIS REPRESENTATIVE. THE ENGINEER SHALL BE ❑ <br /> THIS TYPE OF WORK. C. ALL MATERIAL EXPOSED WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME-SPREAD RATING OF NOTIFIED OF THIS MEETING AT LEAST ONE WEEK IN ADVANCE OF THE TIME PROPOSED BY THE J N X <br /> NOT MORE THAN 25 AND A SMOKE-DEVELOPED RATING OF NOT MORE THAN 50. CONTRACTOR AND A MUTUALLY AGREEABLE TIME ARRANGED. THE CONTRACTOR SHALL MAKE ALL 3: <br /> ❑ W Q <br /> 1.5 RULES, REGULATIONS, AND CODES D. DUCT LEAKAGE SHALL NOT BE MORE THAN 6%OF TOTAL AIR FLOW AND SHALL BE VERIFIED. NECESSARY ADJUSTMENTS AND CORRECTIONS TO THE SYSTEMS PRIOR TO ACCEPTANCE TEST SO RETURN AIR GRILL a \ Q W <br /> THAT THE SYSTEMS ARE OPERATING SMOOTHLY AND PROPERLY AND ARE ABSOLUTELY READY <br /> 1. ALL WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE WITH THE LATEST RULES, CODES, AND 2.3 BALANCING DAMPERS FOR CHECK AND ACCEPTANCE AT THIS TIME. ElQ <br /> REGULATIONS OF THE FOLLOWING: 2. ANY EQUIPMENT, SYSTEM, OR WORK FOUND DEFICIENT DURING THE TEST SHALL BE REPLACED OR ❑ <br /> A. NATIONAL FIRE PROTECTION ASSOCIATION. 1. BALANCING DAMPERS SHALL BE FURNISHED AND INSTALLED AT LOCATIONS INDICATED ON THE REVISED AS REQUIRED TO THE ENTIRE SATISFACTION OF THE ENGINEER. Z <br /> B. STATE FIRE MARSHAL. DRAWINGS. 3. DURING THIS TIME, A REPRESENTATIVE OF THE ENGINEER SHALL BE INSTRUCTED IN THE PROPER <br /> C. PART- 5, T24 CALIFORNIA CODE OF REGULATIONS. 2. DAMPERS SHALL HAVE LOCKING AND INDICATING QUADRANT PARKER-KALON COMPANY'S, ELGIN, OR CARE AND OPERATION OF THE EQUIPMENT AND CONTROLS. A SET OF TYPEWRITTEN <br /> EQUAL, DAMPERS INSTALLED IN INACCESSIBLE LOCATIONS SHALL HAVE DAMPER RODS EXTENDED INSTRUCTIONS GIVING PERTINENT OPERATING DATA SHALL BE FRAMED UNDER GLASS AND <br /> D. STATE HEALTH DEPARTMENT. <br /> E. STATE INDUSTRIAL ACCIDENT COMMISSION'S SAFETY ORDERS. AND TERMINATED WITH CEILING, WITH A YOUNG COMPANY'S ELGIN, OR EQUAL, ADJUSTABLE MOUNTED IN A LOCATION AS DIRECTED BY THE ENGINEER. THIS INCLUDES WIRING AND W Ln <br /> COVER CONCEALED DAMPER REGULATOR. SCHEMATIC DIAGRAMS OF ALL CONTROLS, THERMOSTATS, ETC. m W <br /> Ln <br /> F. RULES OF LOCAL UTILITY. 3. DAMPERS IN SQUARE OR RECTANGULAR DUCTS NOT SHOWN AS SPLATTER OR BUTTERFLY J W <br /> G. CALIFORNIA MECHANICAL CODE. DAMPERS SHALL BE OF THE MULTI-LOUVER TYPE ARRANGED FOR OPPOSED BLADE OPERATION <br /> H. CALIFORNIA BUILDING CODE. <br /> J. CALIFORNIA PLUMBING CODE. AND SHALL BE CONTROLAIR, KRUEGER, OR EQUAL TO CONTROLAIRE OPP-MD. BUTTERFLY AND W <br /> SPLITTER TYPE DAMPER BLADES SHALL BE OF U.S. 16 GAUGE GALVANIZED STEEL, MINIMUM, a W E <br /> K. CALIFORNIA ELECTRIC CODE. AND SHALL HAVE A MINIMUM SHAFT SIZE OF 3/8". DAMPERS IN ROUND DUCTS SHALL BE SINGLE En2. RULING AND INTERPRETATIONS OF THE ENFORCING AGENCY WILL BE CONSIDERED PART OF THE BLADE TYPE, CONTROL AIR OR EQUAL, WITH EXTENDED SHAFT AS REQUIRED. <br /> REGULATIONS. 4. MARK DUCTS TO INDICATE PERMANENT DAMPER POSITION AFTER THE SYSTEM HAS BEEN TESTED AND <br /> 3. NOTHING IN THESE SPECIFICATIONS IS TO BE CONSTRUED TO PERMIT WORK NOT CONFORMING ❑ I <br /> TO THE ABOVE, AND EXPENSE IN COMPLIANCE WITH THE ABOVE SHALL BE BORNE BY THE BALANCED. Q <br /> CONTRACTOR. <br /> 4. WHENEVER THE SPECIFICATIONS AND DRAWINGS REQUIRE HIGHER STANDARDS OR LARGER 2.4 FLEXIBLE CONNECTIONS ❑ 0) <br /> SIZES THAN THOSE REQUIRED BY THE ORDINANCES AND STATUTES, THE SPECIFICATIONS ANDW r <br /> DRAWINGS SHALL TAKE PRIORITY OVER THE SPECIFIC ORDINANCES AND STATUTES. FLEXIBLE CONNECTIONS SHALL BE FURNISHED AND INSTALLED WHERE SHOWN. DUCT <br /> CONNECTIONS SHALL ALSO BE FURNISHED AND INSTALLED WHERE SHOWN. DUCT CONNECTIONS I 0 N <br /> 1.6 SITE EXAMINATION AND CONDITIONS SHALL BE VENT-FABRICS, BAUER AND BLACK FIBERGLASS THERMOSETTING ADHESIVE TAPES NO. 263 <br /> AND 281. APPLY PER MANUFACTURER'S RECOMMENDATIONS. WIDTH OF FLEXIBLE <br /> THE CONTRACTOR SHALL EXAMINE THE SITE, VERIFY DIMENSIONS AND LOCATIONS AGAINST THE CONNECTIONS SHALL BE SUFFICIENT TO ALLOW ONE INCH (1") MINIMUM FREE SPACE BETWEEN TWO tD I <br /> DRAWINGS AND INFORM HIMSELF OF ALL CONDITIONS UNDER WHICH WORK IS TO BE DONE BEFORE METAL COLLARS TO BE CONNECTED. PROVIDE COVER OVER FLEX-CONNECTONS TO PROTECT THEM a <br /> SUBMITTING HIS PROPOSAL. NO ALLOWANCE WILL BE MADE IN HIS BEHALF FOR EXTRA EXPENSE ON FROM THE SUN. <br /> ACCOUNT OF ERROR. 0 <br /> 2.5 FILTERS <br /> 1.7 AS BUILT DRAWINGS <br /> 1. GENERAL <br /> 1. SUPPLEMENTING THE REQUIREMENTS OF THE GENERAL CONDITIONS AND SUPPLEMENTARY GENERAL A. AIR FILTERS SHALL BE OF AN APPROVED TYPE TESTED IN ACCORDANCE WIT TEST METHOD El <br /> CONDITIONS, AS-BUILT DRAWINGS SHALL SHOW INVERT ELEVATIONS OF SANITARY SEWERS, RAIN SCFM-12-71-1 AS SHOWN IN PART 12, T-24, CALIFORNIA CODE OF REGULATIONS. PREFORMED <br /> WATER LEADERS AND STORM SEWERS OF CRITICAL LOCATIONS, LOCATIONS OF SHUT-OFF VALVES FILTERS HAVING COMBUSTIBLE FRAMING SHALL BE TESTED AS COMPLETE ASSEMBLY. <br /> AND STUB-OUTS FOR FUTURE, AND ALL CHANGES MADE DURING THE COURSE OF THE WORK. FURNISH B. AIR FILTERS IN ALL OCCUPANCIES SHALL BE CLASS 2 OR BETTER, AS DEFINED IN THE TEST <br /> REPRODUCIBLE DRAWINGS WHEN WORK IS COMPLETE. METHOD ABOVE. <br /> 2. THE GRADE OR QUALITY OF MATERIALS DESIRED IS INDICATED BY THE TRADE NAMES OR CATALOG C. AIR FILTERS SHALL BE ACCESSIBLE FOR CLEANING OR REPLACEMENT. c,EO p RC,S, <br /> NUMBERS STATED HEREIN. D. THE CONTRACTOR SHALL FURNISH THE OWNER WITH ONE (1)ADDITIONAL COMPLETE FILTER OBJ. 13 <br /> 3. DIMENSIONS, SIZES, AND CAPACITIES SHOWN ARE A MINIMUM AND SHALL NOT BE CHANGED WITHOUT CHANGE FOR ALL UNITS UPON ACCEPTANCE OF THE MECHANICAL SYSTEM. p Oji <br /> PERMISSION OF THE ARCHITECT. 2. UNIT FILTERS: ALL FILTERS SHALL BE AMERICAN FILTER-AMER-GLAS AG-5, FARR, LOW VELOCITY 2 <br /> FILTERS, 2"THICK, WITH FRAMES AND ACCESS PANELS. ~ C-25449 p <br /> 1.8 MATERIAL LIST AND SUBSTITUTIONS 2.6 GRILLES, REGISTERS, AND DIFFUSERS s Q <br /> 63021 <br /> RENEWAL DATE <br /> 1. PRIOR TO COMMENCEMENT OF WORK, AND WITHIN 35 DAYS AFTER SIGNING OF THE CONTRACT BY 1. CEILING SUPPLY DIFFUSERS SHALL BE METALAIRE MODULAR CORE (SERIES 9000) OR EQUAL, WITH �T 0 <br /> THE OWNER AND GENERAL CONTRACTOR, THIS CONTRACTOR SHALL SUBMIT IN QUINTUPLE TO LAY-IN OR SURFACE TYPE FRAME, AS SPECIFIED, OPPOSED BLADE DAMPER AND EXTRACTOR. OF CAL�� <br /> THE ARCHITECT FOR APPROVAL A COMPLETE LIST OF EQUIPMENT AND MATERIALS TO BE DIFFUSER SHALL BE PROVIDED WITH FACTORY APPLIED OFF WHITE FINISH, ALL AS SCHEDULED ON THE <br /> FURNISHED, INCLUDING ALL SUBSTITUTIONS. PARTIAL OR INCOMPLETE LISTS OF MATERIALS WILL DRAWINGS. <br /> NOT BE CONSIDERED. NO SUBSTITUTIONS WILL BE CONSIDERED THEREAFTER. ONLY ONE (1) 2. CEILING RETURN GRILLE AND EXHAUST SHALL BE METALAIRE (SERIES SRH) OR EQUAL, MADE OF STEEL <br /> REQUEST FOR SUBSTITUTION WILL BE CONSIDERED ON EACH ITEM OF MATERIAL OR WITH FACTORY APPLIED FINISH TO MATCH THE SUPPLIES, ALL AS SCHEDULED ON THE DRAWINGS. <br /> EQUIPMENT. 3. WALL SUPPLIES SHALL BE METALAIRE V4004 WITH OPPOSED BLADE DAMPER. REGISTER SHALL BE <br /> 2. IF THE CONTRACTOR DESIRES TO MAKE A SUBSTITUTION, HE SHALL SUBMIT COMPLETE INFORMATION RY APPLIED WHITE FINISH. <br /> OR CATALOG DATA TO SHOW THE QUALITY OF THE EQUIPMENT OR MATERIAL OFFERED TO THAT 4. WALL RETURN SHALL PROVIDED WITH FACTORY <br /> METALAIRE RH WITH A WHITE FINISH TO MATCH THE SUPPLY. <br /> SPECIFIED. NO SUBSTITUTION WILL BE ALLOWED UNLESS REQUESTED AND APPROVED IN WRITING. 5. DOOR LOUVERS SHALL BE J &j SERIES 700 PRIME PAINTED. <br /> MATERIALS OF EQUAL MERIT AND APPEARANCE IN THE OPINION OF THE ARCHITECT WILL BE OUTSIDE AIR AND COMBUSTION AIR LOVERS SHALL BE BUSKIN WITH INSECT SCREEN AND <br /> APPROVED FOR USE. ARCHITECT RESERVES THE RIGHT TO REQUIRE ORIGINALLY SPECIFIED ITEM. 6. MOUNTING FRAME. LOUVERS SHALL BE PRIME PAINTED. CrVrY1b� <br /> 3. INSTALLATION OF APPROVED SUBSTITUTION IS THE CONTRACTOR'S RESPONSIBILITY. ANY CHANGES 7 GRILLES SHALL BE SELECTED AND APPROVED BY MANUFACTURER TO OPERATE WITHOUT <br /> REQUIRED FOR INSTALLATION OF APPROVED SUBSTITUTED EQUIPMENT MUST BE MADE WITHOUT <br /> ADDITIONAL COST. OBJECTIONABLE NOISE OR DRAFT. C O O ICI e S <br /> 4. SUBMIT TO ARCHITECT FOR APPROVAL, WITHIN A REASONABLE TIME AFTER AWARD OF CONTRACT AND 2.7 EQUIPMENT INTERIOR TENANT <br /> IN AMPLE TIME TO AVOID DELAY OF CONSTRICTION, SHOP DRAWINGS OR SUBMITTALS ON ALL ITEMS IMPROVEMENT <br /> OF EQUIPMENT AND MATERIALS COVERED IN LIST MENTIONED ABOVE. SHOP DRAWINGS SHALL BE <br /> SUBMITTED IN FIVE (5) COPIES AND IN COMPLETE PACKAGE. PARTIAL SUBMITTALS WILL NOT BE 1. INLINE EXHAUST FAN: <br /> CONSIDERED. A. INLINE EXHAUST FANS SHALL HAVE THE CAPACITY AS SHOWN ON THE DRAWINGS. THEY SHALL LOCATION <br /> INCLUDE WALL OR ROOF CAP AS APPLICABLE, AND REQUIRED DUCTWORK. FANS SHALL BE 864 W. BENJAMIN HOLT DR. <br /> 1.9 FEES, PERMITS, AND UTILITY SERVICES CONTROLLED BY WALL SWITCHES. EXHAUST FAN SHALL BE SCHEDULED ON THE DRAWINGS STOCKTON, CA <br /> AND BE COMPLETE AS FOLLOWS: 95207 <br /> THIS CONTRACTOR SHALL ARRANGE TO OBTAIN AND TO PAY FOR ALL PERMITS AND SERVICE <br /> B. MOTOR AND FAN SHALL BE MOUNTED ON RUBBER ISOLATORS AND BE VIBRATION FREE AND A.P.N.: 09741060 CHARGES REQUIRED IN THE INSTALLATION OF HIS WORK, ARRANGE FOR REQUIRED INSPECTIONS, A QUIET OPERATING. CAPACITY AND RPM SHALL BE AS SCHEDULED ON THE DRAWINGS. <br /> ND SECURE APPROVALS FROM AUTHORITIES HAVING JURISDICTION. CONTRACTOR SHALL ARRANGE 08 TEMPERATURE CONTROL FRANCHISE OWNER <br /> 2. <br /> FOR UTILITY CONNECTIONS AND PAY CHARGES INCURRED, INCLUDING EXCESS SERVICE CHARGES, IF KTK CO. <br /> ANY. 3966 GLEN ABBY CIRCLE <br /> 1. GENERAL: THE WIRING AND LOW VOLTAGE TEMPERATURE CONTROL EQUIPMENT IN ACCORDANCE STOCKTON, CA <br /> 1.1 GUARANTEE WITH THE WIRING DIAGRAMS AND THE FUNCTIONAL OPERATION OF THE TEMPERATURE CONTROL 95219 <br /> SYSTEM SHALL BE THE WIRING, AND ALL LINE AND LOW VOLTAGE CONDUIT, DISCONNECTS, <br /> AFTER COMPLETION OF THE INSTALLATION OF EQUIPMENT HEREIN SPECIFIED, THE CONTRACTOR MANUAL AND AUTOMATIC STARTERS, AND CONNECT UP ALL MOTORS COMPLETE. <br /> SHALL GUARANTEE SAME AGAINST DEFECTS OF WORKMANSHIP OR MATERIAL FOR A PERIOD OF 2. DRAWINGS OF TEMPERATURE CONTROL SYSTEM ARE DIAGRAMMATIC ONLY, AND ANY APPARATUS NOT <br /> ONE (1) YEAR. IF WITHIN THE SPECIFIED PERIOD FROM THE DATE OF ACCEPTANCE ANY OF THE SHOWN, SUCH AS RELAYS, ACCESSORIES, ETC., BUT REQUIRED TO MAKE THE SYSTEM OPERATIVE <br /> SYSTEM IN PROVEN TO BE DEFECTIVE IN WORKMANSHIP AND/OR MATERIAL, IT WILL BE ADJUSTED, TO THE COMPLETE SATISFACTION OF THE ARCHITECT SHALL BE FURNISHED AND INSTALLED DRAWN <br /> REPAIRED, OR REPLACED FREE OF CHARGE BY THIS CONTRACTOR. WITHOUT ADDITIONAL COST. TAF <br /> 3. ALL ELECTRIC CONNECTIONS TO BE IDENTIFIED AND LABELED AS TO FUNCTION AND POSITION WITH <br /> 1.11 ACCESSIBILITY PERMANENTLY ENGRAVED NAMEPLATES. CHECKED <br /> 4. ALL EQUIPMENT FURNISHED BY THIS CONTRACTOR THAT IS NORMALLY WIRED BEFORE SLW <br /> CONTRACTOR SHALL BE RESPONSIBLE FOR THE SUFFICIENCY OF SIZE AND THICKNESS OF PARTITIONS INSTALLATION SHALL BE FURNISHED COMPLETELY WIRED. TEMPERATURE CONTROL WIRING DATENORMALLY PERFORMED IN THE FIELD WILL BE FURNISHED AND INSTALLED BY THE MECHANICAL 5/25/2021 <br /> FOR ADEQUATE INSTALLATION OF HIS WORK, ANY EQUIPMENT REQUIRING ACCESS FOR OPERATION CONTRACTOR. <br /> OR SERVICE SHALL BE MADE ACCESSIBLE BY THE USE OF ACCESS DOORS AS REQUIRED. 5. PRIOR TO INSTALLATION, THE MECHANICAL CONTRACTOR SHALL SUBMIT DIAGRAMS, COMPONENT SCALE <br /> DATA AND DESCRIPTION OF SEQUENCE OF OPERATION TO ARCHITECT FOR APPROVAL. AS SHOWN <br /> 6. ENTIRE SYSTEM SHALL BE GUARANTEED FOR ONE YEAR WITH EMERGENCY SERVICE FOR AN JOB NO. <br /> ADDITIONAL YEAR WITHOUT CHARGE TO THE OWNER FROM THE DATA OF ACCEPTANCE OF THE 21-136 <br /> COMPLETED BUILDING. AFTER COMPLETION OF THE INSTALLATION, THE MECHANICAL <br /> CONTRACTOR SHALL REGULATE AND ADJUST ALL THERMOSTATS, DAMPERS, MOTORS AND OTHER SHEET <br /> TEMPERATURE CONTROL EQUIPMENT PROVIDED UNDER THIS CONTRACT. <br /> 7. ENTIRE SYSTEM SHALL BE AS SHOWN ON THE DRAWINGS. mmi no <br /> OF SHEETS <br />