ELECTRICAL SPECIFICATIONS ELECTRICAL SYMBOL LEGEND REVISIONS BY <br /> PART 1 - GENERAL PART 2 - PRODUCTS PART 3 - EXECUTION LIGHTING SYMBOLS ELECTRICAL SYMBOLS <br /> 1.1 GENERAL NOTES 2.1 WIRING DEVICES 3.1 SUBMITTALS 24 x 48 LIGHT FIXTURE 120 VOLT DUPLEX WALL OUTLET <br /> +15"A.F.F. TO BOTTOM OF BOX <br /> 1. SEE ARCHITECTURAL DRAWINGS FOR ALL APPLICABLE CODES 1. UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS (BROWN, 1. PROVIDE THE FOLLOWING SUBMITTALS FOR REVIEW AND APPROVAL. � 120 VOLT FOURPLEX WALL OUTLET <br /> 2. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING POWER AND PHONE WHITE, BREY, BEIGE OR IVORY) AS SELECTED BY THE ARCHITECT: A. PANEL BOARDS +15"A.F.F. TO BOTTOM OF BOX <br /> SERVICES AT SITE PRIOR TO BIDDING. SERVICES SHALL CONFORM TO UTILITY COMPANY B. LIGHT FIXTURES 24 x 24 LIGHT FIXTURE <br /> REQUIREMENTS, ELECTRICAL CONTRACTOR SHALL ARRANGE FOR SERVICE INSTALLATION PER UTILITY WIRING DEVICES LEVITION# HUBBELL# P & S# C. SERVICE SWITCHBOARD 120 VOLT DUPLEX CEILING OUTLET <br /> ■ <br /> COMPANY REQUIREMENTS. ALL SERVICE INFORMATION AND LOCATIONS SHOWN ON THESE 24 x 24 LIGHT FIXTURE 120 VOLT COUNTERTOP OUTLET <br /> PLANS ARE ASSUMED, TO BE VERIFIED WITH THE RESPECTIVE UTILITY COMPANIES AND MODIFIED AS SINGLE POLE SWITCH 1221 1221 20AC1 3.2 WORKING CLEARANCES FOR PANELS & SWITCHBOARDS <br /> REQUIRED TO SUIT. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CONTACTING THE <br /> THREE WAY SWITCH 1223 1223 20AC3 +44"A.F.F. TO BOTTOM OF BOX <br /> UTILITIES COMPANIES IN A TIMELY FASHION TO OBTAIN AND COORDINATE THIS INFORMATION. DUPLEX CONV. OUT. 15A 5262 5262 5262 COORDINATE WITH OTHER TRADES TO ENSURE CODE REQUIRED WORKING CLEARANCES, <br /> DUPLEX GFI CONVOUTGF5262 O RECESSED CAN LIGHT FIXTURE � 120 VOLT WEATHERPROOF OUTLET <br /> . . <br /> 3. ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL LICENSES, PERMITS, ETC. REQUIRED TO ACCESS, ETC. FOR PANELS AND SWITCHBOARDS PER C.E.C. 110.26 AND ARTICLE 408. 120 VOLT DUPLEX WALL OUTLET <br /> 2 <br /> CARRY ON AND COMPLETE THE WORK. PENDANT LIGHT FIXTURE HALF-SWITCHED <br /> 4. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, TRANSPORTATION AND PERFORM 2.2 DEVICE PLATES 3.3 OPERATIONS AND MAINTENANCE MANUALS +15"A.F.F. TO BOTTOM OF BOX ❑ <br /> ALL OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER EXECUTION AND <br /> COMPLETION OF ALL"ELECTRICAL WORK"WHETHER SPECIFICALLY MENTIONED OR NOT; ALL AS 1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE SMOOTH NYLON OR APPROVED EQUAL UNLESS 1. PROVIDE AS-BUILT DRAWINGS. WALL SCONSE LIGHT FIXTURE 120 VOLT FOURPLEX WALL OUTLET UJ ko <br /> INDICATED, SPECIFIED HEREIN, AND/OR IMPLIED THEREBY TO CARRY OUT THE APPARENT INTENT OTHERWISE NOTED. 2. PROVIDE THREE SETS OF OPERATION AND MAINTENANCE MANUALS FOR POWER, LIGHTING ANDHALF-SWITCHED L r <br /> THEREOF. 2. TELEPHONE (AND COMPUTER SIGNAL) PLATES SHALL BE PROVIDED BY OWNER'S VENDOR UNLESS SIGNAL SYSTEMS. EXIT ILLUMINATED EXIT SIGN +15"A.F.F. TO BOTTOM OF BOX V co5. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS' LABORATORIES, OTHERWISE NOTED ON PLANS. 3. ASSEMBLE EACH OPERATIONS AND MAINTENANCE MANUALS SET IN STANDARD HARDBACK, 3-RING <br /> INC., SHALL MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE 3. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL PLATES. JO <br /> BINDERS. DO NOT EXCEED BINDER FILL OF 50 PERCENT: i.e., 1-INCH THICKNESS OF PAPER IN 2-INCH JUNCTION BOX � W Ln <br /> BEEN ESTABLISHED AND LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. WEATHERPROOF COVERS TO BE SNAP TYPE COVERS. rl <br /> BINDER. USE TABULAR DIVIDERS TO ORGANIZE THE MATERIALS. MARK EACH DIVIDER ACCORDING TO CEILING FAN THERMOSTAT <br /> 6. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE AND (SUB) SECTION NUMBER AND NAME. O +48" A.F.F. TO TOP OF CONTROLS <br /> LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, CONTRACTOR SHALL MAKE 2.3 SUPPORTS I ul <br /> USE OF ALL DATA IN ALL CONTRACT DOCUMENTS AND VERIFY THIS INFORMATION AT THE SITE. 3.4 TESTING SD CEILING MOUNT SMOKE DETECTOR V .-. <br /> CONTRACTOR SHALL BE RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID 1. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL ELECTRICAL El Q <br /> INTERFERENCE WITH OTHER TRADES. ENCLOSURES, CONDUITS AND EQUIPMENT. 1. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS AND IMPROPER OS CEILING MOUNT V Ql <br /> 7. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THWN UNLESS OTHERWISE NOTED OR 2. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, TO METAL WITH MACHINE GROUNDS. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND GROUNDS BEFORE ANY SWITCHING SYMBOLS OCCUPANCY SENSOR ❑ <br /> REQUIRED BY CODE. SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION ANCHORS AND MACHINE SCREWS OR FIXTURES OR EQUIPMENT ARE CONNECTED AND WHERE SUCH TESTS INDICATE FAULTY INSULATION uj <br /> 8. ALL LUMINARIES AND BALLASTS SHALL BE CERTIFIED BY THE MANUFACTURER TO THE CALIFORNIA BOLTS. OR OTHER DEFECTS, THEY SHALL BE LOCATED, REPAIRED AND RETESTED AT THE CONTRACTOR'S SEE DRAWING E-1.1 FOR LIGHT SWITCH DS CEILING MOUNT DAYLIGHT SENSOR N <br /> ENERGY COMMISSION. ALL FLUORESCENT FIXTURES TO BE LAMPED WITH F032, T8, 410OK LAMPS OR EXPENSE. PROVIDE ALL INSTRUMENTS TO MAKE SUCH TESTS. LEGEND AND SPECIFICATIONS <br /> APPROVED EQUAL, AND HAVE AN ENERGY SAVING "A" SOUND RATED ELECTRONIC BALLAST OR EQUAL, 2.4 NAMEPLATES & IDENTIFICATION 2. DEMONSTRATE TO THE OWNER AND THE ARCHITECT, THAT THE ENTIRE INSTALLATION IS COMPLETE, IN PS ROOF MOUNT PHOTOCELL �/ <br /> UNLESS OTHERWISE SHOWN. ALL H.I.D. LIGHT FIXTURES SHALL HAVE HIGH POWER FACTOR BALLASTS. PROPER OPERATING CONDITION AND THAT THE CONTRACT HAS BEEN PROPERLY AND FULLY X <br /> 9. FLASH AND COUNTERFLASH ALL ITEMS PASSING THROUGH THE ROOF. FLASHING SHALL BE INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, ETC. NAMEPLATES SHALL EXECUTED. = O W Q <br /> COMPATIBLE WITH ROOFING SYSTEM. E FUSED DISCONNECT SWITCH W <br /> 10. THE OWNER RESERVES THE RIGHT TO RELOCATE ALL LIGHTING, OUTLETS AND SWITCHES BEFORE BE SECURELY FASTENED TO THE EQUIPMENT WITH #4 PHILLIPS ROUND HEAD CADMIUM PLATED SELF-TAPPING <br /> SCREWS, BRASS BOLT. 3.5 CERTIFICATE OF COMPLETION <br /> THEY ARE ROUGHED IN AT NO EXTRA COST. MANUAL MOTOREl <br /> 11. RECEPTACLES IN RATED WALLS SHALL HAVE A MINIMUM OF 24" HORIZONTAL SEPARATION FROM 2DISCONNECT SWITCH <br /> THOSE IN ADJACENT ROOMS AT THE OTHER SIDE OF WALL. .5 GROUNDING ACCEPTANCE OF THE CONTRACT FOR THIS WORK INCLUDES THIS GUARANTEE: THE CONTRACTOR Z C <br /> 12. ALL GROUND WIRES SHALL BE INSULATED GROUNDS. GUARANTEES THAT HE HAS PERFORMED THE WORK IN ACCORDANCE WITH THE CONTRACT TC TIMECLOCK G <br /> 13. THE ENTIRE LIGHTING INSTALLATION AND THE PRODUCTS USED SHALL BE IN COMPLIANCE WITH GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND SPECIFICALLY INCLUDING DOCUMENTS. CONTRACTOR AGREES TO REPLACE OR REPAIR, AS NEW ANY DEFECTIVE WORK, Q <br /> THE CALIFORNIA ENERGY EFFICIENCY STANDARDS. SWITCHBOARD, PANELBOARDS, MOTOR CASES, ETC. MATERIALS, OR PART WHICH MAY APPEAR WITHIN ONE YEARS (1) OF FINAL ACCEPTANCE, IF, IN THE SD DUCT SMOKE DETECTOR <br /> I14. THE FOLLOWING SHALL BE PROVIDED PER PLANS AS A MINIMUM TO ENSURE COMPLIANCE: OPINION OF THE ARCHITECT OR THE OWNER, THE DEFECT IS DUE TO WORKMANSHIP OR MATERIAL. Q] <br /> A. LIGHTING SHALL BE CONTROLLED BY SELF-CONTAINED LIGHTING CONTROL DEVICES WHICH 2.6 MAIN SERVICE SWITCHBOARD m W Ln <br /> ARE CERTIFIED TO THE ENERGY COMMISSION ACCORDING TO THE TITLE 24 EFFICIENCY 3.6 WARRANTIES, GUARANTEES, CERTIFICATES, ETC. PANEL# ELECTRICAL SUB PANEL m W <br /> REGULATIONS IN ACCORDANCE WITH SECTION 110.9. 1. SERVICE SWITCHBOARD SHALL BE AS MANUFACTURED BY GENERAL ELECTRIC, SIEMENS, CUTLER <br /> B. LIGHTING SHALL BE CONTROLLED BY A LIGHTING CONTROL SYSTEM OR ENERGY MANAGEMENT HAMMER, SQUARE D OR APPROVED EQUAL, METAL ENCLOSED UNIT. ARRANGEMENT AND RATINGS OF WARRANTIES, GUARANTEES, CERTIFICATES, ETC. THAT ARE FURNISHED AND AVAILABLE FOR LTG LIGHTING CONTROL PANEL ❑ <br /> CONTROL SYSTEM IN ACCORDANCE WITH 110.9. AN INSTALLATION CERTIFICATE SHALL BE EQUIPMENT ARE SHOWN ON DRAWINGS. UNIT SHALL MEET ALL UTILITY COMPANY REQUIREMENTS AND EQUIPMENT AND MATERIALS FURNISHED AND INSTALLED UNDER THIS SECTION SHALL BE PROPERLY a W <br /> SUBMITTED IN ACCORDANCE WITH SECTION 130.4(B). BE APPROVED BY THE ASMAE PRIOR TO PROCUREMENT AND INSTALLATION. FILLED OUT AS OF DATE OF ACCEPTANCE OF THE WORK BY THE OWNER AND SHALL BE COMMUNICATIONS SYMBOLS En r- <br /> C. ALL LIGHTING CONTROLS AND EQUIPMENTS SHALL COMPLY WITH THE APPLICABLE 2. SWITCHBOARD SHALL BE ENCLOSED STRUCTURE OF CODE GAUGE STEEL PLATES WITH REMOVABLE DELIVERED TO THE ARCHITECT. <br /> REQUIREMENTS IN 110.9 AND SHALL BE INSTALLED IN ACCORDANCE WITH THE FRONT. FULL FRONT ACCESS SHALL BE PROVIDED FOR CONNECTIONS AND OPERATIONS. FRONT DATA WALL OUTLET <br /> MANUFACTURER'S INSTRUCTIONS IN ACCORDANCE WITH SECTION 130.1. SECTIONS SHALL BE ATTACHED WIT MACHINE SCREWS, EVENLY SPACED. HINGED DOOR SHALL HAVE 3.7 ACCEPTANCE BY GOVERNING AUTHRITIES - +15" A.F.F. TO BOTTOM OF BOX ECURIT SECURITY SYSTEM PANEL L� <br /> D. ALL LUMINARIES SHALL BE FUNCTIONALLY CONTROLLED WITH MANUALLY SWITCHED ON AND VAULT TYPE HANDLES AND LOCKS. UNIT SHALL BE NEMA 3R FOR OUTDOORS INSTALLATION AND Q <br /> OFF LIGHTING CONTROLS IN ACCORDANCE WITH SECTION 130.1(A). NEMA 1 FOR INDOORS INSTALLATION. UPON THE COMPLETION OF THE ELECTRICAL WORK, AND AS CONDITION OF ITS ACCEPTANCE, THIS 0 TELEPHONE WALL OUTLET MUSIC SOUND SYSTEM RECEIVER <br /> E. THE GENERAL LIGHTING OF ANY ENCLOSED AREA 100 SQUARE FEET OR LARGER, WITH A 3. ALL BUSES SHALL BE COPPER, SIZED TO CONFORM TO UL TO LIMIT TEMPERATURE RISE. ALL BUS CONTRACTOR SHALL OBTAIN FINAL INSPECTIONS AND ACCEPTANCE FROM LOCAL BUILDING +15" A.F.F. TO BOTTOM OF BOX ❑ r- O) <br /> CONNECTED LIGHTING LOAD THAT EXCEEDS 0.5 WATTS PER SQUARE FOOT SHALL MEET CONNECTIONS SHALL BE BOLTED. BUSES SHALL BE BRACED TO WITHSTAND, AS A MINIMUM, THE INSPECTION AGENCIES, UTILITY COMPANIES AND/OR OTHER GOVERNING AUTHORITIES. DELIVERED TODATA/TELEPHONE WALL OUTLET O W W ❑ <br /> MULTI-LEVEL LIGHTING CONTROL REQUIREMENTS IN ACCORDANCE WITH SECTION 130.1 (B) SHORT CIRCUIT CURRENT INDICATED ON DRAWINGS. BUSES SHALL BE SEQUENCE PHASED AND SHALL THE OWNER AND THE ARCHITECT VERIFICATION OF SUCH ACCEPTANCE. +15" A.F.F. TO BOTTOM OF BOX SP CEILING MOUNT SPEAKER <br /> F. ALL INSTALLED INDOOR LIGHTING SHALL BE EQUIPPED WITH CONTROLS THAT MEET THE RUN FULL HEIGHT. I N <br /> APPLICABLE SHUTT-OFF CONTROL REQUIREMENTS IN SECTION 103.1(C) 4. PROVIDE "SPACES" INDICATED ON DRAWINGS WITH ALL NECESSARY MOUNTING HARDWARE TELE TELEPHONE BACKBOARD r- <br /> G. LIGHTING IN ALL DAY LIT ZONES SHALL BE CONTROLLED IN ACCORDANCE WITH THE PERMITTING EASY FUTURE INSTALLATION OF BREAKERS IN THE FIELD. 2 <br /> k I <br /> REQUIREMENTS IN SECTION 130.1(D) AND DAYLIT ZONES ARE SHOWN ON THE PLANS 5. PROVIDE INCOMING SERVICE TERMINALS METERING SECTION, CTS, ETC. IN ACCORDANCE WITH THE DATA DATA PATCH PANEL <br /> H. BEFORE AN OCCUPANCY PERMIT IS GRANTED FOR A NEWLY CONSTRUCTED BUILDING OR UTILITY COMPANY AND PLANS. a <br /> AREA, OR A NEW LIGHTING SYSTEM SERVING A BUILDING, AREA OR SITE IS OPERATED FOR 6. PROVIDE A COPPER GROUND BUS. 2 <br /> NORMAL USE, INDOOR LIGHTING CONTROLS SERVING THE BUILDING, AREA, OR SITE SHALL BE CONDUIT 0 <br /> CERTIFIED AS MEETING THE ACCEPTANCE REQUIREMENTS FOR CODE COMPLIANCE IN 2.7 PANEL BOARD CONDUITS: <br /> ACCORDANCE WITH SECTION 130.4(A), THE CONTROLS REQUIRED TO MEET THE ACCEPTANCE CONDUIT CONCEALED IN WALL OR CEILING MINIMUM SIZE-%2" C <br /> REQUIREMENTS INCLUDE AUTOMATIC DAYLIGHT CONTROLS, AUTOMATIC SHUT-OFF UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE PANEL SCHEDULE, WITH THE ------- CONDUIT CONCEALED IN FLOOR OR UNDERGROUNDU <br /> CONTROLS, AND DEMAND RESPONSIVE CONTROLS. NUMBER AND SIZE OF BREAKERS AS INDICATED ON THE PANEL SCHEDULE. SINGLE POLE, TWO POLE, TICS = NO. #1 LI WIRES <br /> 15. THE FOLLOWING LIGHTING CONDITIONS NEED TO BE PROVIDED WITHIN THE FACILITY: AND THREE POLE BREAKERS SHALL BE BOLT-ON TYPE. MULTIPLE POLE BREAKERS SHALL HAVE FLEXIBLE CONDUIT FOR LIGHTING ABOVE CEILING NO TICS =2#12 LION <br /> A. DRY FOOD STORAGE AREA COMMON INTERNAL TRIP CONNECTION. SINGLE POLE BREAKERS SHALL NOT BE TIED AT HANDLES <br /> 10 FOOT CANDLES AT 30" ABOVE FLOOR MINIMUM. TO FORM MULTIPLE POLE BREAKERS. THE PANEL DOORS SHALL HAVE FLUSH TYPE LOCKS, ALL LOCKS <br /> B. SELF-SERVICE FOOD SHALL BE KEYED ALIKE AND HAVE TYPEWRITTEN DIRECTORIES INDICATING FIXTURES, SED ARC/ <br /> 20 FOOT CANDLES MINIMUM.PRODUCE OR EQUIPMENT, OR OUTLETS SERVICED BY EACH BREAKER. PANELS SHALL HAVE COPPER BUSSING. <br /> C. PREPACKAGED FOOD ��OQ�J• 13 <br /> 20 FOOT CANDLES MINIMUM 2.8 HVAC SYSTEMS <br /> D. INSIDE OF REACH-IN OR UNDER-COUNTER REFRIGERATION UNITS 2 <br /> 20 FOOT CANDLES MINIMUM 1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT ~ C-25449 p <br /> E. HAND WASHING, WARE WASHING, EQUIPMENT STORAGE, UTENSIL STORAGE AND RESTROOMS LOCATIONS OF ALL HVAC UNITS, DISCONNECTS AND DEVICES IN FIELD. COORDINATE ROOF <br /> 6-30-21 <br /> F. FOOD EMPLOYEE WORK AREEASS IN WHICH SAFETY IS A FACTOR (I.E.SLICING, CUTTING, <br /> 20 FOOT CANDLES ABOVE THE FLOOR MINIMUM. PENETRATIONS AND STUB UPS FOR DISCONNECTS WITH ELECTRICAL CONNECTION POINTS ON THE S RENEWAL DATE <br /> UNITS TO KEEP FLEXIBLE CONDUIT LENGTH TO A MINIMUM (36" MAXIMUM). VERIFY AND CONFIRM 9T Q <br /> GRINDING) O <br /> WITH THE MECHANICAL CONTRACTOR THE ACTUAL MOUNTING LOCATION ON THE HVAC UNIT FOR THE F SF <br /> 50 FOOT CANDLES MINIMUM. DISCONNECT PRIOR TO ROUGH-IN. ENSURE CODE REQUIRED WORKING CLEARANCES IN FRONT OF THE OF CAL <br /> 16. ALL HEATING, AIR CONDITIONING AND REFRIGERATION EQUIPMENT SHALL HAVE A DISCONNECT WITHIN DISCONNECTS. <br /> SIGHT AND HAVE A SERVICE RECEPTACLE ON THE SAME LEVEL AND WITHIN 25 FEET OF THE UNIT. 2. THE RATING OF THE DISCONNECT SHALL BE SUCH AS TO ENABLE THE LARGEST FUSE SIZE ON THE <br /> 17. GFCI PROTECTION SHALL BE PROVIDED AT ALL KITCHEN AREA RECEPTACLES UNIT NAMEPLATE TO BE INSTALLED IN THE DISCONNECT. VERIFY WITH MECHANICAL <br /> CONTRACTOR THIS INFORMATION PRIOR TO BUYING AND INSTALLING THE DISCONNECT. PROVIDE • <br /> FUSES OF THIS RATING. <br /> 1.2 PENETRATIONS 3. FURNISH AND INSTALL ALL LINE VOLTAGE CONDUITS AND LINE VOLTAGE WIRING (LOW VOLTAGE <br /> WIRING AND RELATED CONDUITS BY OTHERS)TO HVAC EQUIPMENT AND ASSOCIATED CONTROLS <br /> PENETRATIONS IN EXTERIOR WALLS SHALL BE SEALED AND RENDERED AS WATERTIGHT AS POSSIBLE AND DEVICES AS SHOWN ON THE ELECTRICAL AND MECHANICAL PLANS, UNLESS OTHERWISE NOTED. <br /> 4. RUN ALL CONDUITS FOR ROOFTOP EQUIPMENT TO CEILING BELOW. SURFACE CONDUIT RUNS ON THE crumbl <br /> 1.3 WIRING METHODS ROOF ARE NOT PERMITTED ON THIS PROJECT. <br /> 5. DISCONNECTS SHALL NOT BE USED AS THROUGH RACEWAYS FOR WIRING NOT DIRECTLY SERVING THE <br /> 1. ALL WIRING SHALL BE INSTALLED IN STEEL CONDUITS. CONDUITS SHALL BE RUN CONCEALED IN DISCONNECTS. SERVICING OUTLETS SHALL NOT BE MOUNTED ON DISCONNECTS. C O O ICI e S <br /> WALLS AND CEILINGS. INTERIOR TENANT <br /> 2. MINIMUM CONDUIT SIZE SHALL BE 1/2". MINIMUM ACCEPTABLE CONDUITS ARE IMPROVEMENT <br /> A. GALVANIZED RIGID STEEL- FOR USE ON EXTERIOR WALL SURFACES AND ROOF. <br /> OBTAIN ARCHITECTS PERMISSION FOR SURFACE RUN. <br /> B. GALVANIZED STEEL EMT- FOR USE CONCEALED IN INDOOR SPACES. LOCATION <br /> C. LIQUID TIGHT STEEL FLEX- FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT. (NOT TO 864 W. BENJAMIN HOLT DR. <br /> STOCKY N, CA <br /> EXCEED 36") <br /> D. FLEXIBLE STEEL CONDUIT - FOR INDOOR FINAL CONNECTIONS TO RECESSED LIGHT FIXTURES 95207 <br /> (NOT TO EXCEED 72") AND HVAC EQUIPMENT. A.P.N.: 09741060 <br /> E. PVC CONDUIT APPROVED FOR USE UNDERGROUND ONLY. <br /> F. NO ALUMINUM CONDUITS, IMC CONDUITS OR ALUMINUM FITTINGS ARE APPROVED FOR USE ON FRANCHISE OWNER <br /> THIS PROJECT. <br /> G. ALL CONDUIT FITTINGS SHALL BE MALLEABLE IRON/STEEL. KTK CO. <br /> GLEN ABBY CIRCLE <br /> H. EMT COUPLING APPLETON TWC-CS SERIES STOCKTON, CA <br /> EMT CONNECTOR APPLETON TW-CSI-SERIES 3966 <br /> FLEX CONDUIT CONNECTOR T&B "TITE BITE", INSULATED LIQUID TIGHT FLEX 95219 <br /> CONDUIT CONNECTOR APPLETON "STB" SERIES UP TO 2", "ST" SERIES OVER 2". <br /> J. RIGID STEEL CONDUIT CONNECTED TO BOXES AND CABINETS SHALL BE FITTED WITH TWO <br /> LOCKNUTS AND INSULATING BUSHING, OA "A" SERIES. PROVIDE GROUNDING BUSHING OZ "BU <br /> SERIES WHERE LOCKNUTS AND BUSHING IS NOT USED. CONDUITS CONNECTED TO BOXES DRAWN <br /> EXPOSED TO WEATHER/MOISTURE SHALL BE FITTED WITH WATERTIGHT SEALING HUBS OF TAF <br /> STEEL OR MALLEABLE IRON WITH SEALING RING AND INSULATED THREAT, T& B 370 SERIES. <br /> K. NO MC OR AC CABLE TO BE USED ON THIS PROJECT. CHECKED <br /> L. TYPE NM AND NMC CABLES SHALL NOT BE USED ON THIS PROJECT. SLW <br /> DATE <br /> 5/25/2021 <br /> SCALE <br /> AS SHOWN <br /> JOB NO. <br /> 21-136 <br /> SHEET <br /> Eml m0 <br /> OF SHEETS <br />