Laserfiche WebLink
_ anknology 111 1100 Field Test Apparatus Page 1 of 1 <br /> TLine Leak Detector Test <br /> Work Order: 2352824 Date: 11/15/2021 <br /> Site Name/ID: CHEVRON#99840(N31)/99840 <br /> Address: 4344 E WATERLOO RD @ 99 <br /> City: STOCKTON State: CA Zip: 95215 <br /> Tank ID T1 T2 <br /> Product SUPREME REG UNLEAD <br /> Product Line 1 1 <br /> Tested From 4 4 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD <br /> Serial No. 012388 327320 <br /> Pump Operating Pressure(psi) 36.00 40.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI <br /> *N/A for Electronic LD's <br /> Resiliency(ml) <br /> *N/A for Electronic LD's <br /> Metering PSI <br /> *N/A for Electronic LD's <br /> Opening Time(sec) <br /> *N/A for Electronic LD's <br /> Test Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Jess/us Saldivar Certification#: 115237 A <br /> Technician Signature: ,41-1Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> ©2021 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />