Laserfiche WebLink
PACKAGED AIR CONDITIONING <br />UNITS <br />Section 15855 <br />15-1207 <br />PART 1 —GENERAL <br />1.01 SUMMARY: <br />A. This section provides requirements for split system ducted air conditioning units. <br />1.02 QUALITY ASSURANCE: <br />A. Flame -Smoke Ratings: Except as otherwise indicated, provide air conditioning unit thermal <br />insulation with flame -spread index of 25 or less, fuel -contributed index of 50 or less, and <br />smoke -developed index of 50 or less. <br />B. AMCA Standards: Comply with Air Movement and Control Association (AMCA) Standards as <br />applicable to testing and rating fans. <br />C. SMACNA Compliance: Comply with Sheet Metal and Air Conditioning Contractors National <br />Association (SMACNA) ductwork construction standards as applicable to air conditioning units. <br />D. AGA Certification: Gas fired equipment shall be AGA certified. <br />E. ARI Certification: Coils shall comply with ARI Standard 410. <br />F. UL Compliance: Provide electric components for air conditioning units which have been listed <br />and labeled by Underwriters Laboratories or by a testing organization of equal standing. <br />G. Only Manufacturer's Authorized Commercial and Industrial Equipment Suppliers shall be <br />allowed to supply equipment for this project. Equipment suppliers who's primary business is <br />residential and are not a Manufacturer's Authorized Commercial and Industrial Equipment <br />Supplier shall not be accepted on this project due to lack of a service company capable of <br />proper support on a commercial quality project. <br />1.03 SUBMITTALS: <br />A. Submit the following information for each packaged unit: <br />1. Manufacturer's product data and cut sheet for each unit. <br />2. Submit manufacturer's specifications for air conditioning units showing dimensions, weights, <br />capacities, ratings, certified fan performance with operating point clearly indicated on a fan <br />curve, motor electrical characteristics, gauges, finishes of materials, and installation <br />instructions. <br />B. Maintenance Data: <br />1. Submit maintenance instructions, including lubrication instructions, filter replacement, motor <br />and drive replacement, and spare parts lists. <br />2. Include this data in maintenance manuals only. <br />1.04 PRODUCT DELIVERY, STORAGE, AND HANDLING: <br />A. Deliver air conditioning units with factory -installed shipping skids and lifting lugs; pack <br />components in factory -fabricated protective containers. <br />