My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
WORK PLANS
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
Y
>
YOSEMITE
>
750
>
1600 - Food Program
>
PR0161533
>
WORK PLANS
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
12/20/2021 7:17:05 PM
Creation date
10/15/2021 3:39:59 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
1600 - Food Program
File Section
WORK PLANS
RECORD_ID
PR0161533
PE
1632
FACILITY_ID
FA0001342
FACILITY_NAME
MUSD-LINCOLN SCHOOL
STREET_NUMBER
750
Direction
E
STREET_NAME
YOSEMITE
STREET_TYPE
AVE
City
MANTECA
Zip
95336
APN
22118001
CURRENT_STATUS
01
SITE_LOCATION
750 E YOSEMITE AVE
P_LOCATION
04
P_DISTRICT
005
QC Status
Approved
Scanner
SJGOV\jcastaneda
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
2850
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
INSULATED CONDUCTORS <br />Section 16070 <br />15-1207 <br />Install cables in specific conduit specified. Remove cables installed in incorrect conduit or <br />raceways and if length is not correct, install new cable all at no increase in Contract Sum. <br />Remove and replace any cable damaged during installation with new cable at no increase in <br />Contract Sum. <br />K. Install all. wiring so that when l� completed �pleted .s1. ystem shall be free from short-circuits. and i poi - <br />intentional grounds. <br />L. Use green insulation on conductors intended solely for grounding purposes. <br />M. Leave twelve inches (12") minimum of slack wire in every outlet box whether it be in use or left <br />for future use. <br />N. Install power circuits from distribution panels to individual outlets or control equipment, as <br />shown. Conductors: Size and type shown. <br />0. Install branch circuit conductors for general lighting system from panelboards to outlets and <br />between outlets. If single distance from panelboard to first outlet exceeds one hundred feet <br />(100'), minimum size conductor for such run shall be 10 gauge. <br />P. Provide branch circuits to receptacle outlets as shown. For excessively long runs (fifty feet [50] <br />or more) from panelboard to first receptacle outlet, minimum size wire shall be 10 gauge to first <br />outlet with conductors between outlets being 12 gauge. Make up connections to devices from <br />"thru-feed" branch circuit conductors with pigtails with no interruption of branch circuit <br />conductors. <br />Q. Neatly and securely bundle all conductors located in branch circuit panelboards and <br />switchboards. Neatly and securely cable all conductors larger than No. 10 located in <br />jvV ltl'hbVar dS aI lu pullboxes it l� individual circuits. Use i lyloi � table stra pj for bili �diii ng ai �u <br />cabling cable straps. <br />R. Where conductors are to be connected to metallic surfaces, coated surfaces shall be cleaned <br />to base metal surface before installing connector. Remove lacquer coating of conduits where <br />ground clamps are to be installed. <br />S. Provide supports required to make complete cable installation. <br />T. Provide 12 gauge stranded (green) wire from ground terminal of receptacle to ground bond <br />wire or to stud in outlet box. <br />U. Installation of metal -clad cables shall comply with 2013 C.E.C. Article 334 and Article 517. <br />V. Installation of nonmetallic -sheathed cables shall comply with 2013 C.E.C. Article 336. <br />3.2 INSTALLATION - TYPE MC CABLE: <br />A. MC cable is acceptable for concealed branch circuit wiring under the following conditions: <br />4 <br />
The URL can be used to link to this page
Your browser does not support the video tag.