Laserfiche WebLink
PANELBOARDS <br />Section 16435 <br />15-1207 <br />C. Install flush mounted panel backbox front edges flush with finished wall. Where flush panel <br />backbox is deeper than wall depth, install closing trim of wood or metal to provide a finished trim. <br />D. After installation, make all feeder connections to load side lugs of circuit breakers, disconnect <br />switches and incoming secondary feeders. <br />E. Install in accordance with manufacturer's specifications and recommendations. <br />F. Fill out panelboard circuit identification card, typewritten, with list of circuits in use. Identification <br />shall be specific with room designation and other information as necessary. For distribution <br />panelboards, use engraved laminated phenolic plate showing load served and trip rating. <br />G. Where panelboard is flush in wall, provide one (1) three-quarters inch (3/4") conduit stub into <br />accessible ceiling space for each five (5) spare circuit breaker spaces. <br />H. Provide identification for panelboard, individually mounted circuit breakers and switches as <br />specified under Identification for electrical systems Section. <br />END OF SECTION <br />4 <br />