1. MECHANICAL AND PLUMBING DETAILS APPLY TO ALL BUILDINGS WHETHER REFERENCED OR NOT.
<br />2. PROVIDE FIRE STOPPING ASSEMBLY PROTECTION FOR DUCT PENETRATIONS OF RATED ASSEMBLIES.
<br />FIRE STOP RATING SHALL MATCH RATED ASSEMBLY BEING PENETRATED.
<br />3. DUCTWORK AND PIPING SHALL NOT PENETRATE INTO OR THROUGH IT CLOSETS OR ELECTRICAL
<br />ROOM UNLESS IT SERVES THAT SPECIFIC ROOM.
<br />4. REFERENCE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF DIFFUSERS/GRILLES.
<br />5. DRAWINGS SHALL BE CONSIDERED DIAGRAMMATIC. THE CONTRACTORS SHALL COORDINATE LOCATION
<br />OF ALL MECHANICAL DUCTWORK, EQUIPMENT, AND PIPING WITH ALL OTHER TRADES ON THIS
<br />PROJECT.
<br />6. CEILING SUPPLY AIR DIFFUSERS TO HAVE 4 --WAY BLOW PATTERN UNLESS SHOWN OTHERWISE.
<br />7. THERMOSTATS TO BE INSTALLED AT 46" AFF (TOP OF THERMOSTAT). DO NOT INSTALL
<br />THERMOSTATS OVER CASEWORK OR SHELVING OVER 24" IN DEPTH AND 34" IN HEIGHT.
<br />ALL MECHANICAL AND PLUMBING COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON
<br />THE DSA APPROVED CONTRACT DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING
<br />COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT` REQUIREMENTS
<br />PRESCRIBED IN THE 2013 CBC, SECTION 1616A.1.18 THROUGH 1616A.1.26 AND ASCE 7--10, CHAPTERS IS,
<br />16 AND 30.
<br />1. ALL PERMANENT EQUIPMENT AND COMPONENTS
<br />2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G. HARD WIRED) TO THE
<br />BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER.
<br />3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER
<br />THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.
<br />THE ATTACHMENT OF THE FOLLOWING MECHANICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE
<br />STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE
<br />CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.
<br />A. COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET
<br />OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE
<br />COMPONENT.
<br />B. COMPONENTS WEIGHING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED SYSTEMS, LESS
<br />THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A
<br />WALL.
<br />FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE INSTALLATION
<br />SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD AND THE DSA
<br />DISTRICT STRUCTURAL ENGINEER, THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND
<br />EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCE WITH THE ABOVE REQUIREMENTS.
<br />PIPING AND, DUCTWORK SYSTEM BRACING NOTE:
<br />PIPING AND DUCTWORK SHALL BE BRACED TO COMPLY THE FORCE AND DISPLACEMENTS PRESCRIBED IN
<br />ASCE 7-10 SECTION 13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.6, 13.6.7, AND 13.6.5.6, AND 2013
<br />CBC, SECTIONS 1616A.1.23, 1616A.1.24, 1616A=1.25, AND 1615A.1.26.
<br />THE BRACING AND ATTACHMENT TO THE STRUCTURE SHALL BE DETAILED ON THE APPROVED DRAWINGS
<br />OR THEY SHALL COMPLY WITH ONE OF THE OSHPD PRE -APPROVALS (OPM #) AS MODIFIED TO SATISFY
<br />ANCHORAGE REQUIREMENTS OF AGI 316, APPENDIX D.
<br />COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANDING AND
<br />BRACING OF THE PIPE AND DUCTWORK SYSTEMS.
<br />THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT
<br />THE HANGER AND BRACE LOADS.
<br />AIR CONDITIONING
<br />EXHAUST
<br />FAN
<br />SCHEDULE
<br />MANUFACTURER &
<br />MANUFACTURER &
<br />EXTERNAL SP
<br />SUPPLY AIR BLOWER
<br />HEATING CAPACITY (BTUH)
<br />MIM. COOLING CAPACITY MBH
<br />ARI CONDITIONS)
<br />HEATING CAPACITY (BTUH)
<br />MAXIMUM UNIT
<br />CONTROL INTERLOCK
<br />SCHEDULE
<br />SYMBOL
<br />MODEL NUMBER
<br />TOTAL CFM
<br />INCHES W.C.)
<br />MOTOR HP
<br />MOTOR BHP
<br />MOTOR RPM
<br />ELECTRICAL
<br />WEIGHT
<br />(LBS.)
<br />AC UNIT
<br />LIGHT SWITCH
<br />OUTSIDE AIR
<br />(CFM)
<br />DETECTOR
<br />WEIGHT
<br />ESP.
<br />NOTES
<br />NOMINAL
<br />DESIGN
<br />INTERLOCK
<br />INTERLOCK
<br />EF
<br />GREENHECK
<br />1,200
<br />0.375
<br />1/2
<br />0.12
<br />HP
<br />1,000
<br />120V/10/60 Hz
<br />125
<br />AC/G1
<br />G120
<br />1G
<br />MODEL: CUE -161 -VG
<br />TOTAL
<br />SENSIBLE
<br />INPUT
<br />OUTPUT
<br />PHASE
<br />HERTZ
<br />VOLTS
<br />PHASE
<br />HERTZ
<br />MOCP
<br />EF
<br />2G
<br />GREENHECK
<br />MODEL: CUE -099 -VG
<br />425
<br />0.375
<br />1/4
<br />0.05
<br />AC
<br />1,725
<br />120V/10/60 Hz
<br />100
<br />AC/G2
<br />G116
<br />EF
<br />3G
<br />GREENHECK
<br />MODEL: CUE -099 -VG
<br />625
<br />0.375
<br />1/4
<br />0.07
<br />HEATING TO BE 8 STAGES FURNACE CONTROL (MIN.)
<br />1,725
<br />120V/10/60 Hz
<br />100
<br />AC/G3
<br />G109
<br />EF
<br />GREENHECK
<br />1,200
<br />0.375
<br />1/2
<br />0.12
<br />25
<br />1,000
<br />120V/10/60 Hz
<br />150
<br />MAU/1G
<br />NA
<br />\4G7
<br />MODEL: CUE -099 -VG
<br />STAGE =
<br />2ND STAGE =
<br />11.20
<br />EER
<br />208
<br />30
<br />60
<br />40
<br />SEE NOTE 4
<br />NOT REQUIRED
<br />NOTES:
<br />COOLING
<br />(MIN) COOLING
<br />LISTED AT 2ND STAGE. PROVIDE WITH POWER
<br />2. UNIT TO BE INTERLOCKED TO KITCHEN HOOD AND EXHAUST FAN
<br />1. PROVIDE ROOF MOUNTED EXHAUST FANS WITH
<br />MANUFACTURER'S ROOF CURB.
<br />3, UNIT TO BE PROVIDED WITH THE FOLLOWING:
<br />2. LISTED MAXIMUM UNIT WEIGHT INCLUDES ALL ACCESSORIES (ROOF CURB, BIRDSCREENS,
<br />DAMPERS, ETC.).
<br />1. MECHANICAL AND PLUMBING DETAILS APPLY TO ALL BUILDINGS WHETHER REFERENCED OR NOT.
<br />2. PROVIDE FIRE STOPPING ASSEMBLY PROTECTION FOR DUCT PENETRATIONS OF RATED ASSEMBLIES.
<br />FIRE STOP RATING SHALL MATCH RATED ASSEMBLY BEING PENETRATED.
<br />3. DUCTWORK AND PIPING SHALL NOT PENETRATE INTO OR THROUGH IT CLOSETS OR ELECTRICAL
<br />ROOM UNLESS IT SERVES THAT SPECIFIC ROOM.
<br />4. REFERENCE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF DIFFUSERS/GRILLES.
<br />5. DRAWINGS SHALL BE CONSIDERED DIAGRAMMATIC. THE CONTRACTORS SHALL COORDINATE LOCATION
<br />OF ALL MECHANICAL DUCTWORK, EQUIPMENT, AND PIPING WITH ALL OTHER TRADES ON THIS
<br />PROJECT.
<br />6. CEILING SUPPLY AIR DIFFUSERS TO HAVE 4 --WAY BLOW PATTERN UNLESS SHOWN OTHERWISE.
<br />7. THERMOSTATS TO BE INSTALLED AT 46" AFF (TOP OF THERMOSTAT). DO NOT INSTALL
<br />THERMOSTATS OVER CASEWORK OR SHELVING OVER 24" IN DEPTH AND 34" IN HEIGHT.
<br />ALL MECHANICAL AND PLUMBING COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON
<br />THE DSA APPROVED CONTRACT DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING
<br />COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT` REQUIREMENTS
<br />PRESCRIBED IN THE 2013 CBC, SECTION 1616A.1.18 THROUGH 1616A.1.26 AND ASCE 7--10, CHAPTERS IS,
<br />16 AND 30.
<br />1. ALL PERMANENT EQUIPMENT AND COMPONENTS
<br />2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G. HARD WIRED) TO THE
<br />BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER.
<br />3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER
<br />THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.
<br />THE ATTACHMENT OF THE FOLLOWING MECHANICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE
<br />STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE
<br />CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.
<br />A. COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET
<br />OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE
<br />COMPONENT.
<br />B. COMPONENTS WEIGHING LESS THAN 20 POUNDS, OR IN THE CASE OF DISTRIBUTED SYSTEMS, LESS
<br />THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A
<br />WALL.
<br />FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE INSTALLATION
<br />SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD AND THE DSA
<br />DISTRICT STRUCTURAL ENGINEER, THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND
<br />EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCE WITH THE ABOVE REQUIREMENTS.
<br />PIPING AND, DUCTWORK SYSTEM BRACING NOTE:
<br />PIPING AND DUCTWORK SHALL BE BRACED TO COMPLY THE FORCE AND DISPLACEMENTS PRESCRIBED IN
<br />ASCE 7-10 SECTION 13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.6, 13.6.7, AND 13.6.5.6, AND 2013
<br />CBC, SECTIONS 1616A.1.23, 1616A.1.24, 1616A=1.25, AND 1615A.1.26.
<br />THE BRACING AND ATTACHMENT TO THE STRUCTURE SHALL BE DETAILED ON THE APPROVED DRAWINGS
<br />OR THEY SHALL COMPLY WITH ONE OF THE OSHPD PRE -APPROVALS (OPM #) AS MODIFIED TO SATISFY
<br />ANCHORAGE REQUIREMENTS OF AGI 316, APPENDIX D.
<br />COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANDING AND
<br />BRACING OF THE PIPE AND DUCTWORK SYSTEMS.
<br />THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT
<br />THE HANGER AND BRACE LOADS.
<br />ITEM TO BE REMOVED / DEMOED
<br />RETURN OR EXHAUST AIR DUCT
<br />SUPPLY AIR DUCT
<br />FLEXIBLE CONNECTION
<br />------- - �� BLV BALL VALVE
<br />BV. BALANCE VALVE
<br />BFV BUTTERFLY VALVE
<br />---+�- CKV. CHECK VALVE
<br />THERMOMETER, PRESSURE GAUGE
<br />-;�-- OUTSIDE AIR INTO LOUVER
<br />-r---- RETURN OR EXHAUST AIR INTO REGISTER
<br />SUPPLY AIR FROM REGISTER
<br />EXHAUST AIR DUCT SECTION
<br />RETURN AIR DUCT SECTION
<br />SUPPLY AIR DUCT SECTION
<br />12 x 10 DUCT FIRST FIGURE 510E SHOWN
<br />SECON FIGURE SIDE NOT SHOWN)
<br />SQUARE TO ROUND TRANSITION
<br />fF� TURNING VANES
<br />--� FLEXIBLE DUCTWORK
<br />VCD VCD
<br />---�-' VOLUME CONTROL DAMPER
<br />R _ D_
<br />RISE OR DROP IN DIRECTION OF ARROW
<br />SUPPLY AIR GRILLE ID ZE
<br />CFM
<br />RETURN AIR GRILLE ID -I -E--
<br />FM
<br />EXHAUST AIR GRILLE ID
<br />.. !.
<br />' rainarchitects
<br />forth
<br />ROOM THERMOSTAT (SEE MECHANICAL NOTES
<br />FOR MOUNTING HEIGHT)
<br />Yom' DIAMETER
<br />AC AIR CONDITIONING
<br />AD, AP ACCESS DOOR, ACCESS PANEL
<br />CC CENTER TO CENTER
<br />CFM,f CUBIC FEET OF AIR PER MINUTE
<br />(E), (N) EXISTING, NEW
<br />EA EXHAUST AIR
<br />EAD EXHAUST AIR DAMPER
<br />EF EXHAUST FAN
<br />`F DEGREES FAHRENHEIT
<br />FA / FB FROM ABOVE / FROM BELOW
<br />FD / FSD FIRE DAMPER / FIRE SMOKE DAMPER >;
<br />GA. GAUGE ='
<br />GALV. GALVANIZED
<br />ESTON
<br />GPM GALLONS PER MINUTE ASSOCIATES
<br />HP / 6HP HORSEPOWER / BREAK HORSEPOWER
<br />MAX., MIN. MAXIMUM, MINIMUM
<br />MECHANICAL ENGINEERS
<br />M.D. MANUAL DAMPER 4701 ANNE WAY k CARMICHAEL, CA 95608 1 (91 b) 4€ 2-0820
<br />NA NOT APPLICABLE WESTON & ASSOCIATES #15012
<br />NTS NOT TO SCALE
<br />pFESS�G�
<br />PRV. PRESSURE REDUCING VALVE e ®® A, pit E -le
<br />OA OUTSIDE AIR.y
<br />c� � No. M312 a u
<br />OAD OUTSIDE AIR DAMPER '
<br />IRA RETURN AIR
<br />RENEWAL DATE:
<br />RAO RETURN AIR DAMPER v�'� v31t2015C�_-
<br />flA N
<br />RF RELIEF FAN
<br />SMS SHEET METAL SCREW
<br />SA, OA, SUPPLY AIR, OUTSIDE AIR
<br />TA / T8 TO ABOVE / TO BELOW
<br />T.C.V. TEMPERATURE CONTROL VALVE
<br />T.C.P. TEMPERATURE CONTROL PANEL
<br />TYP. TYPICAL
<br />$ ON/OFF SWITCH / STARTER
<br />ROOM NAME ROOM NAME AND NUMBER
<br />0
<br />ALL WORK PERFORMED UNDER THIS CONTRACT IS TO CONFIRM TO THE FOLLOWING
<br />CODES AND REGULATIONS:
<br />1. CALIFORNIA ADMINISTRATIVE CODE, 2013
<br />2. CALIFORNIA BUILDING CODE, 2013
<br />3. CALIFORNIA MECHANICAL CODE, 2013
<br />4. CALIFORNIA PLUMBING CODE, 2013
<br />5. CALIFORNIA FIRE CODE, 2013
<br />6. CALIFORNIA ELECTRICAL. CODE, 2013
<br />7. CALIFORNIA ENERGY CODE, 2013
<br />THE ABOVE CODES AND REGULATIONS REFER TO THE LATEST EDITION OR REVISION IF
<br />FORCE ON THE DATE OF THE CONTRACT, UNLESS OTHERWISE STATED. NOTHING ON
<br />THE DRAWINGS IS TO BE CONSTRUED AS REQUIRING OR PERMITTING WORK THAT IS
<br />CONTRARY TO THE LISTED CODES AND REGULATIONS, OR OTHER LOCAL, STATE OR
<br />FEDERAL CODES OR REGULATIONS WHICH MAY BE APPLICABLE.
<br />Copyright Q 2014 Rainforth Grau Architects. All rights reserved. Reproduction of ftse plans, either In whole or In part, Intruding any form
<br />of copying andfor proration of derlvaM works toed, for any reason vA#*ut prior wri ten permission, is Wcdy prol•rltaited,
<br />mu
<br />File tela.: 39-53
<br />IDENTIFICATION STAMP
<br />DIV. OF THE STATE ARCHITECT
<br />02-114490 INC. 1
<br />AC r' FLSSS
<br />DATE i 1/ D )/jS-
<br />pr
<br />r::.�
<br />INCREMENT
<br />CAFETERIA
<br />MANTECAUNIFIED SCHOOL
<br />VIANTECA, CALIFORNIA
<br />MECHANICAL -
<br />LEGEND, SCHEDULES, AND NOTE]
<br />DRAW 4 DW PROJECT NO-
<br />CHECKED DATE
<br />DW
<br />SCALE SHEET
<br />15-1207
<br />06-26-15
<br />AIR CONDITIONING
<br />UNIT SCHEDULE
<br />MADE-UP Alm"UNIT
<br />SCHEDULE
<br />SUPPLY AIR BLOWER
<br />MANUFACTURER &
<br />NOMINAL
<br />SUPPLY AIR BLOWER
<br />HEATING CAPACITY (BTUH)
<br />MIM. COOLING CAPACITY MBH
<br />ARI CONDITIONS)
<br />HEATING CAPACITY (BTUH)
<br />MINIMUM
<br />SYMBOL
<br />UNIT ELECTRICAL DATA
<br />MINIMUM
<br />DUCT SMOKE
<br />MAXIMUM
<br />UNIT
<br />SYMBOL
<br />MODEL NUMBER
<br />TONAGE
<br />EER /
<br />SEER
<br />OUTSIDE AIR
<br />(CFM)
<br />DETECTOR
<br />WEIGHT
<br />ESP.
<br />NOTES
<br />NOMINAL
<br />DESIGN
<br />FLA
<br />FLA
<br />FLA
<br />HP
<br />hHP
<br />TSP
<br />CFM
<br />MAXIMUM CFM
<br />bHP
<br />ESP
<br />LD8
<br />TOTAL
<br />SENSIBLE
<br />INPUT
<br />OUTPUT
<br />PHASE
<br />HERTZ
<br />VOLTS
<br />PHASE
<br />HERTZ
<br />MOCP
<br />GREENHECK
<br />MODEL. IG -109-H12
<br />1,200
<br />(LBS.)
<br />0.28
<br />0.5
<br />0.65
<br />MIN.
<br />AC
<br />CARRIER
<br />CARRIER WEATHEREXPERT
<br />WEATHEREXPERT
<br />79F
<br />71'F
<br />100,000
<br />80,000
<br />120
<br />10
<br />60
<br />48
<br />1ST STAGE = 248
<br />1ST2ND
<br />IST STAGE = 200
<br />00
<br />HEATING TO BE 8 STAGES FURNACE CONTROL (MIN.)
<br />27
<br />PROVIDE WITH MEDIUM STATIC DRIVE UNIT TO HAVE 2 STAGES OF
<br />1G
<br />MODEL: 2r3
<br />25
<br />10,000
<br />10,000
<br />5.94
<br />1.2
<br />305,9
<br />231.8
<br />STAGE =
<br />2ND STAGE =
<br />11.20
<br />EER
<br />208
<br />30
<br />60
<br />40
<br />SEE NOTE 4
<br />NOT REQUIRED
<br />3,500
<br />COOLING
<br />(MIN) COOLING
<br />LISTED AT 2ND STAGE. PROVIDE WITH POWER
<br />2. UNIT TO BE INTERLOCKED TO KITCHEN HOOD AND EXHAUST FAN
<br />EF/4G, UNIT
<br />TO OPERATE WHENEVER EF/4G IS ENABLED.
<br />3, UNIT TO BE PROVIDED WITH THE FOLLOWING:
<br />EXHAUST
<br />- SEE NOTE 5
<br />FOR DETAILS
<br />AC
<br />CARRIER WEATHEREXPERT
<br />7.5
<br />3,000
<br />1.40
<br />91.0
<br />0.80
<br />91.0
<br />84,4
<br />1 ST STAGE= 1200
<br />1ST STAGE -_98
<br />13.0
<br />EER
<br />208
<br />310
<br />60
<br />36
<br />500
<br />REQUIRED
<br />2,000
<br />PROVIDE
<br />UNIT TO
<br />WITH MEDIUM STATIC DRIVE
<br />HAVE 3 STAGES OF COOLING (MIN)
<br />2G
<br />MODEL: 48LCD-008
<br />FILTERS, AND
<br />RECIRCULATING PUMP,
<br />4. PROVIDE UNIT WITH A VENTSTAR MODEL T8850 PROGRAMMABLE THERMOSTAT.
<br />2ND STAGE=150
<br />2ND STAGE=120
<br />45
<br />COOLING
<br />LISTED AT 3RD
<br />STAGE
<br />AC
<br />3G
<br />CARRIER WEATHEREXPERT
<br />MODEL: 48LCD-005
<br />4
<br />1,600
<br />1,600
<br />0.95
<br />0.80
<br />4.9.1
<br />366
<br />IST STAGE=50.0
<br />2ND STAGE=72.0
<br />1ST STAGE=41.0
<br />2ND STAGE=56.0
<br />16.4
<br />SEER
<br />208
<br />30
<br />60
<br />27
<br />40
<br />625
<br />NOT REQUIRED
<br />1,200
<br />UNIT TO
<br />COOLING
<br />HAVE 2 STAGES
<br />LISTED AT 2ND
<br />OF COOLING (MIN)
<br />STAGE
<br />NOTES:
<br />1. SCHEDULED COOLING CAPACITIES ARE LISTED AT NOMINAL CFM (400 CFM/TON)
<br />AT ARI CONDITIONS - 95-F AMBIENT, 80-F DB
<br />/' 67°F WB. REFERENCE FLOORPLANS FOR
<br />ACTUAL DESIGN CFM AND BALANCE ACCORDINGLY.
<br />2. PROVIDE ALL UNITS WITH THE FOLLOWING MANUFACTURER'S FACTORY INSTALLED
<br />OPTIONS
<br />/ ACCESSORIES:
<br />- HINGED ACCESS PANELS
<br />- COIL GUARDS
<br />- 2" PLEATED FILTERS (MERV 13 FILTERS)
<br />- TXV VALVE
<br />- 0-1009 ENTHALPY ECONOMIZER WITH BAROMETRIC RELIEF. PROVIDE WITH
<br />JADE T24
<br />COMPLIANT CONTROLLER.
<br />- CARRIER COMFORTLINK CONTROLS
<br />3. PROVIDE EACH UNIT WITH A VENTSTAR MODEL T8850 PROGRAMMABLE THERMOSTAT.
<br />4. AC/1G MINIMUM OUTSIDE AIR TO BE 1,200 WHEN CO2 IS SATISFIED. MINIMUM
<br />OUTSIDE
<br />AIR WHEN CO2 IS NOT SATISFIED TO BE 3,000 CFM
<br />5. AC UNIT AC/IG TO BE PROVIDED WITH MICROMETAL PCD--HE34F-2MH POWER EXHAUST.
<br />POWER EXHAUST TO BE 23OV/30,
<br />MODULATING EXHAUST, EQUIPED WITH TWO 3
<br />HP MOTORS AND CAPABLE OF EXHAUSTING 9,900 CFM AT 2" WC. POWER EXHAUST FLA = 17.6
<br />ITEM TO BE REMOVED / DEMOED
<br />RETURN OR EXHAUST AIR DUCT
<br />SUPPLY AIR DUCT
<br />FLEXIBLE CONNECTION
<br />------- - �� BLV BALL VALVE
<br />BV. BALANCE VALVE
<br />BFV BUTTERFLY VALVE
<br />---+�- CKV. CHECK VALVE
<br />THERMOMETER, PRESSURE GAUGE
<br />-;�-- OUTSIDE AIR INTO LOUVER
<br />-r---- RETURN OR EXHAUST AIR INTO REGISTER
<br />SUPPLY AIR FROM REGISTER
<br />EXHAUST AIR DUCT SECTION
<br />RETURN AIR DUCT SECTION
<br />SUPPLY AIR DUCT SECTION
<br />12 x 10 DUCT FIRST FIGURE 510E SHOWN
<br />SECON FIGURE SIDE NOT SHOWN)
<br />SQUARE TO ROUND TRANSITION
<br />fF� TURNING VANES
<br />--� FLEXIBLE DUCTWORK
<br />VCD VCD
<br />---�-' VOLUME CONTROL DAMPER
<br />R _ D_
<br />RISE OR DROP IN DIRECTION OF ARROW
<br />SUPPLY AIR GRILLE ID ZE
<br />CFM
<br />RETURN AIR GRILLE ID -I -E--
<br />FM
<br />EXHAUST AIR GRILLE ID
<br />.. !.
<br />' rainarchitects
<br />forth
<br />ROOM THERMOSTAT (SEE MECHANICAL NOTES
<br />FOR MOUNTING HEIGHT)
<br />Yom' DIAMETER
<br />AC AIR CONDITIONING
<br />AD, AP ACCESS DOOR, ACCESS PANEL
<br />CC CENTER TO CENTER
<br />CFM,f CUBIC FEET OF AIR PER MINUTE
<br />(E), (N) EXISTING, NEW
<br />EA EXHAUST AIR
<br />EAD EXHAUST AIR DAMPER
<br />EF EXHAUST FAN
<br />`F DEGREES FAHRENHEIT
<br />FA / FB FROM ABOVE / FROM BELOW
<br />FD / FSD FIRE DAMPER / FIRE SMOKE DAMPER >;
<br />GA. GAUGE ='
<br />GALV. GALVANIZED
<br />ESTON
<br />GPM GALLONS PER MINUTE ASSOCIATES
<br />HP / 6HP HORSEPOWER / BREAK HORSEPOWER
<br />MAX., MIN. MAXIMUM, MINIMUM
<br />MECHANICAL ENGINEERS
<br />M.D. MANUAL DAMPER 4701 ANNE WAY k CARMICHAEL, CA 95608 1 (91 b) 4€ 2-0820
<br />NA NOT APPLICABLE WESTON & ASSOCIATES #15012
<br />NTS NOT TO SCALE
<br />pFESS�G�
<br />PRV. PRESSURE REDUCING VALVE e ®® A, pit E -le
<br />OA OUTSIDE AIR.y
<br />c� � No. M312 a u
<br />OAD OUTSIDE AIR DAMPER '
<br />IRA RETURN AIR
<br />RENEWAL DATE:
<br />RAO RETURN AIR DAMPER v�'� v31t2015C�_-
<br />flA N
<br />RF RELIEF FAN
<br />SMS SHEET METAL SCREW
<br />SA, OA, SUPPLY AIR, OUTSIDE AIR
<br />TA / T8 TO ABOVE / TO BELOW
<br />T.C.V. TEMPERATURE CONTROL VALVE
<br />T.C.P. TEMPERATURE CONTROL PANEL
<br />TYP. TYPICAL
<br />$ ON/OFF SWITCH / STARTER
<br />ROOM NAME ROOM NAME AND NUMBER
<br />0
<br />ALL WORK PERFORMED UNDER THIS CONTRACT IS TO CONFIRM TO THE FOLLOWING
<br />CODES AND REGULATIONS:
<br />1. CALIFORNIA ADMINISTRATIVE CODE, 2013
<br />2. CALIFORNIA BUILDING CODE, 2013
<br />3. CALIFORNIA MECHANICAL CODE, 2013
<br />4. CALIFORNIA PLUMBING CODE, 2013
<br />5. CALIFORNIA FIRE CODE, 2013
<br />6. CALIFORNIA ELECTRICAL. CODE, 2013
<br />7. CALIFORNIA ENERGY CODE, 2013
<br />THE ABOVE CODES AND REGULATIONS REFER TO THE LATEST EDITION OR REVISION IF
<br />FORCE ON THE DATE OF THE CONTRACT, UNLESS OTHERWISE STATED. NOTHING ON
<br />THE DRAWINGS IS TO BE CONSTRUED AS REQUIRING OR PERMITTING WORK THAT IS
<br />CONTRARY TO THE LISTED CODES AND REGULATIONS, OR OTHER LOCAL, STATE OR
<br />FEDERAL CODES OR REGULATIONS WHICH MAY BE APPLICABLE.
<br />Copyright Q 2014 Rainforth Grau Architects. All rights reserved. Reproduction of ftse plans, either In whole or In part, Intruding any form
<br />of copying andfor proration of derlvaM works toed, for any reason vA#*ut prior wri ten permission, is Wcdy prol•rltaited,
<br />mu
<br />File tela.: 39-53
<br />IDENTIFICATION STAMP
<br />DIV. OF THE STATE ARCHITECT
<br />02-114490 INC. 1
<br />AC r' FLSSS
<br />DATE i 1/ D )/jS-
<br />pr
<br />r::.�
<br />INCREMENT
<br />CAFETERIA
<br />MANTECAUNIFIED SCHOOL
<br />VIANTECA, CALIFORNIA
<br />MECHANICAL -
<br />LEGEND, SCHEDULES, AND NOTE]
<br />DRAW 4 DW PROJECT NO-
<br />CHECKED DATE
<br />DW
<br />SCALE SHEET
<br />15-1207
<br />06-26-15
<br />MADE-UP Alm"UNIT
<br />SCHEDULE
<br />SUPPLY AIR BLOWER
<br />EVAPORATIVE COOLING
<br />HEATING CAPACITY (BTUH)
<br />UNIT ELECTRICAL DATA
<br />MAXIMUM
<br />SYMBOL
<br />MANUFACTURER &
<br />MODEL NUMBER
<br />UNIT
<br />WEIGHT
<br />NOTES
<br />ESP.
<br />FLA
<br />FLA
<br />DESIGN CFM
<br />HP
<br />hHP
<br />TSP
<br />MIN.
<br />MBIA
<br />EDS
<br />EWB
<br />LD8
<br />INPUT
<br />OUTPUT
<br />VOLTS
<br />PHASE
<br />HERTZ
<br />(LBS.)
<br />MAU
<br />1 G
<br />GREENHECK
<br />MODEL. IG -109-H12
<br />1,200
<br />1/3
<br />0.28
<br />0.5
<br />0.65
<br />MIN.
<br />MBH
<br />97'F
<br />79F
<br />71'F
<br />100,000
<br />80,000
<br />120
<br />10
<br />60
<br />16.5
<br />20
<br />1,200
<br />HEATING TO BE 8 STAGES FURNACE CONTROL (MIN.)
<br />NOTES:
<br />1. PROVIDE UNIT WITH 2" MERV 8 PLEATED FILTERS
<br />2. UNIT TO BE INTERLOCKED TO KITCHEN HOOD AND EXHAUST FAN
<br />EF/4G, UNIT
<br />TO OPERATE WHENEVER EF/4G IS ENABLED.
<br />3, UNIT TO BE PROVIDED WITH THE FOLLOWING:
<br />- ROOF CURB AND PEDESTAL MOUNT
<br />- HINGED ACCESS PANELS
<br />- PLEATED FILTERS (MERV 8 FILTERS)
<br />- EVAPORATIVE COOLING WITH CELDEK MEDIA, 2" ALUM. MESH
<br />FILTERS, AND
<br />RECIRCULATING PUMP,
<br />4. PROVIDE UNIT WITH A VENTSTAR MODEL T8850 PROGRAMMABLE THERMOSTAT.
<br />ITEM TO BE REMOVED / DEMOED
<br />RETURN OR EXHAUST AIR DUCT
<br />SUPPLY AIR DUCT
<br />FLEXIBLE CONNECTION
<br />------- - �� BLV BALL VALVE
<br />BV. BALANCE VALVE
<br />BFV BUTTERFLY VALVE
<br />---+�- CKV. CHECK VALVE
<br />THERMOMETER, PRESSURE GAUGE
<br />-;�-- OUTSIDE AIR INTO LOUVER
<br />-r---- RETURN OR EXHAUST AIR INTO REGISTER
<br />SUPPLY AIR FROM REGISTER
<br />EXHAUST AIR DUCT SECTION
<br />RETURN AIR DUCT SECTION
<br />SUPPLY AIR DUCT SECTION
<br />12 x 10 DUCT FIRST FIGURE 510E SHOWN
<br />SECON FIGURE SIDE NOT SHOWN)
<br />SQUARE TO ROUND TRANSITION
<br />fF� TURNING VANES
<br />--� FLEXIBLE DUCTWORK
<br />VCD VCD
<br />---�-' VOLUME CONTROL DAMPER
<br />R _ D_
<br />RISE OR DROP IN DIRECTION OF ARROW
<br />SUPPLY AIR GRILLE ID ZE
<br />CFM
<br />RETURN AIR GRILLE ID -I -E--
<br />FM
<br />EXHAUST AIR GRILLE ID
<br />.. !.
<br />' rainarchitects
<br />forth
<br />ROOM THERMOSTAT (SEE MECHANICAL NOTES
<br />FOR MOUNTING HEIGHT)
<br />Yom' DIAMETER
<br />AC AIR CONDITIONING
<br />AD, AP ACCESS DOOR, ACCESS PANEL
<br />CC CENTER TO CENTER
<br />CFM,f CUBIC FEET OF AIR PER MINUTE
<br />(E), (N) EXISTING, NEW
<br />EA EXHAUST AIR
<br />EAD EXHAUST AIR DAMPER
<br />EF EXHAUST FAN
<br />`F DEGREES FAHRENHEIT
<br />FA / FB FROM ABOVE / FROM BELOW
<br />FD / FSD FIRE DAMPER / FIRE SMOKE DAMPER >;
<br />GA. GAUGE ='
<br />GALV. GALVANIZED
<br />ESTON
<br />GPM GALLONS PER MINUTE ASSOCIATES
<br />HP / 6HP HORSEPOWER / BREAK HORSEPOWER
<br />MAX., MIN. MAXIMUM, MINIMUM
<br />MECHANICAL ENGINEERS
<br />M.D. MANUAL DAMPER 4701 ANNE WAY k CARMICHAEL, CA 95608 1 (91 b) 4€ 2-0820
<br />NA NOT APPLICABLE WESTON & ASSOCIATES #15012
<br />NTS NOT TO SCALE
<br />pFESS�G�
<br />PRV. PRESSURE REDUCING VALVE e ®® A, pit E -le
<br />OA OUTSIDE AIR.y
<br />c� � No. M312 a u
<br />OAD OUTSIDE AIR DAMPER '
<br />IRA RETURN AIR
<br />RENEWAL DATE:
<br />RAO RETURN AIR DAMPER v�'� v31t2015C�_-
<br />flA N
<br />RF RELIEF FAN
<br />SMS SHEET METAL SCREW
<br />SA, OA, SUPPLY AIR, OUTSIDE AIR
<br />TA / T8 TO ABOVE / TO BELOW
<br />T.C.V. TEMPERATURE CONTROL VALVE
<br />T.C.P. TEMPERATURE CONTROL PANEL
<br />TYP. TYPICAL
<br />$ ON/OFF SWITCH / STARTER
<br />ROOM NAME ROOM NAME AND NUMBER
<br />0
<br />ALL WORK PERFORMED UNDER THIS CONTRACT IS TO CONFIRM TO THE FOLLOWING
<br />CODES AND REGULATIONS:
<br />1. CALIFORNIA ADMINISTRATIVE CODE, 2013
<br />2. CALIFORNIA BUILDING CODE, 2013
<br />3. CALIFORNIA MECHANICAL CODE, 2013
<br />4. CALIFORNIA PLUMBING CODE, 2013
<br />5. CALIFORNIA FIRE CODE, 2013
<br />6. CALIFORNIA ELECTRICAL. CODE, 2013
<br />7. CALIFORNIA ENERGY CODE, 2013
<br />THE ABOVE CODES AND REGULATIONS REFER TO THE LATEST EDITION OR REVISION IF
<br />FORCE ON THE DATE OF THE CONTRACT, UNLESS OTHERWISE STATED. NOTHING ON
<br />THE DRAWINGS IS TO BE CONSTRUED AS REQUIRING OR PERMITTING WORK THAT IS
<br />CONTRARY TO THE LISTED CODES AND REGULATIONS, OR OTHER LOCAL, STATE OR
<br />FEDERAL CODES OR REGULATIONS WHICH MAY BE APPLICABLE.
<br />Copyright Q 2014 Rainforth Grau Architects. All rights reserved. Reproduction of ftse plans, either In whole or In part, Intruding any form
<br />of copying andfor proration of derlvaM works toed, for any reason vA#*ut prior wri ten permission, is Wcdy prol•rltaited,
<br />mu
<br />File tela.: 39-53
<br />IDENTIFICATION STAMP
<br />DIV. OF THE STATE ARCHITECT
<br />02-114490 INC. 1
<br />AC r' FLSSS
<br />DATE i 1/ D )/jS-
<br />pr
<br />r::.�
<br />INCREMENT
<br />CAFETERIA
<br />MANTECAUNIFIED SCHOOL
<br />VIANTECA, CALIFORNIA
<br />MECHANICAL -
<br />LEGEND, SCHEDULES, AND NOTE]
<br />DRAW 4 DW PROJECT NO-
<br />CHECKED DATE
<br />DW
<br />SCALE SHEET
<br />15-1207
<br />06-26-15
<br />
|