SYSTEM GENERAL <br />PROVIDE VENTSTAR TITLE 24 COMPLIANT PROGRAMMABLE THERMOSTATS AS SHOWN ON THE DRAWINGS. <br />VENTSTAR THERMOSTATS ARE A DISTRICT STANDARD — NO SUBSTUTIONS SHALL BE ACCEPTED. <br />AC UNIT OPERATION: <br />THE OCCUPIED AND UNOCCUPIED SCHEDULES AND TEMPERATURE SET POINTS WILL BE PROGRAMMED INTO AC UNIT THERMOSTAT. THE <br />HEATING AND COOLING SET POINT SHALL BE AS FOLLOWS: <br />OCCUPIED UNOCCUPIED OCCUPIED UNOCCUPIED <br />SPACE TYPE COOLING SETPOINT COOLING SETPOINT HEATING SETPOINT HEATING SETPOINT <br />CLASSROOM TYPE SPACES: 74'F 2'F 87'F ±2'F 68'F ±2'F 4rF ±2`F <br />ADMIN AREAS / OFFICES: 74'F t27 87F t2'F 68'F f2'F 477 ±2'F <br />ALL SETPOINTS TO BE ADJUSTABLE. <br />UNIT TO SHUT DOWN UPON ACTIVATION OF THE AUTOMATIC FIRE SPRINKLER SYSTEM, <br />WHEN ECONOMIZER ERROR IS SENSED BY CONTROLLER, ERROR TO BE SENT TO THEIRMOSTATAT. THERMOSTAT TO BE PROGRAMMED TO <br />FLASH "FDI) EQUIPMENT ERROR". <br />SPLIT SYSTEM AC UNITS. <br />CONTRACTOR TO INTERLOCK THE LOW VOLTAGE CONTROL CIRCUIT BETWEEN THE AGE UNIT AND THE ACO UNIT. UNIT TO BE SET TO RUN <br />24 HOURS PER DAY / 7 DAYS PER WEEK / 365 DAYS PER YEAR. SET TEMPERATURE TO 78'F. <br />EXHAUST FAN CONTROL: <br />EXHAUST FAGS SHALL BE INTERLOCKED TO RUN WHEN EITHER THE UNIT(S) SERVING THE EF'S RESPECTIVE AREA IS IN OPERATION BY <br />THE TCC OR THE EXHAUST FAN SMALL BE INTERLOCK TO OPERATE WITH THE LIGHTS BY DIVISION 16. SEE EXHAUST FAN INTERLOCK <br />SCHEDULE. <br />POWER MIRING: <br />POWER WIRING TO ALL EQUIPMENT AND 120V POWER WIRING TO CONTROL PANELS SMALL BE BY ELECTRICAL CONTRACTOR. COORDINATE: <br />WITH CONTROLS CONTRACTOR, <br />OUTSIDE AIR <br />TEMPERATURE <br />SENSOR <br />20K NTC <br />EF <br />: RIB <br />INTERLOCK WITH <br />AC UNIT AS LISTED <br />115V POWER <br />BY DIVISION 16 <br />1. SEE PLANS AND SCHEDULES FOR QUANITIES <br />2. POWER BY DIVISION 16 <br />3. EF INTERLOCKED TO UNIT BY CONTROLS CONTRACTOR <br />4. REFERENCE EF SCHEDULE FOR INTERLOCK SCHEDULE <br />MIXED AIR <br />TEMPERATURE <br />SENSOR <br />20K NTC <br />MA <br />MA <br />CA HONEYWELL <br />OA W7220 <br />AUXZ-0 ECONOMIZER <br />IAQ CONTROLLER <br />ACT (2---1 OV) <br />ACT COM <br />ACT 24V <br />TR <br />TRI M7215 <br />IN + ECONOMIZER MOTOR <br />IN — <br />RQQF_ TQP <br />AC UNIT <br />O/B N Y1 Y2 W1 W2 G <br />AUXZ—I <br />UCC <br />E—GND <br />Y10 <br />AUX 1—O <br />Y21 <br />Y2O <br />Y1I <br />Y1O <br />C R <br />24 VAC THERMOSTAT <br />VENTSTAR <br />T8850 <br />NOTE: <br />1. THERMOSTAT TO BE PROGRAMMED TO FLASH — "FDD EQUIPMENT ERROR" UPON ECONOMIZER ERROR. <br />AC UNIT CONTROLS DIAGRAM <br />NTS <br />rainforth <br />f <br />architM <br />cts <br />L <br />4701 ANNE NAY I CARMICHAEL, CA 9560€3 ( (916) 482-0820 <br />WESTON & ASSOCIATES # 15-012 <br />�aFEsslo <br />QO O A. E art <br />No. M31220 0 <br />W3 o— ® I --A# Z <br />k RENEWAL DATE: <br />T�� 9713'12015 � <br />4� <br />�A 1 �� <br />Q-1 0At.t� <br />Copyright 0 2614 Rainforth Grau Architects. Aft rights reserved. Reproduclion of thew plans, either in whole or in part, including any form <br />of copying andior preparation of derivative works thereof, for any mason wiffmt prior wriffen penission, is strtcfly prohibited. <br />DSA <br />Fife No.: 39-53 <br />IDENTIFICATION STAMP <br />DIV. OF THE STATE ARCHITECT <br />02-114490 INC. 1 <br />ACA2f FLS s's <br />BATE _ I_0 0/t_r- <br />DRAWN <br />DW <br />CHECKED <br />DW <br />SCALE <br />PROJECT NO. <br />15-1207 <br />DATE <br />€3626-15 <br />SHEET <br />M5.1 .1 <br />MATERIAL LEGEND <br />ALL PART NUMBERS ARE ALERTON BACTALK UNLESS OTHERWISE NOTED <br />SYMBOL <br />DESCRIPTION <br />DTS <br />6" DUCT TEMPERATURE SENSOR <br />CS <br />VERIS H-600 CURRENT SWITCH <br />DA <br />FACTORY PROVIDED BEUMO DAMPER ACTUATOR (SIZE AS REQD) <br />MS <br />MOTOR STARTER WITH 120V CONTROL CIRCUIT BY OTHERS <br />ENOL -1 <br />NEMA -1 CONTROL PANEL FOR INDOOR MOUNTING <br />SNCL -3R <br />NEMA -3R CONTROL PANEL FOR OUTDOOR MOUNTING <br />CO2 <br />VERIS 0---2000 PPM ROOM CO2 SENSOR <br />VFD <br />FACTORY PROVIDED POKIER EXHAUST VFD INTERLOCK TO OSA DAMPER <br />RIES <br />FUNCTIONAL DEVICES RELAY IN A BOX <br />SD <br />FIRE MARSHALL APPROVED DUCT SMOKE DETECTOR (PROVIDED BY DIV 16) <br />PWR <br />POWER TO EQUIPMENT BY DIVISION 16 <br />PWR/FA <br />120V PWR AND FIRE ALARM WIRING BY DIV. 16 <br />TX <br />120V TO 24V TRANSFORMER <br />EA EXHAUST AIR <br />AI ANALOG INPUT <br />SA SUPPLY AIR <br />BI BINARY INPUT <br />RA RETURN AIR <br />AO ANALOG OUTPUT <br />OSA OUTSIDE AIR <br />BO BINARY OUTPUT <br />SYSTEM GENERAL <br />PROVIDE VENTSTAR TITLE 24 COMPLIANT PROGRAMMABLE THERMOSTATS AS SHOWN ON THE DRAWINGS. <br />VENTSTAR THERMOSTATS ARE A DISTRICT STANDARD — NO SUBSTUTIONS SHALL BE ACCEPTED. <br />AC UNIT OPERATION: <br />THE OCCUPIED AND UNOCCUPIED SCHEDULES AND TEMPERATURE SET POINTS WILL BE PROGRAMMED INTO AC UNIT THERMOSTAT. THE <br />HEATING AND COOLING SET POINT SHALL BE AS FOLLOWS: <br />OCCUPIED UNOCCUPIED OCCUPIED UNOCCUPIED <br />SPACE TYPE COOLING SETPOINT COOLING SETPOINT HEATING SETPOINT HEATING SETPOINT <br />CLASSROOM TYPE SPACES: 74'F 2'F 87'F ±2'F 68'F ±2'F 4rF ±2`F <br />ADMIN AREAS / OFFICES: 74'F t27 87F t2'F 68'F f2'F 477 ±2'F <br />ALL SETPOINTS TO BE ADJUSTABLE. <br />UNIT TO SHUT DOWN UPON ACTIVATION OF THE AUTOMATIC FIRE SPRINKLER SYSTEM, <br />WHEN ECONOMIZER ERROR IS SENSED BY CONTROLLER, ERROR TO BE SENT TO THEIRMOSTATAT. THERMOSTAT TO BE PROGRAMMED TO <br />FLASH "FDI) EQUIPMENT ERROR". <br />SPLIT SYSTEM AC UNITS. <br />CONTRACTOR TO INTERLOCK THE LOW VOLTAGE CONTROL CIRCUIT BETWEEN THE AGE UNIT AND THE ACO UNIT. UNIT TO BE SET TO RUN <br />24 HOURS PER DAY / 7 DAYS PER WEEK / 365 DAYS PER YEAR. SET TEMPERATURE TO 78'F. <br />EXHAUST FAN CONTROL: <br />EXHAUST FAGS SHALL BE INTERLOCKED TO RUN WHEN EITHER THE UNIT(S) SERVING THE EF'S RESPECTIVE AREA IS IN OPERATION BY <br />THE TCC OR THE EXHAUST FAN SMALL BE INTERLOCK TO OPERATE WITH THE LIGHTS BY DIVISION 16. SEE EXHAUST FAN INTERLOCK <br />SCHEDULE. <br />POWER MIRING: <br />POWER WIRING TO ALL EQUIPMENT AND 120V POWER WIRING TO CONTROL PANELS SMALL BE BY ELECTRICAL CONTRACTOR. COORDINATE: <br />WITH CONTROLS CONTRACTOR, <br />OUTSIDE AIR <br />TEMPERATURE <br />SENSOR <br />20K NTC <br />EF <br />: RIB <br />INTERLOCK WITH <br />AC UNIT AS LISTED <br />115V POWER <br />BY DIVISION 16 <br />1. SEE PLANS AND SCHEDULES FOR QUANITIES <br />2. POWER BY DIVISION 16 <br />3. EF INTERLOCKED TO UNIT BY CONTROLS CONTRACTOR <br />4. REFERENCE EF SCHEDULE FOR INTERLOCK SCHEDULE <br />MIXED AIR <br />TEMPERATURE <br />SENSOR <br />20K NTC <br />MA <br />MA <br />CA HONEYWELL <br />OA W7220 <br />AUXZ-0 ECONOMIZER <br />IAQ CONTROLLER <br />ACT (2---1 OV) <br />ACT COM <br />ACT 24V <br />TR <br />TRI M7215 <br />IN + ECONOMIZER MOTOR <br />IN — <br />RQQF_ TQP <br />AC UNIT <br />O/B N Y1 Y2 W1 W2 G <br />AUXZ—I <br />UCC <br />E—GND <br />Y10 <br />AUX 1—O <br />Y21 <br />Y2O <br />Y1I <br />Y1O <br />C R <br />24 VAC THERMOSTAT <br />VENTSTAR <br />T8850 <br />NOTE: <br />1. THERMOSTAT TO BE PROGRAMMED TO FLASH — "FDD EQUIPMENT ERROR" UPON ECONOMIZER ERROR. <br />AC UNIT CONTROLS DIAGRAM <br />NTS <br />rainforth <br />f <br />architM <br />cts <br />L <br />4701 ANNE NAY I CARMICHAEL, CA 9560€3 ( (916) 482-0820 <br />WESTON & ASSOCIATES # 15-012 <br />�aFEsslo <br />QO O A. E art <br />No. M31220 0 <br />W3 o— ® I --A# Z <br />k RENEWAL DATE: <br />T�� 9713'12015 � <br />4� <br />�A 1 �� <br />Q-1 0At.t� <br />Copyright 0 2614 Rainforth Grau Architects. Aft rights reserved. Reproduclion of thew plans, either in whole or in part, including any form <br />of copying andior preparation of derivative works thereof, for any mason wiffmt prior wriffen penission, is strtcfly prohibited. <br />DSA <br />Fife No.: 39-53 <br />IDENTIFICATION STAMP <br />DIV. OF THE STATE ARCHITECT <br />02-114490 INC. 1 <br />ACA2f FLS s's <br />BATE _ I_0 0/t_r- <br />DRAWN <br />DW <br />CHECKED <br />DW <br />SCALE <br />PROJECT NO. <br />15-1207 <br />DATE <br />€3626-15 <br />SHEET <br />M5.1 .1 <br />