Hydraulic Information
<br />Remote Area Remote Area #3
<br />OCCUPANCY CLASSIFICATION
<br />Light Hazard
<br />DENSITY
<br />0, 1 00gpm/W for 1 500.00ft2 (Actual 1628.60ft2)
<br />TOTAL HOSE STREAMS
<br />100.00
<br />TOTAL HEADS FLOWING
<br />15
<br />K -FACTOR
<br />5.6
<br />TOTAL WATER REQUIRED
<br />338.36
<br />TOTAL PRESSURE REQUIRED
<br />35,648
<br />BASE of RISER (gpm)
<br />238.35
<br />BASE of RISER (psi)
<br />25.229
<br />SAFETY MARGIN (psi)
<br />+15.910 (30.90A)
<br />Hydraulic Information
<br />Remote Area Remote Area #4
<br />OCCUPANCY CLASSIFICATION
<br />Light Hazard
<br />DENSITY
<br />0. 1 00gpmtft2 for 1500,00112 (Actual 1089.94fV)
<br />TOTAL HOSE STREAMS
<br />100,00
<br />TOTAL HEADS FLOWING
<br />13
<br />K -FACTOR
<br />1
<br />15.6
<br />TOTAL WATER REQUIRED
<br />1326.23
<br />TOTAL PRESSURE REQUIRED
<br />42.915
<br />BASE of RISER (gpm)
<br />226,23
<br />BASE of RISER (psi)
<br />32.565
<br />SAFETY MARGIN (ps)
<br />+8,669 (16.8%)
<br />5
<br />6
<br />\ I ... ..... ... .. . .......... . . . ... . . ..
<br />8
<br />N) CAFETERIA OVERHEAD PIPING PLAN
<br />------------------
<br />SCALE: I/&'= 1'-a'NORTH
<br />PIPING NOTES:
<br />1.) ALLWELDED MAIN PIPING TO BE 'ALLIED TUBE & CONDUIT" OR "BULL MOOSE TUBE" SCHEDULE 10 PIPE TYP. U.N.O.
<br />2.) ALL WELDED BRANCHLINE PIPING TO BE "ALLIED TUBE & CONDUIT" OR "BULL MOOSE TUBE" SCHEDULE 40 PIPE TYR U.N.O.
<br />3.) ALL THREADED PIPING TO BE "ALLIED TUBE & CONDUIT" OR "BULL MOOSE TUBE" SCHEDULE 40 PIPE TYR U.N.O.
<br />4.) ALL BRANCHLINES ARE TO BE HUNG ATA CENTERLINE OF 1'4' & 1'-10" BOTTOM OF DECK (+ VARIES A.FF) TYR U.N.O.
<br />5,) ALL MAINS ARE TO BE HUNG AT A CENTERLINE OF 1'-10'" & 24" BOTTOM OF DECK (+ VARIES A.F.F.) TYR U.N.O.
<br />6.) ALL UPRIGHT SPRINKLER HEADS TO BE "TYCO"TY-FRB QUICK RESPONSE SPRINKLERS WITH A DEFLECTOR DISTANCE
<br />OF V MINIMUM AND 12" MAXIMUM FROM THE BOTTOM OF DECK TYR U.N.O.
<br />7.) ALL 2112" MAINS TO BE BRACED WITH TYPE BR -1, BR -2
<br />(BRA) LATERAL: 30'-{Y" ON CENTER, ORIENTATION TYPE E (45-90 deg), T-0" MAX. LENGTH,
<br />(BR -2) LONGITUDINAL: 30'-0" ON CENTER, ORIENTATION TYPE E (45-90 deg), T-09'MAX, LENGTH.
<br />8.) ALL 3" MAINS TO BE BRACED WITH TYPE BR -3, BR -4, BR -5
<br />(BR -3) LATERAL: 20'-0'' ON CENTER, ORIENTATION TYPE E (45-90 deg), 7'-0" MAX. LENGTH.
<br />(BR -4) LONGITUDINAL., 50-0" ON CENTER, ORIENTATION TYPE H (45-90 deg), T-0" MAX. LENGTH.
<br />(BR -5) LONGITUDINAL: 20'-0" ON CENTER, ORIENTATION TYPE H (45-90 deg), 71-01' MAX, LENGTH -
<br />9.) ALL 4" MAINS TO BE BRACED WITH TYPE BR -6, BR -7
<br />(BR -6) LATERAL 35`-0" ON CENTER, ORIENTATION TYPE E (45.90 deg), T-0" MAX. LENGTH.
<br />(BR -7) LONGITUDINAL* 80'-0" ON CENTER, ORIENTATION TYPE H (45-90 deg), 71-0" MAX. LENGTH.
<br />10,) SPRINKLERS SHALL BE PERMITTED TO BE OMITTED WHERE THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS
<br />THAT ARE NONCOMBUSTIBLE, LIMITED -COMBUSTIBLE, OR FIRE RETARDANT -TREATED WOOD AS DEFINED IN NFRA #703.
<br />(PER NFPA#13 2013 EDITION - SECTION 8.15,7.2)
<br />IM
<br />E (G
<br />(B D
<br />H
<br />V li*4
<br />364%
<br />V
<br />Z-7 27'-41/1 V-7 W-10%
<br />.... ........ . ... . . . ... ......... --.-____.......£i'.:
<br />....... .
<br />ii
<br />4'_9% T -91h 6_0% 91-10%
<br />. . .... . . ....... ji
<br />v-9.1 II
<br />It 16-10
<br />r� -*z
<br />up 1-0. 150apm1W for 1600.00W
<br />a
<br />I?
<br />to
<br />C11
<br />LN
<br />4
<br />.. .... . ... . ....... ...... .. ....... .... .. .. . .. . . -4 ... ........ . .. ... .... .....
<br />CJ r
<br />5
<br />HydraulicHydraulic Information
<br />Remote Area Remote Area #2
<br />OCCUPANCY CLASSIFICATION
<br />Ordinary Group I
<br />DENSITY
<br />0. 150gpmtft2 for 1500.00ft' (Actual 1372-49ft2)
<br />TOTAL HOSE STREAMS
<br />100.00
<br />TOTAL HEADS FLOWING
<br />16
<br />K -FACTOR
<br />5,6
<br />TOTAL WATER REQUIRED
<br />406.27
<br />TOTAL PRESSURE REQUIRED
<br />39.425
<br />BASE of RISER (gpm)
<br />306.27
<br />BASE of RISER (psi)
<br />28.592
<br />SAFETY MARGIN (psi)
<br />+11 .955 (23-30/6)
<br />Hydraulic Information
<br />Remote Area Remote Area #1
<br />OCCUPANCY CLASSIFICATION Light Hazard
<br />DENSITY
<br />0. 100gpm/ft2 for 1 600,00ft2 (Actual 1567.38ft2)
<br />TOTAL HOSE STREAMS
<br />100.00
<br />TOTAL HEADS FLOWING
<br />19
<br />K -FACTOR
<br />5.6
<br />TOTAL WATER REQUIRED
<br />436.36
<br />TOTAL PRESSURE REQUIRED
<br />44.329
<br />BASE of RISER (gpm)
<br />336.35
<br />BASE of RISER (psi)
<br />33,296
<br />SAFETY MARGIN (psi)
<br />1+6.967 (13.60/6)
<br />Sprinkler Legend
<br />Symbol
<br />SIN Model
<br />K -Factor Type
<br />Size
<br />l Response orifice
<br />Finish Temperature Note
<br />TY313 TY -FRB
<br />TY313 TY -FI 13
<br />_qq�an�fi
<br />54
<br />70
<br />5.6 Upright
<br />5.6 Upright
<br />%
<br />16
<br />Quick +!'
<br />Quick Y2`
<br />Bass 200OF
<br />Brass 200°F Head Guards
<br />TY323 TY -FRB
<br />29
<br />5.6 Pendent
<br />"A
<br />Quick "W'WhIte
<br />155°F
<br />TY323 TY -FRB
<br />12
<br />5.6 Pendent
<br />%
<br />Quick W'
<br />White 156°F 401 Esc.
<br />TY3531 RF -11
<br />8
<br />5,6 Pendent
<br />1/2
<br />Quick %"
<br />White 155OF
<br />TY3255 DS -1
<br />2
<br />5.6 Pendent
<br />'A
<br />Standard Ih"Wh
<br />ite 20011E
<br />Total = 175
<br />1
<br />raMforth
<br />gra U
<br />(Crga a r c hi t Lem c t s
<br />CEN. C A L
<br />FIRE SYSTEMS,, INC.
<br />CA Lic. No. 488547 NV Lic. No, 33006
<br />P.O. BOX 1284
<br />Lodi, CA 95241
<br />(209) 334-9119 Fax (209) 334-2923
<br />E- 4a: Sprkc@cen-calfirexom
<br />E Sy
<br />C41 . FORMA
<br />LICENSE NO.
<br />488547
<br />Cohimerciii.1 Industrial ResUentiat\ �oT�..�_ . ��;4�v
<br />FIRE SPRINKLER DRAWING PREPARED BYAND PROPERTY OF CEN -CAL
<br />FIRE SYSTEMS FOR USE INACCORD WITH SECTION 6737.40F PROFESSIONAL
<br />ENGINEERS ACT OF THE STATE OF CALIFORNIA. FIRE SPRINKLER DRAWING
<br />GUARANTEED ONLY IF 05N -CAL FIRE SYSTEMS IS THE INSTALLING CONTRACTOR.
<br />Copyright 0 2014 Rainforth Grau Architects. All rights reserved. Reproduction of these plans, either in whole or in part, including any form
<br />Of copying andfor preparation of derivative works thereof, for any reason without prior written permission, is strictly prohibited.
<br />DSA
<br />File No.
<br />IDENTIFICATION STAMP
<br />DIVOFTHE STATE ARCHITECT
<br />AC:j��r FLS O SS
<br />to
<br />DATE
<br />44
<br />CLASSROOM MODERNIZATION,
<br />INCREMENT 1: CAFETERIA
<br />MANTECA UNIFIED SCHOOL DISTRICT
<br />MANTECA, CALIFORNIA
<br />lei
<br />I oik 04MW
<br />DRAWN C.M.Q. PROJECT NO. 15-1207
<br />CM C-_ IAS_
<br />G-A.F
<br />SCA SHEE T
<br />FPw3
<br />
|