260500 ELECTRICAL WORK FOR COMMON RESULTS: <br /> A. SWITCH AND RECEPTACLE BOX SHALL BE ONE PIECE DRAWN OR STAMPED STEEL BOXES 2. WHERE CONDUIT IS ALLOWED TO BE EXPOSED, INSTALL THE CONDUIT PARALLEL WITH OR AT 7. THE SYSTEM SHALL AUTOMATICALLY SWITCH OFF ALL LIGHTS WHEN CONTROLLED SPACE <br /> 1. ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA MINIMUM SIZE SHALL BE FOUR INCHES (4") SQARE. BOXES SHALL BE FITTED WITH FLUSH DEVICE RIGHT ANGLES TO STRUCTURAL MEMBERS, WALLS, AND LINES OF THE BUILDING. BECOMES UNOCCUPIED AND SWITCH ON LIGHTS WHEN THE SPACE IS RE-OCCUPIED. ALL SENSORS SHALL <br /> CODE OF REGULATIONS, INCLUDING THE FOLLOWING: COVERS, PLASTER RINGS, OR TILE SWITCH RINGS IN MASONRY IN AREA WHERE EXPOSED WIRING IS BE PROVIDED WITH USER ADJUSTABLE TIME DELAY(15 SEC. TO 20 MINUTES) FOR "SWITCH-OFF" FUNCTION CD <br /> TITLE 24, CCR, PART 2, 2016 CBC PERMISSIBLE, BOXES SHALL BEFITTED WITH SURFACE TYPE COVERS. 3. INSTALL WHERE INDICATED, OR AS REQUIRED BY CODE, PULLBOXES AND JUNCTION BOXES OF AND ADJUSTABLE SENSITIVITY. CD <br /> TITLE 24, CCR, PART 3, 2016 CEC SUFFICIENT SIZE TO FACILITATE WIRING. BOXES SHALL BE SIZED TO PROPERLY ACCOMMODATE ALL p N <br /> TITLE 24, CCR, PART 4, 2016 CMC B. LIGHTING OUTLETS SHALL BE FOUR INCHES (4")OCTAGON, MINIMUM. CONDUCTORS ENTERING SAME. 8. LOW VOLTAGE WIRING IS NOT REQUIRED TO BE IN CONDUIT EXCEPT IN HARDLID CEILINGS WHEREp LO <br /> TITLE 24, CCR, PART 9, 2016 CFC SUCH WIRES SHALL BE RUN IN CONDUIT. O p 00 <br /> TITLE 24, CCR, PART 6, 2016 CALIFORNIA ENERGY CODE D. WEATHERPROOF BOXES SHALL BE APPLETON FD SERIES AND FITTED WITH GASKETED CAST 4. DO NOT INSTALL CONDUIT OR TUBING WHICH HAS BEEN CRUSHED OR DEFORMED. U � <br /> TITLE 24, CCR, PART 11, 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE COVERS. 262400. MAIN SERVICE SWITCHBOARD <br /> ALL APPLICABLE LOCAL CODES 5. RUN CONDUCTORS OF SAME CIRCUIT IN SAME CONDUIT. RUN CONDUCTORS OF DIFFERENT <br /> E. VOICE/DATA OUTLET BOXES SHALL BE 4_11/16"SQ.x2_1/8" DEEP MINIMUM, FITTED WITH PLASTER VOLTAGE SYSTEMS IN SEPARATE CONDUITS. 1. SQUARE D, EATON, OR APPROVED EQUAL, METAL ENCLOSED UNIT WITH UGPS, METERING SECTION, � O p <br /> 2. ELECTRICAL CONTRACTOR SHALL VERIFY POWER, TELEPHONE AND CABLE TV SERVICES AT SITE PRIOR RINGS. MAIN DISCONNECT AND GROUP MOUNTED, MOULDED CASE BRANCH CIRCUIT BREAKERS COMPLETE WITH N <br /> TO BIDDING. SERVICES TO CONFORM TO UTILITY COMPANY REQUIREMENTS. ELECTRICAL CONTRACTOR 6. INSTALL NO CONDUCTORS UNTIL WORK WHICH MIGHT CAUSE DAMAGE TO SUCH CONDUCTORS INTERCONNECTING BUS IN A FACTORY ASSEMBLED, INTEGRATED UNIT. ARRANGEMENT AND RATINGS OF <br /> SHALL ARRANGE FOR SERVICE INSTALLATIONS PER UTILITY COMPANY REQUIREMENTS AND PAY ALL F. BOXES FOR SPECIAL EQUIPMENT SHALL BE SUITABLE FOR THE PARTICULAR EQUIPMENT. OR THE CONDUIT HAS BEEN COMPLETED. EQUIPMENT ARE SHOWN ON DRAWINGS. UNIT SHALL MEET ALL UTILITY COMPANY REQUIREMENTS. U) =3UO Cz -0 <br /> CUSTOMER CHARGED SERVICE COSTS. COORDINATE WITH OWNER AND UTILITY COMPANY FOR SERVICE <br /> � <br /> INSTALLATION. G. BOXES SHALL BE LOCATED AND PLACED ACCORDING TO ARCHITECTURAL AND STRUCTURAL 7. KEEP ALL CONDUITS AT LEAST SIX INCHES AWAY FROM THE COVERING ON HOT WATER OR STEAM 2. SWITCHBOARD SHALL BE ENCLOSED STRUCTURE OF CODE GAUGE STEEL PLATES WITH REMOVABLE i AZ).) <br /> REQUIREMENTS. PIPES. FRONT. FULL FRONT ACCESS SHALL BE PROVIDED FOR CONNECTIONS AND OPERATIONS. FRONT Q <br /> 3. CONTRACTOR SHALL PROCURE AND PAY FOR ALL PERMITS, LICENSES, ETC. REQUIRED TO CARRY ON SECTIONS SHALL BE ATTACHED WITH MACHINE SCREWS, EVENLY SPACED. HINGED DOOR SHALL HAVE N r O <br /> AND COMPLETE THE WORK. 260550. WIRING METHODS: LINE VOLTAGE SYSTEMS (120V AND ABOVE): 8. CAP RACEWAY ENDS DURING CONSTRUCTION. CLEAN OR REPLACE CONDUITS IN WHICH WATER VAULT TYPE HANDLES AND LOCKS. UNITS SHALL BE NEMA 3R FOR OUTDOOR INSTALLATION AND NEMA 1 _ C>6 > p j <br /> OR FOREIGN MATTER HAVE ACCUMULATED, TO THE SATISFACTION OF THE ARCHITECT. FOR INDOOR INSTALLATION. p Q <br /> 4. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, TRANSPORTATION AND PERFORM ALL 1. ALL WIRING SHALL BE INSTALLED IN CONDUITS. CONDUITS SHALL BE RUN CONCEALED IN WALLS 00 �O <br /> OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER EXECUTION AND COMPLETION AND CEILINGS WHERE FEASIBLE. ALL CONDUITS INSTALLED SURFACE ON WALL SHALL BE PAINTED TO 9. CONDUITS SHALL BE SUPPORTED WITH STRAPS, WITH GALVANIZED MALLEABLE SPLIT RING AND 3. ALL BUSES SHALL BE COPPER OR ALUMINUM SIZED TO CONFORM TO UL TO LIMIT TEMPERATURE RISE. U - <br /> OF ALL"ELECTRICAL WORK"WHETHER SPECIFICALLY MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED MATCH WALL FINISH. MOUNT EXTERIOR CONDUITS ON WALL ON GALVANIZED UNISTRUTS. ALL SURFACE ROD FOR INDIVIDUAL RUNS OR WITH KINDORF OR UNISTRUT CHANNEL SUPPORTS FOR MULTIPLE RUNS. ALL BUS CONNECTIONS SHALL BE BOLTED. BUSES SHALL BE BRACED TO WITHSTAND, AS A MINIMUM, THE Cz � <br /> HEREIN, AND/OR IMPLIED THEREBY TO CARRY OUT THE APPARENT INTENT THEREOF. CONDUIT INSTALLATION/ RUNS SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. DISTANCE BETWEEN SUPPORTS SHALL NOT EXCEED 10 FEET. CONDUITS SHALL BE SUPPORTED SHORT CIRCUIT CURRENT INDICATED ON DRAWINGS. BUSES SHALL BE SEQUENCE PHASED AND SHALL 0 dj <br /> INDEPENDENTLY OF ONE ANOTHER. RUN FULL HEIGHT. i0 O <br /> 5. ALL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS' LABORATORIES, INC., SHALL 2. ALL CONDUITS RUN WITHIN INTERIOR FINISHED SPACES SUCH AS OFFICES, BREAKROOM, Q <br /> MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN RESTROOM ETC. SHALL BE RUN CONCEALED. 10. CONDUITS CONNECTED TO BOXES AND CABINETS SHALL BE FITTED WITH TWO LOCKNUTS AND z <br /> ESTABLISHED AND LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. INSULATED BUSHING, OA"A" SERIES. 4. SERVICE SWITCHBOARD SHALL HAVE PERMANENTLY INSTALLED USER-ACCESSIBLE METERING OF N <br /> 3. ALL CONDUITS RUN IN DEDICATED ELECTRICAL AND MECHANICAL ROOMS SHALL BE RUN TOTAL ELECTRICAL ENERGY USE PER TABLE 130.5-A OF THE 2016 CALIFORNIA ENERGY CODE. AS A U) � 0 <br /> 6. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE AND LOCATIONS EXPOSED. 11. CONDUITS NOT CONNECTED WITH LOCKNUTS AND BUSHINGS SHALL BE FITTED WITH GROUNDING MINIMUM THIS REQUIRES THE FOLLOWING: 00 <br /> OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, CONTRACTOR SHALL MAKE USE OF ALL DATA BUSHING, OZ"BL" SERIES, U. L. APPROVED AND BONDED. <br /> IN ALL CONTRACT DOCUMENTS AND VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE 4. MINIMUM CONDUIT SIZE SHALL BE 1/2"ABOVE GRADE AND 3/4" UNDERGROUND. a. INSTANTANEOUS KW DEMAND. <br /> RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES. 12. CONDUIT STRAPS FOR INDIVIDUAL RUNS SHALL BE SECURED BY TOGGLE BOLTS ON HOLLOW b. HISTORICAL PEAK KW DEMAND. <br /> 5. MINIMUM ACCEPTABLE CONDUITS ARE: MASONRY, EXPANSION ANCHORS ON SOLID CONCRETE OR MASONRY, MACHINE SCREWS OR BOLTS ON c. RESETTABLE KWH. <br /> 7. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE INSTALLED AT LEAST 24" METAL SURFACES AND WOOD SCREWS ON WOOD CONSTRUCTION. THE USE OF NAILS TO ANCHOR <br /> BELOW GRADE UNLESS OTHERWISE NOTED. BACKFILL IN 6"THICK, PROPERLY MOISTENED LAYERS, A. GALVANIZED RIGID STEEL- FOR USE ON: STRAPS ON WOOD CONSTRUCTION IS PROHIBITED. STRAPS SHALL BE TWO HOLE MALLEABLE IRON OR 5. THE DISTRIBUTION SECTION SHALL BE SET UP TO PERMIT IN FUTURE THE DISAGGREGATED <br /> SOLIDLY PACKED AND IRON TAMPED TO A DENSITY NOT LESS THAN THAT OF ADJACENT, UNDISTURBED (1) EXTERIOR WALL SURFACES. SNAP-TYPE STEEL WITH RIBBED BACK, GALVANIZED OR CADMIUM PLATED. THE USE MEASUREMENT OF ELECTRICAL LOAD ENERGY USES DOWNSTREAM FROM THE SERVICE ACCORDING TO <br /> EARTH. RESTORE SURFACES, ROADWAYS, WALKS, CURBS, WALLS AND EXISTING UNDERGROUND TABLE 130.5-B OF THE 2016 CALIFORNIA ENERGY CODE. <br /> INSTALLATIONS TO ORIGINAL CONDITION IN AN ACCEPTABLE MANNER. B. GALVANISED STEEL EMT FOR USE: 13. PLACEMENT OF ALL BOXES SHALL BE GOVERNED BY APPLICABLE ARCHITECTURAL AND <br /> (1) CONCEALED IN INDOOR FINISHED SPACES. STRUCTURAL REQUIREMENTS. 6. PROVIDE "SPACES" INDICATED ON DRAWINGS WITH ALL NECESSARY MOUNTING HARDWARE Ln <br /> 8. ALL ELECTRICAL EQUIPMENT EXPOSED TO THE WEATHER SHALL BE LISTED FOR EXTERIOR USE. (2) EXPOSED INSIDE ELECTRICAL& MECHANICAL ROOMS. PERMITTING EASY FUTURE INSTALLATION OF BREAKERS IN THE FIELD. cn <br /> 14. CONDUIT FITTINGS: EXCEPT WHERE OTHERWISE NOTED, CONDUIT FITTINGS SHALL BE APPLETON E o <br /> 9. ALL U.L. LISTED EQUIPMENT SHALL BE INSTALLED AS PER THEIR LISTING OR LABELING. C. LIQUID TIGHT STEEL FLEX: OR APPROVED EQUAL. UNILETS SHALL BE MALLEABLE IRON AND FITTED WITH COVERS AND GASKETS. 7. PROVIDE INCOMING SERVICE TERMINALS, METERING SECTIONS, CTs, ETC. IN ACCORDANCE WITH THE W ° °' CD <br /> (1) FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT. LENGTH SHALL NOT EXCEED 36". UTILITY COMPANY AND PLANS. 3 w <br /> Cn3 <br /> ° .- 3 <br /> 10. IN LOCATIONS WHERE ELECTRICAL EQUIPMENT WOULD BE EXPOSED TO PHYSICAL DAMAGE, 15. TELEPHONE AND SIGNAL CONDUIT BENDS WHERE REQUIRED SHALL HAVE A RADIUS OF TEN TIMES c -c- Q <br /> ENCLOSURES OR GUARDS SHALL BE SO ARRANGED AND OF SUCH STRENGTH AS TO PREVENT SUCH D. FLEXIBLE STEEL CONDUIT: THE CONDUIT TRADE SIZE. 8. PROVIDE A COPPER GROUND BUS. T Cn <br /> DAMAGE. (1) FOR INDOOR FINAL CONNECTION TO RECESSED LIGHT FIXTURES. LENGTH SHALL NOT EXCEED 72". a52 <br /> (2) FOR INDOOR FINAL CONNECTION TO HVAC EQUIPMENT. LENGTH SHALL NOT EXCEED 36". 16. PROVIDE PULL TAPE IN ALL EMPTY CONDUITS. 262417. PANELBOARDS: E ° _0 ami o <br /> 11. CONFLICTS BETWEEN SPECIFICATIONS AND PLANS: �, ° <br /> E. "PVC" SCHEDULE 40: 260551.01. PENETRATIONS OF FIRE-RATED ASSEMBLIES: 1. UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE PANEL SCHEDULE, WITH o .o m <br /> Fn <br /> a. ANY CONFLICT BETWEEN ELECTRICAL SPECIFICATIONS AND ELECTRICAL PLANS; OR BETWEEN (1) FOR CONDUITS RUN UNDERGROUND AND FOR UNDER BUILDING SLAB. THE NUMBER AND SIZE OF BREAKERS AS INDICATED ON THE PANEL SCHEDULE. SINGLE POLE, TWO POLE, c a� <br /> ELECTRICAL PLANS AND PLANS OF ANOTHER DISCIPLINE SHALL BE BROUGHT TO THE ATTENTION OF THE (2) CONDUIT STUBUPS THROUGH THE FLOOR OR GRADE SHALL BE IN PVC WRAPPED RIGID STEEL 1. PENETRATIONS OF PIPES, CONDUITS, ETC., IN WALLS AND CEILINGS REQUIRING PROTECTED AND THREE POLE BREAKERS SHALL BE BOLT-ON TYPE. MULTIPLE POLE BREAKERS SHALL HAVE COMMON E <br /> ENGINEER AND A RESOLUTION RECEIVED PRIOR TO PROCUREMENT OR INSTALLATION OF THE ITEM IN CONDUIT. PVC WRAPPING SHALL EXTEND 6"ABOVE FINISHED FLOOR OR GRADE. OPENINGS SHALL BE FIRESTOPPED IN ACCORDANCE WITH CBC SECTION 714. FIRE STOP MATERIAL SHALL INTERNAL TRIP CONNECTION. SINGLE POLE BREAKERS SHALL NOT BE TIED AT HANDLES TO FORM ° <br /> QUESTION. (3) NOT PERMITTED FOR WIRING ABOVE FINISHED FLOOR INSIDE BUILDINGS BE A TESTED ASSEMBLY APPROVED BY AUTHORITY HAVING JURISDICTION. MULTIPLE POLE BREAKERS. THE PANEL DOORS SHALL BE DOOR-IN-DOOR CONSTRUCTION AND SHALL <br /> HAVE FLUSH TYPE LOCKS, ALL LOCKS SHALL BE KEYED ALIKE AND HAVE TYPEWRITTEN DIRECTORIES <br /> b. IF THE CONTRACTOR PROCEEDS WITH THE WORK WITHOUT RECEIVING ANY RESOLUTION TO THE F. ALUMINUM CONDUITS, IMC CONDUITS OR ALUMINUM FITTINGS ARE NOT APPROVED FOR USE ON 2. THROUGH PENETRATIONS AND MEMBRANE PENETRATIONS OF FIRE-RESISTANCE RATED WALLS INDICATING FIXTURES, EQUIPMENT, OR OUTLETS SERVICE BY EACH BREAKER. PANELS SHALL HAVE <br /> CONFLICT HE/SHE DOES SO AT HIS/HER OWN RISK AND SHALL RECTIFY THE WORK TO THE SATISFACTION THIS PROJECT. SHALL COMPLY WITH CBC 714.3. COPPER BUSSING. <br /> OF THE ENGINEER AT NO ADDITIONAL COST TO THE OWNER OR ENGINEER. <br /> G. ALL CONDUIT FITTINGS SHALL BE MALLEABLE IRON/STEEL. 3. PENETRATIONS OF FIRE RESISTANCE RATED FLOOR, FLOOR/CEILING ASSEMBLY OR THE CEILING 262726. WIRING DEVICES: <br /> 260500.01. HVAC SYSTEMS: MEMBRANCE OF A ROOF/CEILING ASSEMBLY SHALL COMPLY WITH CBC 714.4. <br /> H. COUPLING: 1. UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS (BROWN, <br /> 1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT (1) EMT COUPLING -APPLETON TWC-CS SERIES 4. ALL ELECTRICAL BOXES INSTALLED IN A FIRE-RESISTIVE SEPARATION SHALL BE AN "APPROVED WHITE, GREY, BEIGE OR IVORY) AS SELECTED BY THE ARCHITECT: J <br /> LOCATIONS OF ALL HVAC UNITS, DISCONNECTS AND DEVICES IN FIELD. COORDINATE ROOF PENETRATIONS (2) EMT CONNECTOR -APPLETON TW-CSI SERIES BOX". AN "APPROVED BOX" IS AN ALL STEEL ELECTRICAL BOX WHICH IS UL LISTED FOR INSTALLATION IN A A. WIRING DEVICES LEVITON# HUBBELL# P & S# <br /> FOR DISCONNECTS AND WEATHERPROOF OUTLETS WITH ELECTRICAL CONNECTION POINTS ON THE UNITS (3) FLEX CONDUIT CONNECTOR -T&B "TITE BITE", INSULATED FIRE-RESISTIVE SEPARATION. SINGLE POLE SWITCH, 15A 1201-2 HBL1201 PS15AC1 <br /> TO KEEP FLEXIBLE CONDUIT LENGTH TO A MINIMUM (36" MAXIMUM). VERIFY AND CONFIRM THE ACTUAL (4) LIQUID TIGHT FLEX CONDUIT CONNECTOR -APPLETON "STB" SERIES UP TO 2", "ST" SERIES OVER 2". DOUBLE POLE SWITCH, 15A 1202-2 HBL1202 PS15AC2 <br /> MOUNTING LOCATION ON THE HVAC UNIT FOR THE DISCONNECT. ALL SERVICING OUTLETS ON THE ROOF 5. ELECTRICAL BOXES, INCLUDING BOXES FOR RECEPTACLES, IN RATED WALLS SHALL HAVE A THREE WAY SWITCH, 15A 1203-2 HBL1203 PS15AC3 <br /> OR OUTDOORS FOR HVAC UNITS SHALL BE WP/GFI. I. RIGID STEEL CONDUIT CONNECTED TO BOXES AND CABINETS SHALL BE FITTED WITH TWO MINIMUM OF 24" HORIZONTAL SEPARATION FROM THOSE IN ADJACENT ROOMS AT THE OTHER SIDE OF DUPLEX CONV. OUTLET, 15A 5262 HBL5262 5262 W <br /> LOCKNUTS AND INSULATING BUSHING, OA"A" SERIES. PROVIDE GROUNDING BUSHING OZ"BL" SERIES WALL IN ACCORDANCE WITH C.B.C. SECTION 714.3.2. IN CASE SUCH HORIZONTAL SEPARATION IS NOT DUPLEX CONV. OUTLET, 20A 5362 HBL5362 5362 ~ <br /> It <br /> w <br /> 2. THE RATING OF THE DISCONNECT SHALL BE SUCH AS TO ENABLE THE LARGEST FUSE SIZE ON THE WHERE LOCKNUTS AND BUSHING IS NOT USED. CONDUITS CONNECTED TO BOXES EXPOSED TO POSSIBLE EACH BOX SHALL BE PROTECTED BY A LISTED FIRE-STOPPING PUTTY PAD AND BOX SHALL BE DUPLEX CONV. GFI OUTLET, 15A 6599 GF15 1595L w <br /> UNIT NAMEPLATE TO BE INSTALLED IN THE DISCONNECT. PROVIDE FUSES OF THIS RATING. WEATHER/MOISTURE SHALL BE FITTED WITH WATERTIGHT SEALING HUBS OF STEEL OR MALLEABLE PROVIDED WITH A METAL COVERPLATE AND NOT PLASTIC OR NYLON. DUPLEX CONV. GFI OUTLET, 20A 6899 GF15 2095L <br /> IRON WITH SEALING RING AND INSULATED THREAT, T& B 370 SERIES. Q W J C) <br /> 3. FURNISH AND INSTALL ALL LINE VOLTAGE CONDUITS AND LINE VOLTAGE WIRING (LOW VOLTAGE 6. WHERE CONDUIT SLEEVE IS USED FOR THE PROTECTION OF WIRING PENETRATIONS, UL LISTED 2. THE CONTROLLED OUTLET SHALL HAVE PERMANENT UNIQUE MARKING PROVIDED BY THE N O <br /> CONDUITS AND WIRING BY MECHANICAL) TO HVAC EQUIPMENT AND ASSOCIATED CONTROLS AND DEVICES J. TYPE NM AND NMC CABLES SHALL NOT BE USED ON THIS PROJECT. FIRESTOP COMPOUND SHALL BE USED TO SEAL THE OPENING AROUND THE CONDUIT AND TO SEAL THE MANUFACTURER OF THE RECEPTACLE. _ <br /> AS SHOWN ON THE ELECTRICAL AND MECHANICAL PLANS, UNLESS OTHERWISE NOTED. CONDUIT ENDS AFTER THE CABLE IS INSTALLED. Q z U <br /> K. THE PROJECT DRAWINGS ARE LAID OUT USING SOLID CONDUITS AND CABLES PULLED THROUGH 3. THE MOUNTING HEIGHTS OF LIGHT SWITCHES, RECEPTACLES AND CONTROLS SHALL BE MAXIMUM J <br /> 4. RUN ALL CONDUITS FOR ROOFTOP EQUIPMENT WITHIN CEILING SPACE BELOW. SURFACE CONDUIT SUCH CONDUITS. MC CABLES MAY BE UTILIZED AS DESCRIBED BELOW, WITH RESTRICTIONS NOTED. 7. WHERE A CABLE OR A GROUP OF CABLES PENETRATES MEMBRANE OR CONTINUOUS BLOCKING, 48" MEASURED TO THE TOP OF BOXES OR MINIMUM 16"TO THE BOTTOM OF BOXES. SEE "LEGEND" FORW <br /> RUNS ON THE ROOF ARE NOT PERMITTED ON THIS PROJECT. UL LISTED FIRESTOP COMPOUND SHALL BE USED TO SEAL THE OPENING AROUND THE CABLES. ACTUAL MOUNTING HEIGHTS OF DEVICES. VERIFY HEIGHT WITH ARCHITECT WHERE AN ACTUAL ( , 0 <br /> (1) PRIOR APPROVAL OF OWNER/ARCHITECT OR ENGINEER REQUIRED. MOUNTING HEIGHT IS NOT CALLED OUT ON PLANS. /1 v O <br /> U) <br /> 5. DISCONNECTS SHALL NOT BE USED AS THROUGH RACEWAYS FOR WIRING NOT DIRECTLY SERVING 8. SEE ARCHITECTURAL PLANS FOR LOCATION OF FIRE-RATED WALLS AND CEILING. r- <br /> THE DISCONNECTS. SERVICING OUTLETS SHALL NOT BE MOUNTED ON DISCONNECTS. (2) MC CABLES SHALL BE AS MANUFACTURED BY SOUTHWIRE TYPE EZ-MC DURACLAD TYPE WITH LIGHT 4. SINGLE RECEPTACLE SERVED BY INDIVIDUAL 20A BRANCH CIRCUIT DEDICATED TO THE OUTLET `\J <br /> WEIGHT STEEL ARMOR AND INSULATED GREEN GROUNDING CONDUCTORS OR APPROVED EQUAL. 260553. NAMEPLATES & IDENTIFICATION: SHALL BE 20A RATED PER CEC 210.21(13)(1). ALL OTHERS SHALL BE 15A RATED. ^ <br /> 260500.02. SUBMITALLS: 0- <br /> (3) SHALL BE USED FOR BRANCH CIRCUITS ONLY AS NOTED BELOW. 1. INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, ETC. 5. ALL 15A AND 20A, 120V OUTLETS IN KITCHEN SHALL BE GFCI PER CEC 210.8(B)(2). LOCATE SUCH <br /> 1. PROVIDE THE FOLOWING SUBMITTALS FOR REVIEW AND APPROVAL. EACH SHALL BE SUBMITTED NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH#4 PHILLIPS ROUND HEAD OUTLETS SO THAT THEY ARE ACCESSIBLE AFTER APPLIANCES THAT ARE PLUGGED INTO THE OUTLETS <br /> SEPARATELY TO AVOID DELAYS IN THE REVIEW OF ONE SUBMITTAL IN HOLDING UP REVIEW OF THE (a) CANNOT BE USED ANYWHERE EXPOSED. CADMIUM PLATED SELF-TAPPING SCREWS, BRASS BOLT. ARE IN PLACE. <br /> REMAINDER. <br /> (b) LIGHTING: VERTICAL DROPS IN WALL FOR LIGHT SWITCHES FORM JBOX IN CEILING. HORIZONTAL 2. PROVIDE CIRCUIT LABEL INDICATING PANEL AND CIRCUIT NUMBER ON EACH COVERPLATE FOR 6. ALL RECEPTACLES INSTALLED OUTDOORS SHALL BE WEATHERPROOF AND HAVE GROUND FAULT <br /> a. SERVICE SWITCHBOARD RUNS IN CEILING SHALL BE IN SOLID STEEL CONDUITS. EACH RECEPTACLE AND LIGHT SWITCH, MOTION SENSOR SWITCH. SUCH LABEL SHALL BE SELF ADHESIVE CIRCUIT INTERRUPTER PROTECTION. <br /> d. LIGHTING CONTROL PANEL. WHITE TAPE WITH BLACK LETTERS MADE ON A LABEL MAKER. <br /> e. LIGHTING CONTROLS (c) POWER RECEPTACLES: 7. 120V, 15A AND 20A RECEPTACLES ARE NOW SUBJECT TO CALIFORNIA ENERGY CODE, SECTION <br /> b. PANELBOARDS 3. ALL CONTROLLED RECEPTACLES SHALL BE PERMANENTLY MARKED TO DIFFERENTIATE THEM 130.5(d). ALL SUCH OUTLETS SHALL BE CONSIDERED AS UNCONTROLLED EXCEPT THOSE WHICH ARE <br /> f. BASIC ELECTRICAL MATERIALS (1) FOR UNDERGROUND HOMERUNS: SOLID CONDUIT VERTICAL RISER IN WALL FROM UNDERGROUND FROM UNCONTROLLED RECEPTACLES PER CALIFORNIA ENERGY CODE SECTION 130.5(d)(3). SPECIFICALLY CALLED OUT ON THE PLANS AS CONTROLLED. SEE "CONTROLLED 120V RECEPTACLES" <br /> C. LIGHT FIXTURES CONDUIT TO FIRST RECEPTACLE JBOX. THEN HORIZONTAL RUNS WITHIN WALLS TO OTHER PARAGRAPH BELOW. <br /> RECEPTACLE BOXES IN MC CABLE. 260573. ARC FLASH HAZARDS: <br /> 260500.03. WORKING CLEARANCES FOR ELECTRICAL SWITCHGEAR: (2) FOR OVERHEAD HOMERUNS: VERTICAL DROPS FROM JBOX IN CEILING THEN HORIZONTAL RUNS 262726.01. CONTROLLED 120V RECEPTACLES: <br /> WITHIN WALLS TO OTHER RECEPTACLES. HORIZONTAL RUNS IN CEILING SHALL BE IN SOLID STEEL 1. PROVIDE WARNING LABEL ON ELECTRICAL EQUIPMENT OF POSSIBLE ARC FLASH HAZARDS PER <br /> 1. PROVIDE WORKING SPACES FOR ELECTRICAL PANELS AND SWITCHGEAR TO COMPLY WITH CEC CONDUITS. C.E.C. 110.16. 1. CALIFORNIA ENERGY CODE, SECTION 130.5(d) NOW REQUIRES THAT BOTH CONTROLLED AND <br /> 110.26. 260943. INTERIOR LIGHTING CONTROL SYSTEM: UNCONTROLLED 120V OUTLETS FOR PLUG LOADS BE PROVIDED IN THE FOLLOWING LOCATIONS: <br /> (d) NO OTHER USE IS PERMITTED WITHOUT SPECIFIC WRITTEN APPROVAL OF THE ARCHITECT OR <br /> 2. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL TRADES INVOLVED TO ENSURE THE ENGINEER. 1. PROVIDE A COMPLETE AND FULLY OPERATIONAL INTERIOR LIGHTING CONTROL SYSTEM FOR A. EACH PRIVATE OFFICE. <br /> CLEARANCES REQUIRED BY ITEM 1 ABOVE ARE PROVIDED. INTERIOR LIGHTING AS SPECIFIED HEREIN AND SHOWN ON THE DRAWINGS. B. EACH OPEN OFFICE AREA. <br /> (4) ALL FITTINGS AND TERMINATIONS FOR THE MC CABLING SYSTEM SHALL BE METAL AND SUITABLE C. RECEPTION LOBBY. <br /> 260526. GROUNDING: AND LISTED FOR SUCH USE. 2. THE COMPLETE SYSTEM, INCLUDING ALL DEVICES SHALL BE IN COMPLIANCE WITH THE 2016 D. CONFERENCE ROOM. <br /> CALIFORNIA ENERGY CODE. E. KITCHENETTE AND BREAK ROOM IN OFFICE SPACES. <br /> 1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND SPECIFICALLY (5) ALL SUPPORTS, ATTACHMENTS SPACING SHALL BE PER CEC 330.30. F. COPY ROOM. <br /> INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, METAL PIPING SYSTEMS, STRUCTURAL STEEL, 3. THE COMPLETE SYSTEM SHALL BE AS MANUFACTURED BY NLIGHT, WATTSTOPPER, OR cn <br /> ETC. (6) FOR MULTI-WIRE BRANCH CIRCUITS SUCH CABLES SHALL HAVE MULTIPLE NEUTRALS, ONE FOR GREENGATE CONSISTING OF: 2. CIRCUITS SERVING CONTROLLED RECEPTACLES SHALL BE AUTOMATICALLY BE SHUT-OFF IN w <br /> EACH CIRCUIT. ACCORDANCE WITH SECTION 130.1(c)1. 0 <br /> 2. PROVIDE GROUND WIRES IN ALL FEEDERS AND BRANCH CIRCUITS, SIZE PER CEC TABLE 250.122 A. LUMINAIRES WITH 0-10V DIMMING LED DRIVERS. z <br /> 6. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THHN/THWN UNLESS OTHERWISE NOTED 3. PROVIDE A SPLITWIRED DUPLEX RECEPTACLE WITH ONE HALF CONTROLLED AND ONE HALF Q <br /> 3. ALL GROUND WIRES SHALL BE INSULATED GROUND WIRES. OR REQUIRED BY CODE. B. WALL DIMMER SWITCHES THAT COMMUNICATE THROUGH ROOM CONTROLLERS. UNCONTROLLED DUPLEX RECEPTACLE AS SHOWN ON THE PLANS. THIS RECEPTACLE SHALL BE SPLIT w <br /> DUPLEX OUTLET AS MANUFACTURED BY SAME MANUFACTURER AS THE OCCUPANCY LIGHTING SENSOR z <br /> w <br /> 260529. INSTALLATION OF SUPPORT SYSTEMS 7. ALL DEVICES, CONDUITS, RACEWAYS AND CABLES SHOWN ARE NEW TO BE PROVIDED UNLESS C OCCUPANCY SENSORS THAT COMMUNICATE THROUGH ROOM CONTROLLERS. SYSTEM WITH A 15-AMP RELAY-SWITCHED OUTLET AND A 15-AMP CONSTANT POWER OUTLET. c� <br /> OTHERWISE NOTED. <br /> 1. RACEWAYS, CABLE ASSEMBLIES, BOXES, CABINETS, AND FITTINGS SHALL BE SECURELY FASTENED D WHERE LIGHT FIXTURES FALL UNDER THE PRIMARY AND SECONDARY DAYLIT ZONES AS DEFINED 262726.02. DEVICE PLATES: <br /> IN PLACE PER CEC ARTICLE 300.11. SUPPORT WIRES THAT DO NOT PROVIDE SECURE SUPPORT SHALL NOT 8. FLASH AND COUNTERFLASH ALL ITEMS PASSING THROUGH THE ROOF. BY SECTION 130.1(d) AND THE TOTAL INSTALLED GENERAL LIGHTING POWER IN THE PRIMARY DAYLIT ZONE <br /> BE PERMITTED AS THE SOLE SUPPORT. SUPPORT WIRES AND ASSOCIATED FITTINGS THAT PROVIDE IS NOT LESS THAN 120W (EXCEPTION#1 TO SECTION 130.1(d)2) SUCH LIGHT FIXTURES SHALL BE PROVIDED 1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE NYLON. <br /> SECURE SUPPORT AND THAT ARE INSTALLED IN ADDITION TO THE CEILING GRID SUPPORT WIRES SHALL BE 9. THE OWNER RESERVES THE RIGHT TO RELOCATE ALL LIGHTING, OUTLETS AND SWITCHES WITH AUTOMATIC DAYLIGHITNG CONTROLS IN ACCORDANCE WITH SECTION 130.1(d)(2)(D). Q?OESS/ON <br /> PERMITTED AS THE SOLE SUPPORT. WHERE INDEPENDENT SUPPORT WIRE ARE USED, THEY SHALL BE BEFORE THEY ARE ROUGHED IN AT NO EXTRA COST. 2. ALL DEVICE BOXES WHICH ARE INSTALLED IN FIRE RATED WALL ASSEMBLY AND IS PROVIDED WITH R0 C. q� <br /> SECURED AT BOTH ENDS. CABLES AND RACEWAYS SHALL NOT BE SUPPORTED BY CEILING GRIDS. E. PROVIDE A DEMAND RESPONSIVE CONTROLS FOR THE INTERIOR LIGHTING SYSTEM PER CEC A FIRE-STOPPING PUTTY PAD SHALL HAVE A BRUSHED STAINLESS STEEL COVERPLATE IN ACCORDANCE SMi���� <br /> 10. SEPARATION OF WIRING OF DIFFERENT VOLTAGE CLASSIFICATIONS: SECTION 130.5(e). PROVIDE A GATEWAY DEVICE TO ACHIEVE THIS. SET UP DEVICE SUCH THAT WHEN IT WITH THE REQUIREMENTS OF THE PUTTY PAD. s Z <br /> 2. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL ELECTRICAL RECEIVES AN OPEN AUTOMATIC DEMAND RESPONSE (ADR) 2.0 SIGNAL IT TRANSMITS THE ADR SIGNAL TO U Exp.. 6 1300 21 rn <br /> ENCLOSURES, CONDUITS AND EQUIPMENT. A. WIRING FOR DIFFERENT VOLTAGE CLASSIFICATIONS SHALL BE INSTALLED IN ENTIRELY EACH OTHER AND TO THE ROOM LIGHTING CONTROLLERS. THE ROOM CONTROLLERS SHALL DIM THE 3. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL PLATES. <br /> SEPARATE RACEWAYS/CONDUITS SYSTEM AND ENCLOSURES/BOXES. LIGHT FIXTURES TO REDUCE ENERGY CONSUMPTION BY AT LEAST 15%, BUT NOT MORE THAN 50%WHEN F <br /> 3. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, TO METAL WITH THE SIGNAL IS RECEIVED. 4. DEVICE COVERS FOR DEVICES LOCATED IN DAMP LOCATIONS SHALL COMPLY WITH CEC 406.9(A). ��yT< 'CTR�cP���P <br /> MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION ANCHORS AND MACHINE SCREWS OR CLASSIFICATION 1 0 TO 30V FOF CAO- o <br /> BOLTS. CLASSIFICATION 2 100 TO 250V F. TIME BASED GATEWAY DEVICE THAT PROVIDES TIME-BASED SIGNAL TO ROOM CONTROLLERS FOR 5. DEVICE COVERS FOR DEVICES LOCATED IN WET LOCATIONS SHALL COMPLY WITH CEC 406.9(B). <br /> CLASSIFICATION 3 251 TO 500V ALL SPACES THAT CONTROLLED BY MOTION SENSORS TO AUTOMATICALLY SHUT-OFF LIGHTS AT THE END <br /> 2. RIGID STEEL CONDUIT SHALL BE SUPPORTED AT INTERVALS NOT GREATER THAN 10 FT, ELECTRICAL OF DAY <br /> METALLIC TUBING AT INTERVALS NOT GREATER THAN 5 FT. B. PARTICULAR ATTENTION SHALL BE PAID TO THE WIRING FOR Drawn: RCS <br /> 4. ALL SYSTEM COMPONENTS SHALL BE UL LISTED. ALL SYSTEM CONTROL COMPONENTS SHALL BE <br /> 3. A SUPPORT SHALL BE PROVIDED NOT MORE THAN 3 FT. FROM ANY CHANGE IN DIRECTION. 1. ROOF TOP CONVENIENCE OUTLETS FOR SERVICING ROOF TOP EQUIPMENT. APPROVED BY THE CALIFORNIA ENERGY COMMISSION. Date: 8.6.18 <br /> ADDITIONAL SUPPORTS TO THOSE SPECIFIED ABOVE SHALL BE INSTALLED WHERE REQUIRED TO SUIT JOB Plan Check 10.23.18 <br /> CONDITIONS AND TO PROVIDE A SECURE INSTALLATION. ALL HANGERS AND SUPPORTS SHALL BE THE 2. LINE VOLTAGE CONTROLS FOR ROOF TOP HVAC AND OTHER REQUIREMENTS. 5. ALL EQUIPMENT AND ITEMS OF CONTROL SHALL BE INSTALLED AND WIRED IN ACCORDANCE WITH Revised: Plan Check 1.29.19 <br /> PRODUCTS OF ONE MANUFACTURER. MANUFACTURER'S REQUIREMENTS. <br /> C. DISCONNECTS SHALL NOT BE USED AS THROUGH RACEWAYS FOR WIRING NOT DIRECTLY <br /> 260533. PULL OR JUNCTION BOXES: SERVING THE DISCONNECTS. SERVICING OUTLETS SHALL NOT BE MOUNTED ON DISCONNECTS. 6. PROVIDE WALL OCCUPANCY SENSOR LIGHT SWITCHES WHERE SO SHOWN ON PLANS. SUCH <br /> OCCUPANCY SENSOR SWITCHES SHALL BE SINGLE LEVEL AUTOMATIC "ON"/AUTOMATIC "OFF"AS SHOWN <br /> 1. INSTALL WHERE INDICATED, OR AS REQUIRED BY CODE, PULL BOXES AND JUNCTION BOXES OF 260551. INSTALLATION OF RACEWAYS AND FITTINGS ON PLANS. SENSORS SHALL COMPLY WITH SECTION 110.9 OF THE ENERGY CODE. H C S ENGINEERING, INC. <br /> SUFFICIENT SIZE AND CAPACITY TO FACILITATE ALL WIRING. BOXES SHALL BE SIZED TO PROPERLY <br /> ACCOMMODATE ALL CONDUCTORS ENTERING SAME. 1. CONCEAL RACEWAYS WITHIN CEILINGS, WALLS, AND FLOORS EXCEPT WHERE EXPOSED CONSULTING ELECTRICAL ENGINEERS <br /> RACEWAYS ARE SPECIFICALLY PERMITTED. 4512 FEATHER RIVER DRIVE, SUITE F <br /> 2. BOXES SHALL BE OF THE SHAPE AND SIZE BEST SUITED FOR THE PARTICULAR APPLICATION AND STOCKTON, CA 95219 (209) 478-8270 E001 <br /> SHALL BE SUPPORTED DIRECTLY TO STRUCTURAL MEMBERS, FRAMING OR BLOCKING BY MEANS OF email address richard@hcs-eng.com <br /> SCREWS, ANCHORS, BOLTS OR EMBEDDED IN MASONRY. Project#: 2017.xxx Drafter: RCS Engineer: RCS <br /> K:\2018\201-300\Papavalous\PAPAVALOS ELECTRICAL Plan Check Set.rvt <br />