Laserfiche WebLink
2. Where the pump is offset from the well or <br /> where a submersible pump is used, the opening between the <br /> well casing and any pipes or cables which enter the well <br /> shall be closed by a watertight seal or "well cap". <br /> 3. If the pump is not installed immediately or <br /> if there is a prolonged interruption in construction of the <br /> well, a watertight cover shall be installed at the top of the <br /> casing. <br /> SCREENED AND INVERTED AIR RELEASE <br /> VACUUM FROM SLAB.BREAKER VENT, 3FT.MINfNUM 4. A watertight seal or gasket shall be placed <br /> SCREENED AND INVERTED CASING � between the pump discharge head and the discharge line; or, <br /> YENT. 3IN.11. MINIMUM DIAMETER in the event of a below-ground discharge, between the <br /> NO THREADED HOSE BIBS discharge pipe and discharge line (see Figures 6 and 7). <br /> BETWEEN PUMP AND <br /> MOTOR CHECK VALVE, 5. If a concrete base Or slab (sometimes <br /> SITE FOR SAMPLING TAP called a pump block or pump pedestal) is constructed around <br /> OR CHLORINATION the top of the casing, it shall be free from cracks, honey- <br /> combs or other defects likely to detract from its watertight- <br /> ness. The joint between the base and the annular seal must <br /> PUMP HEAD also be watertight. The base shall slope away from the well <br /> ® casing. The minimum thickness of the concrete base shall be <br /> sauNDIMG TUBE 4 inches (100 millimetres).f <br /> AIRLINE _ / 6. Where the well is to be .gravel packed and <br /> SOURDING TUBE GRAVEL FILL PIPE the pack extends to the surface, a watertight cover shall be <br /> F. ALL VENT PIPES MUST installed between the conductor casing and the inner casing <br /> i ! W, BE OINT OF <br /> ENTRY OENYSEALER <br /> POINT (see also Section 9, Part B, Item 5 and Figure 5). <br /> :'.•;• ...•.• <br /> II . INTO WELL. <br /> B. Well Pits. Because of their susceptability. to <br /> f ;i MPERVlOUS SURFACE sUR- contamination and pollution, the use of well pits should be <br /> , - ROUNDING WELL SLOPED I avoided whenever possible. A substitute device called a <br /> U AWAY FROM WELL• <br /> C� pitless adapter?/ or pitless adapter unit (a variation) may <br /> be used in place of a well pit. <br /> n <br /> C. Enclosure of Well and Appurtenances. In <br /> STEEL REBAR community water..supply wells, the well and pumps all be <br /> located in a locked enclosure to exclude access by <br /> PUMP PEDESTAL OF MO%OLITHIC4 unauthorized persons. <br /> ALLY POURED CONCRETE IS IN. <br /> ABOVE FINISHED GRADE. - <br /> 1 This value is for small (under 10 inches or 250 millimetres <br /> -GRAVEL PACK in diameter) individual domestic well installations. The <br /> GROUT SEAL, shape and dimensions of pump bases varies with the size, <br /> 2IN.MINIMUM THICKNESS weight and type of pumping equipment to be installed and <br /> SOFT.MINIMUM DEPTH. � <br /> the bearing capacity of the soil on which it is situated. <br /> A variety of designs have been used. For large diameter <br /> RCONDUCTOR CASING turbine pump installations the Vertical Turbine Pump <br /> LINE SHAFT <br /> rINNER CASING Association has developed a standard design for a square, <br /> PUMP COLUMN concrete pump base that is based on weight, including full <br /> pump column and soil bearing capacity. (See Bibliography, <br /> Appendix E.) <br /> Pitless adaptors and uni.ts.were developed for use in areas <br /> where prolonged freezing occurs and below ground (below <br /> frost line) discharges are common. Both the National <br /> Sanitation Foundation and Water Systems Council have <br /> Figure 7. SURFACE CONSTRUCTION FEATURES developed standards for their manufacture and installation. <br /> 1 COMMUNITY WATER SUPPLY WELL l (See Bibliography, Appendix E.) <br />