A1.5 EGRESS & ACCESSIBILITY PLAN12" MIN CLR ON
<br />PUSH SIDE
<br />60" X 54"
<br />72" X 60"
<br />48" X 48"
<br />18" MIN CLR ON
<br />PULL SIDE
<br />DOOR WIDTH
<br />X 48"
<br />48" X 30"
<br />USE: RETAIL SALES
<br />AREA: 2,287 SF
<br />LOAD FACTOR: 60 SF/OCC
<br />OCCUPANTS:39
<br />EXITS:1 REQUIRED
<br />39 OCC + 3 OCC = 42 OCC
<br />1 EXIT REQUIRED
<br />2 EXITS PROVIDED
<br />MERCHANDISE
<br />101
<br />SALES
<br />102
<br />COOLER/VAULT
<br />109
<br />FREEZER
<br />108
<br />106
<br />ALL GENDER
<br />RESTROOM #2
<br />105
<br />BACKROOM
<br />104
<br />OFFICE
<br />103
<br />ELECTRICAL
<br />107
<br />USE: BUSINESS
<br />AREA: 51 SF
<br />LOAD FACTOR: 100 SF/OCC
<br />OCCUPANTS: 1
<br />EXITS: 1 REQUIRED
<br />TURNING RADIUS60" Ø
<br />TOILET STALL60" X 59"
<br />24" MIN CLR ON
<br />PULL SIDE
<br />DUAL DIRECTION
<br />SWINGING DOOR
<br />USE: UTILITY/STORAGE
<br />AREA: 310 SF
<br />LOAD FACTOR: 300 SF/OCC
<br />OCCUPANTS: 2
<br />EXITS: 1 REQUIRED
<br />2 OCC + 1 OCC = 3 OCC BCE #:Scale:Date:Drawn By:Checked By:Rev. #DateDescriptionSHEET:7-ELEVEN #411871829 N. WILSON WAY, STOCKTON, CA20744.SKAS NOTED03-25-20GUGGENHEIM PARTNERS, LLC3000 INTERNET BLVD., SUITE 570, FRISCO, TEXAS 75034PROTO 10-23-2019
<br />7043 SIP - RIGHT
<br />24" MIN CLEAR ON
<br />PULL SIDE60" X 60"
<br />ALL GENDER
<br />RESTROOM #1
<br />SINGLE DOOR EXIT
<br />WIDTH 34" CLEAR
<br />1 EGRESS PLAN
<br />1/4" = 1'-0"FEM - CHIPS5'-8"CIG'SCIG'SITPOTPNâ‚‚
<br />Nâ‚‚2' CANDY RACK4' CANDY RACK4' CANDY RACK4'-11"
<br />3'-0"
<br />FLOOR
<br />SPINNER:
<br />SUNGLASSES
<br />GLOVES
<br />UMBRELLAS
<br />4'-2"42'-0"BUN DRAWERWASTE
<br />7'-2"
<br />7'-6"
<br />7'-6"4'-1"3'-10"3'-10"4'-4"5'-3"4'-8"4'-1"5'-1"SS A
<br />5'-2"
<br />5'-0"
<br />6'-0"
<br />5'-5"
<br />3'-4"3'-10"3'-0"3'-0
<br />"5'-1"3'-11"
<br />4'
<br />-
<br />1
<br />0
<br />"5'-4"70'-0"43'-4"SEXIT
<br />21
<br />61'-4" MAX. TRAVEL DISTANCEEXIT
<br />DOUBLE DOOR EXIT
<br />WIDTH 68" CLEAR
<br />2154" HIGH
<br />54" HIGH
<br />54" HIGH
<br />36" HIGH
<br />ND
<br />I
<br />A
<br />G
<br />O
<br />N
<br />A
<br />L
<br />
<br />D
<br />I
<br />S
<br />T
<br />A
<br />N
<br />C
<br />E
<br />68'-9" MAX.TRAVEL DISTANCE60'-2" MAX. TRAVEL DISTANCE
<br />76'-3" MAX. TRAVEL DISTANCE13
<br />BUILDING CODE INFORMATION
<br />BUILDING CODE:2019 CALIFORNIA BUILDING STANDARDS CODE
<br />OCCUPANCY CLASSIFICATION:MERCANTILE GROUP - M
<br />CONSTRUCTION TYPE:TYPE VB
<br />SPRINKLER:NOT SPRINKLERED
<br />OCCUPANCY LEGEND
<br />BUILDING CODE:TOTAL SQFT
<br />N/A
<br />328
<br />42
<br />NON OCCUPIED SPACE PER SEC. 202
<br />DEFINITION OF OCCUPIABLE SPACE
<br />MERCANTILE
<br />(STORAGE, STOCK, SHIPPING AREAS)
<br />BUSINESS
<br />OCCUPANCY SIGNAGE NOTES:
<br />SIGNS STATING THE MAXIMUM OCCUPANT CONTENT SHALL BE CONSPICUOUSLY
<br />POSTED IN EACH AREA OF ASSEMBLY, ASSEMBLY ROOM, OR ROOM USED FOR
<br />SIMILAR PURPOSE.
<br />OCCUPANT LOAD ANALYSIS:
<br />FUNCTION OCCUPANT AREA OCCUPANT
<br />OF SPACE LOAD FACTOR LOAD
<br />MERCANTILE/60 2,287 SF 39
<br />CASHIER
<br />UTILITY/300 328 SF 2
<br />STORAGE
<br />OFFICE 100 51 SF 1
<br />TOTAL 42
<br />1,906MERCANTILE/CASHIER
<br />N/A
<br />UTILITY - NON OCCUPIED SPACE PER
<br />SEC. 202 DEFINITION OF OCCUPIABLE
<br />SPACE
<br />EMERGENCY EXIT LIGHTING, SEE ALSO ELECTRICAL
<br />DRAWINGS
<br />EXIT SIGN
<br />CODE PLAN KEYED NOTES
<br />CUMULATIVE NUMBER OF OCCUPANTS EXITING AN
<br />AREA OR BUILDING
<br />NUMBER OF OCCUPANTS EXITING AND DIRECTION
<br />MANEUVERING CLEARANCE AT DOORS OR CLEAR
<br />FLOOR SPACE. SEE KEY BELOW
<br />XX
<br />CODE PLAN LEGEND
<br />XX
<br />CBC SECTION 504.1, BUILDING HEIGHT AND NUMBER OF STORIES
<br />ALLOWABLE BUILDING HEIGHT AND NUMBER OF STORIES SHALL BE DETERMINED
<br />BASED ON THE TYPE OF CONSTRUCTION, OCCUPANCY CLASSIFICATION AND
<br />AUTOMATIC SPRINKLERS.
<br />*ASSUME OCCUPANCY GROUP "M" WITH TYPE VB CONSTRUCTION AND
<br />NON-SPRINKLERED
<br />CBC TABLE 504.3, ALLOWABLE BUILDING HEIGHT
<br />MAXIMUM ALLOWABLE HEIGHT: 40 FEET
<br />CBC TABLE 504.4, ALLOWABLE STORIES
<br />MAXIMUM NUMBER OF STORIES: 1 STORY
<br />CBC SECTION 506.1, BUILDING AREA
<br />ALLOWABLE BUILDING AREA SHALL BE DETERMINED BASED ON THE TYPE OF
<br />CONSTRUCTION, OCCUPANCY CLASSIFICATION, AUTOMATIC SPRINKLERS AND THE
<br />AMOUNT OF BUILDING FRONTAGE ON A PUBLIC WAY.
<br />CBC TABLE 506.2, ALLOWABLE BUILDING AREA
<br />MAXIMUM ALLOWABLE AREA: 9,000 SQUARE FEET
<br />* PROPOSED BUILDING AREA: 3,033 SQUARE FEET
<br />ALLOWABLE AREA IS OK
<br />CBC SECTION 602.5, TYPE V
<br />TYPE V CONSTRUCTION IS THAT TYPE OF CONSTRUCTION IN WHICH THE
<br />STRUCTURAL ELEMENTS, EXTERIOR WALLS AND INTERIOR WALLS ARE OF ANY
<br />MATERIALS PERMITTED BY THIS CODE.
<br />TABLE 601, FIRE RESISTANCE RATING FOR BUILDING ELEMENTS
<br />FOR TYPE V-B CONSTRUCTION IN HOURS
<br />PRIMARY STRUCTURAL FRAME: 0
<br />EXTERIOR BEARING WALLS: 0
<br />INTERIOR BEARING WALLS: 0
<br />EXTERIOR NON-BEARING WALLS: SEE TABLE 602
<br />INTERIOR NON-BEARING WALLS: 0
<br />FLOOR CONSTRUCTION: 0
<br />ROOF CONSTRUCTION: 0
<br />TABLE 602, FIRE RESISTANCE FOR EXTERIOR WALLS BASED ON FIRE SEPARATION
<br />DISTANCE
<br />DISTANCE CONST. TYPE OCC. GROUP RATING
<br />10</=X<30 VB M 0
<br />X>/=30 VB M 0
<br />*ALL EXTERIOR WALLS HAVE A SEPARATION DISTANCE GREATER THAN 10 FEET.
<br />THEREFORE, NO RATING IS REQUIRED.
<br />CBC TABLE 1004.1.2, FLOOR AREAS PER OCCUPANT
<br />SEE PLAN BELOW FOR OCCUPANT LOAD CALCULATIONS.
<br />CBC SECTION 1006.2.1, EGRESS BASED ON OCCUPANT LOAD
<br />TWO EXITS OR EXIT ACCESS DOORWAYS SHALL BE PROVIDED WHERE THE DESIGN
<br />OCCUPANT LOAD OR COMMON PATH OF EGRESS TRAVEL EXCEEDS THE VALUES IN
<br />TABLE 1006.2.1.
<br />CBC TABLE 1006.2.1, SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY
<br />A SPACE IN AN "M" OCCUPANCY WITH AN OCCUPANT LOAD OF 49 OR LESS AND A
<br />MAXIMUM PATH OF EGRESS TRAVEL OF 75 FEET IS ALLOWED TO HAVE ONLY ONE
<br />EXIT.
<br />CBC SECTION 1008.2.1, ILLUMINATION LEVEL UNDER NORMAL POWER
<br />THE MEANS OF ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FOOTCANDLE AT
<br />THE WALKING SURFACE.
<br />CBC SECTION 1008.3.1, EMERGENCY POWER FOR ILLUMINATION
<br />IN THE EVENT OF POWER FAILURE, AN EMERGENCY ELECTRICAL SYSTEM SHALL
<br />ILLUMINATE THE FOLLOWING AREAS:
<br />AISLES, CORRIDORS, EXIT ACCESS STAIRWAYS AND RAMPS.
<br />CBC SECTION 1009.1, ACCESSIBLE MEANS OF EGRESS
<br />ACCESSIBLE SPACES SHALL BE PROVIDED WITH NOT LESS THAN ONE ACCESSIBLE
<br />MEANS OF EGRESS. WHERE MORE THAN ONE MEANS OF EGRESS ARE REQUIRED,
<br />EACH ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY AT LEAST THE
<br />SAME NUMBER AS REQUIRED BY SECTIONS 1006.2 OR 1006.3. IN ADDITION, MEANS
<br />OF EGRESS SHALL ALSO COMPLY WITH THE REQUIREMENTS OF CHAPTER 11B.
<br />CBC SECTION 1010.1.1, SIZE OF DOORS
<br />THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE
<br />OCCUPANT LOAD AND SHALL PROVIDE A MINIMUM CLEAR WIDTH OF 32 INCHES.
<br />CBC SECTION 1010.1.2.1, DIRECTION OF SWING
<br />DOORS SHALL SWING IN THE DIRECTION OF TRAVEL WHERE SERVING A ROOM OR
<br />AREA CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS.
<br />CBC SECTION 1010.1.9, DOOR OPERATIONS
<br />EGRESS DOORS SHALL BE READILY OPENABLE FROM THE EGRESS SIDE WITHOUT
<br />THE USE OF A KEY OR SPECIAL KNOWLEDGE OR EFFORT.
<br />CBC SECTION 1013.1, EXIT SIGNS, WHERE REQUIRED
<br />EXITS AND EXIT ACCESS DOORS SHALL BE MARKED BY AN APPROVED EXIT SIGN
<br />READILY VISIBLE FROM ANY DIRECTION OF TRAVEL.
<br />EXCEPTION 1: EXIT SIGNS ARE NOT REQUIRED IN ROOMS OR AREAS THAT
<br />REQUIRE ONLY ONE EXIT OR EXIT ACCESS.
<br />CBC TABLE 1017.2, EXIT ACCESS TRAVEL DISTANCE
<br />OCCUPANCY WITHOUT SPRINKLER
<br /> M 200 FEET
<br />CBC SECTION 11B-206.2.1 SITE ARRIVAL ROUTE
<br />AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN THE SITE FROM
<br />ACCESSIBLE PARKING SPACES AND ACCESSIBLE PASSENGER DROP OFF AND
<br />LOADING ZONES; PUBLIC STREETS AND SIDEWALKS; AND PUBLIC TRANSPORTATION
<br />STOPS TO THE ACCESSIBLE BUILDING OR FACILITY ENTRANCE THEY SERVE.
<br />EXCEPTION: AN ACCESSIBLE ROUTE SHALL NOT BE REQUIRED BETWEEN SITE
<br />ARRIVAL POINTS AND THE BUILDINGS OR FACILITY ENTRANCE IF THE ONLY
<br />MEANS OF ACCESS BETWEEN THEM IS A VEHICULAR WAY NOT PROVIDING
<br />PEDESTRIAN ACCESS.
<br />CBC SECTION 11B-206.2.2, WITHIN A SITE
<br />AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE BUILDINGS,
<br />FACILITIES, ACCESSIBLE ELEMENTS AND ACCESSIBLE SPACES THAT ARE ON THE
<br />SAME SITE.
<br />EXCEPTION: AN ACCESSIBLE ROUTE SHALL NOT REQUIRED BETWEEN
<br />ACCESSIBLE BUILDINGS, ACCESSIBLE FACILITIES, ACCESSIBLE
<br />ELEMENTS AND ACCESSIBLE SPACES IF THE ONLY MEANS OF ACCESS BETWEEN
<br />THEM IS A VEHICULAR WAY NOT PROVIDING PEDESTRIAN ACCESS.
<br />CPC TABLE 422.1, MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
<br />OCCUPANT LOAD FACTOR PER CPC TABLE A, OCCUPANT LOAD FACTOR:
<br />C-STORE = 3,033 SQ FT
<br /> TOTAL = 3,033 SQ FT
<br />TOTAL OCCUPANT LOAD = 42 OCCUPANTS
<br />OCCUPANCY WATER CLOSETS LAVATORIES DRINKING SERVICE
<br /> FOUNTAINS SINK
<br /> MALE FEMALE MALE FEMALE
<br /> M 1:1-100 1:1-100 1:1-200 1:1-200 1:1-250 1
<br />OCCUPANTS:
<br />42 OCCUPANTS = 21 MALE AND 21 FEMALE
<br />TOTAL REQUIRED PLUMBING FIXTURES:
<br />MALE = 1 WATER CLOSET AND 1 LAV
<br />FEMALE = 1 WATER CLOSET AND 1 LAV
<br />DRINKING FOUNTAIN = 1
<br />SERVICE SINK = 1
<br />PLUMBING FIXTURES PROVIDED:
<br />MALE = 1 WATER CLOSET, 1 URINAL, AND 1 LAV
<br />FEMALE = 2 WATER CLOSET AND 1 LAV
<br />DRINKING FOUNTAIN = 1 (AT SODA MACHINE)
<br />SERVICE SINK = 1
<br />CFC 505.1, ADDRESS IDENTIFICATION
<br />NEW BUILDINGS SHALL BE PROVIDED WITH APPROVED ADDRESS IDENTIFICATION.
<br />THE ADDRESS IDENTIFICATION SHALL BE PLACED IN A POSITION VISIBLE FROM THE
<br />STREET FRONTING THE PROPERTY AND SHALL CONTRAST WITH THEIR
<br />BACKGROUND. EACH CHARACTER SHALL BE NOT LESS THAN 4" HIGH AND NOT
<br />LESS THAN 1/2" WIDE. SEE CFC 505 FOR ADDITIONAL.
<br />CFC 907.2 FIRE ALARM DETECTION SYSTEMS, WHERE REQUIRED
<br />AN APPROVED FIRE ALARM SYSTEM INSTALLED IN ACCORDANCE WITH THE
<br />PROVISIONS OF THIS CODE AND NFPA 72 SHALL BE PROVIDED IN NEW BUILDINGS
<br />AND STRUCTURES.
<br />CFC 907.5, OCCUPANT NOTIFICATION SYSTEM
<br />A FIRE ALARM SYSTEM SHALL ANNUNCIATE AT THE FIRE ALARM CONTROL UNIT AND
<br />SHALL INITIATE OCCUPANT NOTIFICATION UPON ACTIVATION.
<br />OCCUPIABLE SPACE - A ROOM OR ENCLOSED SPACE DESIGNED FOR HUMAN
<br />OCCUPANCY IN WHICH INDIVIDUALS CONGREGATE FOR AMUSEMENT,
<br />EDUCATIONAL OR SIMILAR PURPOSES OR IN WHICH OCCUPANTS ARE ENGAGED IN
<br />LABOR, AND WHICH IS EQUIPPED WITH MEANS OF EGRESS AND LIGHT AND
<br />VENTILATION FACILITIES MEETING THE REQUIREMENTS OF THIS CODE.
<br />BID SET 5/26/20
|