Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> CITY OF TRACY BOYD SERVICE CTR 520 S TRACY BLVD,TRACY December 10, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 721 CFR 112.8(d)(1)Failed to provide corrosion protection for buried piping. <br /> OBSERVATION: The SPCC Plan failed to discuss buried piping. <br /> REGULATION GUIDANCE: (d)(1)Provide buried piping that is installed or replaced on or after August 16, 2002, <br /> with protective wrapping and coating.You must also cathodically protect such buried piping installations or <br /> otherwise satisfy the corrosion protection standards for piping in part 280 of this chapter or a State program <br /> approved under part 281 of this chapter. If a section of the buried line is exposed for any reason, you must carefully <br /> inspect it for deterioration. If you find corrosion damage,you must undertake additional examination and corrective <br /> action, as indicated by the magnitude of the damage. <br /> CORRECTIVE ACTION: Ensure the SPCC Plan discusses buried piping. Provide proof of correction to the EHD. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 1/9/2022. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($152). To schedule an appointment, please call (209)468-3420. <br /> The following was observed during this inspection: <br /> - 10,000-gallon regular unleaded tank <br /> - 10,000-gallon diesel tank <br /> -400-gallon used oil <br /> - 120-gallon hydraulic lift <br /> -275-gallon new oil tank <br /> - Nine 55-gallon oil drums <br /> Reviewed: <br /> - monthly inspections <br /> - annual inspections <br /> - monthly training records <br /> -weekly training records <br /> The following was provided during this inspection: <br /> -Schedule of free CUPA classes <br /> Inspection report emailed to Frank Desousa <frank.desousa@cityoftracy.org> <br /> FA0009384 PR0528294 SCO01 12/10/2021 <br /> EHD 28-01 Rev.12/06/2021 Page 7 of 8 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />