Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by Lj Manufacturer 7 Industry Standard Professional Engineer <br /> Test Type Li Pressure Ll Vacuum v/ Hydrostatic <br /> Test Equipment Used:TS-STS <br /> Sump/UDC ID UDC 5/6 <br /> Sump Manufacturer Bravo <br /> Sump Depth (inches) 3611 <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 9,, <br /> (inches) <br /> Test Start Time 1:16PM <br /> Initial Reading 2.7837" <br /> Test End Time 1:3IPM <br /> Final Reading 2.7835" <br /> Change in Reading 0.0002 <br /> Pass/Fail Criteria +/- 0.002. <br /> Tightness Test Results ZPass FailIL]Pass[_JFail Pass FailPass Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> [Tightness Test Results !L]PassLFailL-1Pass[1FaF11LJPassLFaiI Pass Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />