Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 9. COMMENTS <br /> 87 &89& 91 & Diesel Secondary Piping Failed Due to Torn Test Boots. <br /> 87 &89& 91 STP Sumps Failed Needs Further Investigation. Diesel STP Sump Failed Due to Torn Test Boots. <br /> 87, 89, 91, Diesel Fill sumps failed possible conduit penetrations. <br /> UDC 1/2&3/4&5/6&7/8&9/10 & 11/12&13/14&15/16-Failed Due to Torn Test Boots. <br /> No Inspector Present. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 5 of 5 <br />