Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 8. IN-TANK GAUGING TESTING <br /> El Check this box if tank gauging is used only for inventory control. <br /> ❑ Check this box if NO tank gauging equipment is installed. Yes No NA <br /> Do not complete this section if either box is checked. <br /> All wiring has been: 1) visually inspected for kinks, breaks and proper entry and ❑ ❑ ❑ <br /> termination; and 2 tested for ground faults? <br /> Were all in-tank gauging probes visually inspected for damage and residue buildup ❑ ❑ ❑ <br /> to ensure that floats move freely, functionally tested, and confirmed operational? <br /> Was accuracy of system's product level readings tested? ❑ ❑ ❑ <br /> Was accuracy of system's water level readings tested? ❑ ❑ ❑ <br /> Were all probes reinstalled properly? ❑ ❑ ❑ <br /> Were all items on the equipment manufacturer's maintenance checklist completed? ❑ ❑ ❑ <br /> Probe ID Probe Model Tanks Monitored Pass Fail <br /> T-1 Mag 1 Waste Oil Near Rack 4K ❑ ❑ <br /> T-2 Mag 1 Waste Oil Near Gate 1 K ❑ ❑ <br /> T-3 Mag 1 Anti Freeze 6K ❑ ❑ <br /> T-4 Mag 1 Gear Oil 6K ❑ ❑ <br /> T-5 Mag 1 Motor Oil 1 OK ❑ ❑ <br /> T-6 Mag 1 Waste Oil 6K ❑ ❑ <br /> 9. COMMENTS <br /> Describe all answers marked "No"or "Fail"and proposed remedy. <br /> List all monitoring equipment either replaced or repaired. <br /> All sensors tested. <br /> No repairs needed. <br /> Probes tested for Overfill, High Product, Max product, High water Warning and Alarm on 2-16-22. <br /> Annunciator AIV in shop functions when in-tank alarms activated. <br /> Fax output functions,email to C.Roy functional. <br /> Page 5 of 6 <br />