Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer 0 Industry Standard ❑ Professional <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used : Incon TS STS, <br /> Sump/UDC ID Fill Sump Piping Vault Vent Box <br /> Sump Manufacturer Containment Bravo Bravo <br /> Sump Depth (inches) 74 30 30 <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) 31 13 11 <br /> Test Start Time 12:48 12:48 12:48 <br /> Initial Reading 4.0924 4.7018 5.8207 <br /> Test End Time 13:03 13:03 13:03 <br /> Final Reading 4.0939 4.7016 5.8207 <br /> Change in Reading 0.0015 0.0002 0 <br /> Pass/Fail Criteria 1 0.002 1 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail N Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked 'Fail' and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 6 <br />