Laserfiche WebLink
Underground Storage Tank <br />Secondary Containment Testing Report Form <br />All tests marked "Fail" and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 3 of 6 <br />Test Method Developed by Manufacturer Industry Standard Professional <br />Test Type Pressure Vacuum Hydrostatic <br />Test Equipment Used: Incon TS STS. <br />Sump/UDC ID Fill Sump Piping Vault Vent Box <br />Sump Manufacturer Containment <br />solutions Bravo Bravo <br />Sump Depth (inches)74 30 30 <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches)31 13 11 <br />Test Start Time 12:48 12:48 12:48 <br />Initial Reading 4.0924 4.7018 5.8207 <br />Test End Time 13:03 13:03 13:03 <br />Final Reading 4.0939 4.7016 5.8207 <br />Change in Reading 0.0015 0.0002 0 <br />Pass/Fail Criteria 0.002 0.002 0.002 <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Sump/UDC ID <br />Sump Manufacturer <br />Sump Depth (inches) <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />Test Start Time <br />Initial Reading <br />Test End Time <br />Final Reading <br />Change in Reading <br />Pass/Fail Criteria <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Additional copies of this page may be attached. <br />8. SUMP/UDC TEST