Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8 . SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used : Caldwell Level Change Indicator <br /> Sump/UDC ID 1 -87 - PS 2 =91 -PS <br /> Sump Manufacturer XERXES XERXES <br /> Sump Depth ( inches ) 39 38 " <br /> Sump Bottom to Top of 12 14 " <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time 9 : 47 8 : 52 <br /> Initial Reading . 001 . 001 <br /> Test End Time 10 : 17 9 : 22 <br /> Final Reading . 001 . 001 <br /> Change in Reading . 001 0 <br /> Pass/ Fail Criteria > . 002 > . 002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1 &2 UDC 3 &4 UDC 5&6 UDC 7 &8 <br /> Sump Manufacturer CSI CSI CSI CSI <br /> Sump Depth ( inches ) 26 " 26 " 261 /2 27 " <br /> Sump Bottom to Top of 7 " 8 " 71 /2 it 8 " <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time 8 : 57 9 : 02 9 : 52 9 : 57 <br /> Initial Reading . 001 . 001 . 001 . 001 <br /> Test End Time 9 : 27 9 : 32 10 : 22 10 : 27 <br /> Final Reading . 001 . 001 . 001 . 001 <br /> Change in Reading 0 0 0 0 <br /> Pass/ Fail Criteria > . 002 > . 002 > . 002 > . 002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail" and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section . <br /> Page 3of5 <br />