Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-87-PS 2-91-PS <br /> Sump Manufacturer XERXES XERXES <br /> Sump Depth (inches) 39" 38" <br /> Sump Bottom to Top of 12" 14" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:47 8:52 <br /> Initial Reading .001 .001 <br /> Test End Time 10:17 9:22 <br /> Final Reading .001 .001 <br /> Change in Reading .001 0 <br /> Pass/Fail Criteria > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br /> Sump Manufacturer CSI CSI CSI CSI <br /> Sump Depth (inches) 26" 26" 26 1/2" 27" <br /> Sump Bottom to Top of 7" 8" 7 1/2" 8" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:57 9:02 9:52 9:57 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:27 9:32 10:22 10:27 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />