Measure & record " A" and ' Z, " and then peform the following calculation : <br /> " A " II Ll 05 " Drop tube seal surface to the bottom of the tank <br /> - ( subtract ) <br /> Upper drop tube flange to the edge of the upper tube adapter <br /> - ( subtract ) <br /> 4 , 5 Reference offset <br /> _ ( equals ) <br /> Final shutoff volume height <br /> Locate the final shutoff volume <br /> height on the tank chart <br /> Use the tank chart provided by the tank provided by the tank <br /> manufacturer to record and calculate the following : manufacturer, and record the <br /> closest corresponding volume . <br /> IlG1ILI gal Final shutoff volume <br /> ( divide by) <br /> 52 -7 gal Actual tank capacity <br /> X ( muliply by) <br /> 100 <br /> > > = ( equals ) If the final shutoff volume <br /> O Qn ,t1 ' percentage is 95% or less, the <br /> U U L qH % Final shutoff volume percentage installation conforms to FFS and <br /> Lindustry recommended practices. <br /> ( l 5 �L 'T gal Actual tank capacity <br /> - ( subtract) The final Shutoff Volume Percentage may <br /> be greater than 95% as long as the ullage <br /> L4 gal Final shutoff volume volume remaining is greater than or <br /> _ ( equals ) equal to 250 gallons, so that " . . . none of <br /> the fittings located on the top of the tank <br /> G <br /> gall Ullage volume remaining are exposed to product due to <br /> overfilling, " according to EPA 40 CFR Part <br /> 280 . The installation must also meet all <br /> applicable regulatory requirements, and <br /> must be acceptable to the Authority <br /> Having Jurisdiction (AHJ ) . <br /> J <br /> J 410 - ` <br />