Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 8 . IN -TANK GAUGING TESTING <br /> rl Check this box if tank gauging is used only for inventory control <br /> Check this box if NO tank gauging equipment is installed . Yes No = X NA ' <br /> Do not complete this section if either box is checked. <br /> All wiring has been : 1 ) visually inspected for kinks , breaks and proper entry and ® Q <br /> termination ; and 2 tested for ground faults ? <br /> Were all in -tank gauging probes visually inspected for damage and residue buildup <br /> to ensure that floats move freely, functionally tested , and confirmed operational ? <br /> Was accuracy of system' s product level readings tested ? El M <br /> Was accuracy of system ' s water level readings tested ? El 97 01 <br /> Were all probes reinstalled properly ? <br /> Were all items on the equipment manufacturer's maintenance checklist completed ? ® 0 <br /> Probe ID Probe Model Tanks Monitored Pass Fail <br /> Tl 846390 - 111 87 <br /> T2 846390 - 111 91 <br /> T3 846390 - 111 DSL <br /> 9 . COMMENTS <br /> Describe all answers marked "No " or "Fail" and proposed remedy. <br /> List all monitoring equipment either replaced or repaired. <br /> Found brine on bottom of STP Is . Pumped out , all clear . <br /> Found liquid on the bottom of the vent sump . Pumped out , all clear . <br /> Brine sensor in dispenser 3 / 4 failed initial test due to bad sensor . Replaced sensor ( 304 ) and <br /> retest passed . <br /> Page 5 of 6 <br />