Laserfiche WebLink
STEP 25: INSTALL WARNING PLATE <br /> Bend the three warning plate ears down then slide the <br /> tie wrap over the warning plate ears and position warn- <br /> ing plate against riser pipe approximately 1"below the <br /> adaptor. Tighten the tie wrap securely. The valve is <br /> now fully installed and in operating position. <br /> Q <br /> NOTE: the warning plate includes important warn- <br /> ings,operating parameters,and listing information <br /> and must be installed. '� <br /> l0,0 <br /> Manufacturer:"OPW" <br /> Model:"7150-4" <br /> (4" represents size) <br /> Manufacture Date: <br /> "MPC MMYY" <br /> MM=Month YY=Year <br /> ?W4 <br /> Plate <br /> Figure 26-Product Identification <br /> Figure 23 <br /> STEP 26: VALVE REMOVAL <br /> The valve can be removed for tank leak testing,inspec- <br /> tion,etc.,by removing the Rotatable Product Adaptor, <br /> the 4"ni pple,and the Jack Screw Kit, Reinstall per the <br /> above instructions. <br /> For tastable models only: It is not necessary to re- <br /> move the valve to check poppet movement 1 function. <br /> See Page 17 for full testing details. <br /> STEP 27: ELECTRONIC LIQUID LEVEL MONITORING <br /> If an electronic level monitor is installed, it must be cali- <br /> brated to match the top of the 7150 valve body,which <br /> must correlate with 95°/a of the actual tank capacity. <br /> 16 <br />