Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUN r <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> PAUL E VAZ TRUCKING INC 4740 E PELTIER RD,ACAMPO December 27, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 610 CFR 112.7(a)(3vi), 112.7(a4)Plan failed to adequately detail information and procedures for reporting a discharge. <br /> OBSERVATION: The Spill Prevention, Control, and Countermeasure(SPCC) Plan does not adequately discuss <br /> procedures for reporting a discharge, and information and procedures for reporting a discharge are not included <br /> within the Plan. <br /> -The phone number for the California Office of Emergency Services was missing from the list of emergency <br /> contacts. <br /> -Discharge reporting procedures were not included in the SPCC plan <br /> REGULATION GUIDANCE: The SPCC plan shall include: (vi)Contact list and phone numbers for the facility <br /> response coordinator, National Response Center, cleanup contractors with whom you have an agreement for <br /> response, and all appropriate Federal, State, and local agencies who must be contacted in case of a discharge as <br /> described in § 112.1(b). <br /> (4)Unless you have submitted a response plan under§ 112.20, provide information and procedures in your Plan to <br /> enable a person reporting a discharge as described in § 112.1(b)to relate information on the exact address or <br /> location and phone number of the facility;the date and time of the discharge,the type of material discharged; <br /> estimates of the total quantity discharged; estimates of the quantity discharged as described in§ 112.1(b);the <br /> source of the discharge; a description of all affected media;the cause of the discharge; any damages or injuries <br /> caused by the discharge; actions being used to stop, remove, and mitigate the effects of the discharge;whether an <br /> evacuation may be needed; and, the names of individuals and/or organizations who have also been contacted. <br /> CORRECTIVE ACTION: Ensure the SPCC Plan to includes complete procedures for reporting a discharge. Submit <br /> proof of correction to the EHD. <br /> This is a minor violation. <br /> 612 CFR 112.7(b) Plan doesn't have discharge prediction, including direction, rate of flow, and quantity of oil. <br /> OBSERVATION: The Spill Prevention, Control, and Countermeasure(SPCC) Plan failed to predict the direction, <br /> rate of flow, and the total quantity of the oil that could be discharged for each type of major equipment failure. The <br /> potential equipment failure and the resulting spill from all APSA regulated storage were not addressed in the SPCC <br /> Plan. <br /> REGULATION GUIDANCE: (b)Where experience indicates a reasonable potential for equipment failure(such as <br /> loading or unloading equipment,tank overflow, rupture, or leakage, or any other equipment known to be a source of <br /> a discharge), include in your Plan a prediction of the direction, rate of flow, and total quantity of oil which could be <br /> discharged from the facility as a result of each type of major equipment failure. <br /> CORRECTIVE ACTION: Ensure the SPCC Plan describes potential equipment failures with direction, rate of flow, <br /> and total quantity for all APSA regulated storage. Submit proof of correction to the EHD. <br /> This is a minor violation. <br /> FA0010337 PR0515786 SCO01 12/27/2021 <br /> EHD 28-01 Rev.12/06/2021 Page 9 of 14 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />