Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2353622 Date: 2/8/2022 <br /> Site Name/ID. 7 ELEVEN 35355/35355 <br /> Address: 3202 W HAMMER LANE(N-136) <br /> City: STOCKTON State: CA Zip: 95209 <br /> Tank ID T1: T2: T3: <br /> Product RUL PUL Diesel <br /> Product Line 1 1 1 <br /> Tested From 8 8 8 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model FE Petro MLD FE Petro MLD Vaporless LD-2000 <br /> Serial No. UNREADABLE 02070690 05071049 <br /> Pump Operating Pressure(psi) 32.00 32.00 31.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 32.00 32.00 31.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 160.00 155.00 165.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 14 13 15 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) 5 3 5 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus S�/aldivar Certification#: 115237 <br /> Technician Signature: /-1 1�� Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> @2022 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />