<br /> Aboveground Petroleum Storage Act Inspection Report
<br /> Facility Name: Facility Address: Date:
<br /> American Crane Rental, Inc. 1 17800 Comconex Rd, Manteca January 20, 2022
<br /> SUMMARY OF VIOLATIONS
<br /> (CLASS I,CLASS II,or MINOR-Notice to Comply)
<br /> Item# Remarks
<br /> 629 CFR 112.7(a)(1), 112.70) Failure to include in the Plan discussion of conformance with Federal and State
<br /> requirements.
<br /> OBSERVATION: Facility's Spill Prevention, Control, and Countermeasure(SPCC)Plan failed to adequately discuss
<br /> conformance with all SPCC rule requirements, other effective discharge prevention and containment procedures, or
<br /> any applicable more stringent State rules, regulations, and guidelines. Section 3.11 of the SPCC plan states that
<br /> tanks are registered with Stanislaus County. Tanks are located in San Joaquin County.
<br /> REGULATION GUIDANCE:
<br /> (a)(1) Include a discussion of your facility's conformance with the requirements listed in this part.
<br /> 0) In addition to the minimal prevention standards listed under this section, include in your Plan a complete
<br /> discussion of conformance with the applicable requirements and other effective discharge prevention and
<br /> containment procedures listed in this part or any applicable more stringent State rules, regulations, and guidelines.
<br /> CORRECTIVE ACTION: Ensure that SPCC Plan includes an adequate discussion of conformance with all SPCC
<br /> rule requirements, other effective discharge prevention and containment procedures, or any applicable more
<br /> stringent State rules, regulations, and guidelines. Submit proof of correction to the EHD.
<br /> This is a minor violation.
<br /> 713 CFR 112.7(e), 112.8(c)(6) Failed to test or inspect each container for integrity based on industry standards.
<br /> OBSERVATION: Facility failed to inspect each aboveground container for integrity based on industry standards, as
<br /> discussed in the SPCC Plan. Monthly and annual inspections have not been conducted per John Pascale, Shop
<br /> Manager.
<br /> REGULATION GUIDANCE: REGULATION GUIDANCE: 112.8(c)(6)Test or inspect each aboveground container
<br /> for integrity on a regular schedule and whenever you make material repairs.You must determine, in accordance
<br /> with industry standards,the appropriate qualifications for personnel performing tests and inspections,the frequency
<br /> and type of testing and inspections,which take into account container size, configuration, and design (such as
<br /> containers that are: shop-built,field-erected, skid-mounted, elevated, equipped with a liner, double-walled, or
<br /> partially buried). Examples of these integrity tests include, but are not limited to: visual inspection, hydrostatic
<br /> testing, radiographic testing, ultrasonic testing, acoustic emissions testing, or other systems of non-destructive
<br /> testing.You must keep comparison records and you must also inspect the container's supports and foundations. In
<br /> addition, you must frequently inspect the outside of the container for signs of deterioration,discharges,or
<br /> accumulation of oil inside diked areas. Records of inspections and tests kept under usual and customary business
<br /> practices satisfy the recordkeeping requirements of this paragraph.
<br /> 112.7(e) Inspections,tests, and records. Conduct inspections and tests required by this part in accordance with
<br /> written procedures that you or the certifying engineer develop for the facility. You must keep these written
<br /> procedures and a record of the inspections and tests, signed by the appropriate supervisor or inspector,with the
<br /> SPCC Plan for a period of three years. Records of inspections and tests kept under usual and customary business
<br /> practices will suffice for purposes of this paragraph.
<br /> CORRECTIVE ACTION: Immediately conduct the necessary inspections and all APSA regulated containers based
<br /> on industry standards, on a regular schedule. Maintain testing and inspection records. Submit a copy of the
<br /> inspection results to the EHD.
<br /> This is a Class II violation.
<br /> FA0021903 PR0540930 SCO01 01/20/2022
<br /> EHD 28-01 Rev.12/06/2021 Page 7 of 8 Aboveground Petroleum Storage Act OIR
<br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD