A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> STOCKTON MOBIL 2 3440 E MAIN ST, STOCKTON February 11, 2022 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 104 CCR 2632(d)(1), 2634(d)Failure to have an approved UST Monitoring Plan. <br /> OBSERVATION: The monitoring plan is not current. The diesel mechanical line leak detector(MLLD) is incorrectly <br /> listed in CERS as VMI 99LD2000 and the premium MLLD is incorrectly listed in CERS as Red Jacket xlp. The <br /> MLLDs observed at the time of inspection were Red Jacket FX1 DV for the diesel tank and VMI 99LD2000 for the <br /> premium tank. <br /> REGULATION GUIDANCE: The monitoring plan must be uploaded to the California Environmental Reporting <br /> System (CERS). <br /> CORRECTIVE ACTION: This was corrected on site. <br /> This is a repeat violation, Class Il. <br /> 106 CCR 2632(d), 2641(h) Failure to submit and maintain a current facility plot plan/site map. <br /> OBSERVATION:An accurate UST Monitoring Site Plan was not submitted. <br /> -The locations of the premium and regular tanks are incorrectly swapped on the site plan. <br /> -The site plan incorrectly shows the UDCs contain sensors.The UDCs contained floats and chains at the time of <br /> inspection. <br /> REGULATION GUIDANCE:A site plan must be submitted identifying the locations where monitoring will be <br /> performed. The site plan must show the general layout of tanks and clearly identify locations of the following <br /> equipment, if installed: 1)monitoring panels; 2)in-tank liquid level probes(if used for leak detection); 3)devices <br /> monitoring tank annular spaces or vault; 4)devices monitoring product piping; 5)devices monitoring fill piping; 6) <br /> devices monitoring vent piping; 7)devices monitoring vapor recovery piping; 8)devices monitoring vent/transition <br /> sumps; 9)devices monitoring under-dispenser containment; 10)line leak detectors; and 11)devices monitoring any <br /> other secondary containment areas. <br /> CORRECTIVE ACTION: This was corrected on site. <br /> This is a repeat violation, Class Il. <br /> FA0006423 PR0231173 SCO01 02/11/2022 <br /> EHD 23-01 Rev.12/06/2021 Page 4 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />