Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> STOCKTON MOBIL 2 3440 E MAIN ST, STOCKTON February 11, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The designated operator failed to check and note the correct test dates for the Overfill Prevention <br /> Equipment Inspection on the designated operator inspection reports. On the 10/8/21, 7/16/21,4/23/21, and 3/25/21 <br /> designated operator reports,the designated operator incorrectly noted the Overfill Prevention Equipment Inspection <br /> date as 2/12/21. On the 5/20/21 designated operator report,the Overfill Prevention Equipment Inspection date was <br /> incorrectly noted as 1/2/20.The correct date for the Overfill Prevention Equipment Inspection is 3/12/21. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> This is a repeat violation, Class II. <br /> 304 CCR 2631(a); HSC 25290.1(c) Failure to construct, operate, and maintain primary containment as product-tight. <br /> OBSERVATION:Approximately 2 cups of diesel was found on the far left side of UDC 1/2 when facing pump 2, <br /> indicating a leak in the primary containment. <br /> REGULATION GUIDANCE:All primary containment for the UST system must be product tight. <br /> CORRECTIVE ACTION: Immediately have a properly licensed,trained, and certified contractor repair or replace the <br /> failed component(s), under permit and inspection of the EHD if necessary. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 3/13/2022. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($152). To schedule an appointment, please call (209)468-3420. <br /> Documents provided during inspection: Official Inspection Report, Return To Compliance Certification & <br /> Corrective Action Statement form, inspection photos, List of free CUPA classes <br /> FA0006423 PR0231173 SCO01 02/11/2022 <br /> EHD 23-01 Rev.12/06/2021 Page 7 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />