Laserfiche WebLink
im GETTLER-RYAN <br /> INC, GR .IOL! # 22203381 <br /> TP-201.1C Form 1 <br /> Drop Tube/Drain Vale Assembly Data Sheet <br /> Facility: Test Company: Gettler-Ryan Inc. Test Date: <br /> Arco 2093 8/10/2022 <br /> Address. Test Personnel <br /> 3425 Tracy Blvd. Robert Jacobs <br /> city. State,Zip Code <br /> Tracy CA, 95376 <br /> Overfill Prevention Make&Model; Spill Container Make&Model: <br /> Veeder Root OFW <br /> Date f last Flow Meter Calibration. Date of Last Pressure Gauge Calibration <br /> 6/3/2022 6/3/2022 <br /> Test Results <br /> Device Type&ProductGrade Time to Pressurize 30 Second Flow rate 30-Second Pressure an. <br /> PH) H20) <br /> 87-1 2min 41sec SGML 2.01 <br /> 87-2 2min 36sec 10ML 2.03 <br /> 87-3 2min 38sec lOML 2.03 <br /> 91 2min 53sec 10ML 2.00 <br /> Comments: <br /> California Air Resource Board October 8, 2003 <br /> TP-201.1C, Page 8 <br />