RECEIVED BY EHD VIA EMAIL:
<br /> 2/23/2022
<br /> UNDERGROUND STORAGE TANK
<br /> RESPONSE PLAN-PAGE 2
<br /> VI. REPORTING AND RECORD KEEPING
<br /> W'c will rrporUremrd any overfill,spill,or unauthonycd rc,,,from a UST system as indicated in this plan.
<br /> Recordable Releases: Any unauthurircd release from primary containment which the USI'operator is able to clean up within eight(8)hours after the relCa%e was
<br /> detected or should reasonably have been detected,and which does not escape from secondary containmenes t,donot increase the hazard of fire or explosion,and docs
<br /> not cause any deterioration of.ecordary containment,must be recorded in the facility's monitoring records. Monitoring records must include:
<br /> > The UST operatoes name and telephone number,
<br /> Y A lost of the Wes,quantities,and corcentnnon%of hayaniou%substances rrlcased.
<br /> > A description of the actions taken to control and clan up the release,
<br /> > The method and location of disposal of the rtleued hazardous substances,and whether a hazardous waste manifest was or will be usal;
<br /> > A description of actiom%taken to repair the UST and to prevent future mleascs;
<br /> > A description of the method used to reactivate interstitial monitoring after replacement or repair of primary containment.
<br /> Reportable Reieatas: Any overf-ill,spill,or uneuthonred release which escapes from secondary containment(or primary containment if no secondary containment
<br /> titsul,Increl%cs the hazard of fire or explosion,or causes any docTiorst ion of secondary containment,is a reportable release. Reportable releases are also recordable.
<br /> Within 24 hours after a reportable release has born dctated,or should have been detected,we will notify the local agcrcy adimmmenng the UST program of the
<br /> release,anvcwgwt the rel=%_and take immediate measures to stop the release_ If necessary,or if required by the foul agency,remaining stored product/waste will
<br /> be removed from the UST to prevent further relea%es or facilitate corrective action If an emergency exists,we will notify the California Emergency Management
<br /> Agency at(800)852-7550.
<br /> W ath:n five(5)working days Or a reportable release,we will submit to the local agency a full written report containing all of the following information to the extent
<br /> that the information as known at the time of filing the report.
<br /> > The UST ow-set's or openn>es name and telephone number,
<br /> > A Iasi of flier gTxm.quantities,and concentrations of hazardous materials relca.%ad;
<br /> > The approximate date of the relmse;
<br /> > The dee on%loch Bae release wax dtscovrnd:
<br /> Y The date on which the release was stopped;
<br /> > A description of actions taken to control anddor stop the tcicasc,
<br /> > A descnption of corrective and remedial actions,including investigations which were undertaken and will be conducted to determine the nature and extent of
<br /> sail,ground water or surface water contamination due to the release;
<br /> > The methods)o`cicanup implemented to date,proposed cleanup actions,and a vchcdulc for implementing the proposed actions;
<br /> > The method(s)and location(O of disposal of relaxed hazardous materials and any contaminated mils,groundwater,or surface water.
<br /> > Copia of tiny hazardous waste manifesu used for off-site transport of hazardous wastes associated with clean-up activity;
<br /> > A desaiptior of proposed methods for any repair or replacement of UST system primary/secondary containment systems;
<br /> > A desrnlotion of additional actions taken to prevent future releases
<br /> We will follow the reporting procedures described above if any of the following conditions occur.
<br /> > A recordable Lmaut ton7zd release can not be cleaned up or is still under investigation within eight(8)hours of detection;
<br /> > Released hazardous subrari=we discovered at the UST site or in the surrounding area;
<br /> > Urnmiall operating conddtiorn are ob cned,including erratic behavior of product dispensing equipment,%udden loss of product,or the unexplained presence of
<br /> water in the ink,unless system equipment is found to be defective and is immediately repaired or replaced,and no leak has o mmed;
<br /> > Monitoring resulu from UST system monitoring equipmentlmelhods indicate that a rclmsc may have occurred,unless the monitoring equipment is found lobe
<br /> defective and is irnmodiately repaired,recalibrated,or replaced,and additional monitoring docs not confirm the initial results.
<br /> Record lteimtlm; Mnnnnring records and written repart%of unamhnHied releases must be maintained on-site(or off-site at a readily available location,if approved
<br /> by the kcal agcsry)for at hast 3 years llayandou%wa%tc sh)pping/dkposal record%(e g,manifest%)must be maintained for at(cast 3 years from the date of shipment
<br /> VII. OWNER/OPERATOR SIGNATURE
<br /> CERTMCATTON:I eertlfy that the information provided herein Is true and accurate to the best of my knowledge.
<br /> O)KNE3t/OPFjtATOR SIGNATURE TE
<br /> pA
<br /> izC t 1 IS 1z1 am
<br /> OWNTR/OPFRATOR NAME(print) a71 OWNUUOPERATOR TTiLE an
<br /> (A;encn Use On/a) This plan has been rrviewed and, ❑Approved Approved With Conditions ❑Disapproved
<br /> Local Agency Signature: Date:
<br /> 11'1 Rrapraaw Plan(12!21010)•V3
<br />
|