Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by © Manufacturer Q Industry Standard El Professional Engineer <br /> Test Type © Pressure Q Vacuum E Hydrostatic <br /> Test Equipment Used: Incon Sump Tester <br /> Sump/UDC ID 87-1 STP 87-2 STP 91 STP <br /> Sump Manufacturer Unknown (FRP) Unknown (FRP) Unknown (FRP) <br /> Sump Depth (inches) 52 53 53 <br /> Sump Bottom to Top of 16 18 16 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:16 10:16 10:16 <br /> Initial Reading 3.6541 4.1719 1.7113 <br /> Test End Time 10:31 10:31 10:31 <br /> Final Reading 3.6534 4.1706 1.7107 <br /> Change in Reading 0.0007 -0.0013 -0.0006 <br /> Pass Fail Criteria +/-0.002 +/-0.002 +/- 0.002 <br /> Tightness Test Results El Pass rl Fail © Pass rl Fail © Pass © Fail 0 Pass 0 Fail <br /> Sump/UDC ID UDC#1-2 UDC#3-4 UDC#5-6 <br /> Sump Manufacturer Bravo (FRP) Bravo (FRP) Bravo (FRP) <br /> Sump Depth (inches) 30 30 30 <br /> Sump Bottom to Top of 11 11 11 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:33 11:56 11:56 <br /> Initial Reading 0.9877 .1607 3.2130 <br /> Test End Time 10:48 12:11 12:11 <br /> Final Reading 0.9885 .1607 3.2112 <br /> Change in Reading 0.0008 0.0 0.0018 <br /> Pass Fail Criteria +/-0.002 +/-0.002 +/- 0.002 <br /> Tightness Test Results © Pass 0 Fail © Pass 0 Fail 0 Pass © Fail I! Pass Ll Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />