Laserfiche WebLink
FFSPRO <br /> .; UNIVER&FTY <br /> OPV DROP TUBE CALCULATION E-FORM <br /> Defender Spill Containment(Ref.) <br /> 7,-7 <br /> Seat surface of upper drop tube <br /> 0 <br /> Upper Drop Tube Top of Tank <br /> Final Shutoff Volume"" <br /> Overfill Prevention Valve <br /> «An <br /> (U.S.T.) <br /> Lower "BPI <br /> Drop Tube <br /> «Y„ <br /> rfJ <br /> YH <br /> 6" (152 mm)Max* <br /> i Bottom of Tank Not to scale <br /> 2 i <br /> If local codes require this distance to be smaller, <br /> subtract less than 6"052mm] <br /> Calculate final shutoff volume <br /> To find Upper Drop Tube length"x" To find Lower Drop Tube length"Y" <br /> Actual Tank Capacity prop tube seat <br /> I <br /> surface to �,BI� t 05 3/8 a Final shutoff <br /> 11904 Gallons A" 184 /2 volume height <br /> I <br /> bottom of tank <br /> X (Multiply) - (Subtract) - (subtract) <br /> OPV Length <br /> Typically 95%** 105 318 Final shutoff 15'/."(400 mm) offset <br /> volume height _ (subtract) <br /> Final shutoff volume (subtract) Position and - <br /> Tank bottom <br /> 11279.04 (gallons) 2'/z'(63.5 mm) mounting L 5dearance <br /> adjustment <br /> _(equals) _(equals) <br /> B x1176 518" "Y" 84 118" <br /> Final Shutoff Volume Height Upper Drop Tube Le°5"' L� Dmp Tube Length <br /> tranklinfueling.com <br /> 3760 Marsh Rd.•Madison,WI 5371 B.USA <br /> Tel:+1 608 838 8786•Fax:+1 608 838 6433 <br /> Tel:USA&Canada+1 800 225 9787•Tel-UK+44{01 1473 243300 <br /> Tel:Mex 001 800 738 7610•Tel',bE+49 6571 105 308-Tel-CN+86 10 8565 4566 @ 2018 Franklin Fueling Systems,LLC,All Rights Reserved. <br /> --,Sam dim <br />