FFSPRO <br /> IPPWJ 1 1 <br /> :� . . UNIVERSITY <br /> OPV DROP TUBE CALCULATION E-FORM <br /> Defender Spill Containment(Rei.) <br /> Seat surface of upper drop tube <br /> 0 <br /> X, Top of Tank <br /> «X» <br /> Upper Drop Tube / <br /> t i <br /> Final Shutoff Volume** <br /> Overfill Prevention Valve <br /> rrArr <br /> (U.S.T) <br /> Lower uBtr <br /> Drop Tube <br /> rrYrr <br /> _ri <br /> "Y„ <br /> 1 <br /> 6" (152 mm) Max* <br /> Bottom of Tank Not to Scale <br /> If local codes require this distance to be smaller, <br /> subtract less than 6"(152mm) <br /> Calculate final shutoff volume <br /> To find Upper Drop Tube length"X" To find Lower Drop Tube length"Y" <br /> Actual Tank Capacity <br /> Drop tube sea[ nFinal shutoff <br /> 19782 Gallons "A" 186 surface to "B" 105 7/8 volume height <br /> bottom of tank <br /> X (Multiply) - (Subtract) - (subtract) OPV <br /> Final shutoff 15'/+'(400 mm) offset <br /> Length <br /> Typically 95%** "13" l Q$ ��� volume height <br /> - (subtract) <br /> (subtract) .r Tank bottom <br /> Final shutoff volume Posittonand � <br /> 18743.44 (gallons) 2%"(63.5 mm) mounting �Z clearance <br /> =(equals) adjustment =(equals) <br /> 105 718" = B X"77 5/8" Y" 84 5/8" <br /> Final Shutoff Volume Height Ipper Drop Tube Length Lower Drop Tuba Length <br /> franklinfueling.com <br /> 3760 Marsh Rd.•Madison,WI 53718,USA <br /> Tel:+1 608 83B 8786•Fax:+1 608 638 6433 <br /> Tel:USA&Canada+1 800 225 9787•TeL UK+44(0)1473 243300 <br /> Tel:Mex 001 800 738 7610•Tel:DE+49 6571 105 308•Tel:CN+86 10 8565 4566 ©2018 Franklin Fueling Systems,LLC.All Rights Reserved. <br />