Laserfiche WebLink
• Tank AVGAS 100(4000):Ancillary Equipment-Paint failure and surface corrosion where paint failure has <br /> occurred.** <br /> • Tank Jet A: Corrosion- Some surface corrosion where paint failure has occurred.** <br /> • Tank Jet A: Coating Failure? - Some paint failure on top of tank.** <br /> • Tank Jet A:External Coating Condition - Some paint failure.** <br /> • Tank Jet A:Does the Tank Overfill Protection Operate As Designed?-Unable to test** <br /> • Tank Jet A:Fire Valve Installed? -Install a fire valve on product transfer piping through which liquid could flow <br /> through gravity. <br /> • Tank Jet A:Normal Vent Properly Sized? -Per NFPA 30 2015 21.4.3.3 Normal vents shall be sized in accordance <br /> with either API Standard 2000,Venting Atmospheric and Low-Pressure Storage Tanks,or another approved <br /> standard.Alternatively,the normal vent shall be at least as large as the largest filling or withdrawal connection,but in <br /> no case shall it be less than 1?in.(3.2 cm)nominal inside diameter. <br /> Estimated Repair Total,if applicable: <br />