FACTORY INSTALLED AIR INTAKE FACTORY INSTALLED UNIT-MOUNTED FAN SPEED CONTROLLER
<br /> MECHANICAL EQUIPMENT SCHEDULES HOOD WITH FACTORY INSTALLED DISCONNECT WITH SINGLE POINT FACTORY MOUNTED r FACTORY-MOUNTED
<br /> MOTORIZED OUTSIDE AIR DAMPER ELECTRICAL SERVICE CONNECTION. DISCONNECT UNDER � I INSIDE FAN HOUSING.
<br /> - -
<br /> GAS FLUE HOOD FAN H
<br /> J � r
<br /> SELF CONTAINED ROOFTOP A/C UNIT - GAS FIRED HEAT CD o
<br /> RE: 5M2.1 FOR FACTORY INSTALLED FLOAT SWITCH IN UNIT ROOF INSULATION ` . n a
<br /> CONDENSATE RTU DRAIN PAN. UPON ACTIVATION OF FLOAT CANTSTRIP nn a; ti
<br /> TAG TONS CFM O.A. EXT. * COOLING COOLING EVA HEATING HEATING AFUE WEIGHT REMARKS DRAIN DETAIL SWITCH, UNIT SHALL SHUT DOWN. ROOFING CD w CD ~ N
<br /> CFM S.P. IN MBTUH EFFICIENCY ELECTRICAL DATA FAN
<br /> INPUT OUTPUT LBS _______________ ___________________________
<br /> - . o M
<br /> (LBS) UNION =:>:>:>:>:>:>:>:>:>:>:>:>:>:>:>:>:>:>:>:>:>.>.>.>.>.>.>.>.>.>.>.>.>.>.> >:>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>.>::_----------- i�
<br /> W.G. SENS. TOTAL EER IEER VOLTS PH. HZ MCA MOCP H.P. BTUH BTUH T. D IHS W Q
<br /> DIRT LEG ROOFFACTORY ROOF CURB � � �
<br /> RTU-1 10.0 4000 660 1.0 68.5 118.1 12.0 13.0 208 3 60 52 60 3 130,000 104,000 80% 1,600 ❑i ❑2 ❑3 ® ❑s © ❑� ® ❑9 ROOF DECK GAS v � � o
<br /> 13.0 5200 1187 1.0 83.2 143.4 12.0 13.2 208 3 60 72 80 5 169,000 135,000 80% 2,650 1 2 3 4 s s a COCK SUPPORT ANGLES, AS BACKDRAFT DAMPER ~ o
<br /> RTU-2 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ PIPE SUPPORT, TYPICAL �+
<br /> SD REQUIRED, BY GENERAL EXHAUST DUCT O Cn o
<br /> RE: 2P2.1 CONTRACTOR (DESIGNED `�1-1/2" EXTERNAL INSULATION N
<br /> GENERAL NOTES: a u BY STRUCTURAL ENGINEER 'm N
<br /> (EXHAUST DUCT ONLY). EXTEND o „
<br /> Cn
<br /> 1. PROVIDE UNIT WITH 2" MERV-13 FILTERS. FILTERS ASSUMED TO BE PART OF INTERNAL STATIC PRESSURE. OF RECORD). INSULATION BEYOND ROOF c
<br /> FACTORY ROOF CURB, FLASHED INTO ROOFING INSULATION. � a'
<br /> 2. CONDITIONS BASED ON 100°F AIR ENTERING CONDENSER. SYSTEM PER ROOFING CONTRACTOR'S �
<br /> 3. UNITS SHALL UTILIZE R-410A REFRIGERANT. , REQUIREMENTS. COORDINATE WITH ROOFING ELECTRIC CONDUIT
<br /> 4. ROOFTOP UNITS SHALL BE LENNOX ENERGENCE SERIES. UNITS SHALL BE FURNISHED BY OWNER AND INSTALLED BY CONTRACTOR. CONTRACTOR. BY ELECTRICAL
<br /> LENNOX INDUSTRIES NATIONAL ACCOUNT MANAGER ED WRIGHT: (972)752-4071, ED.WRIGHTQLENNOXIND.COM. CONTRACTOR SHALL FLEXIBLE CONNECTION,
<br /> COORDINATE START-UP OF EACH UNIT WITH LENNOX INDUSTRIES. TYPICAL FACTORY INSTALLED SUPPORT ANGLES, AS REQUIRED, CURB MOUNTING FOR ROOF-
<br /> 5. RTU-1 IS BASED ON A NOMINAL 10-TON UNIT. RTU-2 IS BASED ON A NOMINAL 13-TON UNIT. BY GENERAL CONTRACTOR
<br /> NOTES: DETECTORS .PLY AIR SMOKE CONDUIT WINDOW MOUNTED EXHAUST FAN
<br /> ❑� PROVIDE 14" FACTORY ROOF CURB WITH FACTORY RESTRAINT BRACKETS TO SECURE UNIT TO CURB. CONTROL WIRE CONDUIT BY MECHANICAL 41 N.T.S. Store:
<br /> ❑2 PROVIDE FACTORY CS7500 THERMOSTAT. PROVIDE REMOTE TEMPERATURE/HUMIDITY SENSORS AS SHOWN ON PLANS. ROOFTOP UNIT DETAIL ELECTRIC CONDUIT BY ELECTRICAL KETTLEMAN & L. SACRMENTO
<br /> F3-1 PROVIDE
<br /> PROVIDE FACTORY UNIT-MOUNTED DISCONNECT, OUTSIDE AIR DAMPER AND HOOD, DIRTY FILTER SWITCH, 21 ROOFTOP UNIT 1-1/2" DRAIN LODI, CA 95242
<br /> CONVENIENCE OUTLET (FIELD WIRED), SINGLE POINT ELECTRICAL SERVICE CONNECTION, AND SA SMOKE DETECTORS. COOLING COIL TRAP AND VENT
<br /> ® PROVIDE CLEAR PLEXIGLASS LOCKABLE THERMOSTAT BOX. DRAIN PAN 1-1 2" DRAIN LINE, Restaurant #RC576
<br /> GALVANIZED SHEET METAL GALVANIZED SHEET METAL ROUND /
<br /> BRANCH DUCT RUNOUT WITH SLOPE AT
<br /> IN 1/4" PER P4E HV-M SCHEME A
<br /> PROVIDE LENNOX FACTORY INSTALLED HUMIDITROL HOT GAS REHEAT OPTION AND REMOTE HUMIDITY SENSOR. DUCT WRAP INSULATION OVER ADJUSTABLE ELBOW. ADJUST EXTERNAL DUCT WRAP INSULATION. ROOFTOP 6» FOOT, MINIMUM -
<br /> SHEET METAL ELBOW, MITER ELBOW ANGLE TO MATCH TURNING RE: MECHANICAL GENERAL NOTES. AIR UNIT
<br /> © PROVIDE FACTORY INSTALLED AIR ECONOMIZER WITH DIFFERENTIAL ENTHALPY CONTROL. PROVIDE SOLID-STATE ENTHALPY SENSORS CUT INSULATION TO ELIMINATE ANGLE OF RUNOUT DUCT. - - - - Professional of Record: NAME
<br /> AT MANUFACTURER'S RECOMMENDED LOCATIONS. EXCESS. GASKETING AT
<br /> PROVIDE FACTORY INSTALLED DOWNFLOW BAROMETRIC RELIEF DAMPERS. FACTORY INSTALL DAMPERS WITH ECONOMIZER. MAX 5 FT. (INNER CORE) SPIN-TAP FITTING WITH ADJUSTABLE TOP OF CURB
<br /> [-71FOR RECTANGULAR OR SQUARE LENGTH PRE-INSULATED DAMPER, RE: SPECS. -1/2" BUILT-UP
<br /> [-81 PROVIDE FACTORY MESH HAIL COIL GUARDS AND PROTECTIVE COATED COIL FOR OCEAN COAST. MESH HAIL COIL GUARDS SHALL BE FIELD INSTALLED. CONNECTIONS FROM DUCT TO FLEXIBLE DUCT, RE: SPECS. FACTORY ROOF ROOF SYSTEM
<br /> / / EXTERNALLY WRAPPED SUPPLY DUCT.
<br /> DIFFUSER, USE #8x1/2" LONG, TRIM INNER CORE LENGTH TO CURB
<br /> ❑s PROVIDE CO2 SENSOR FOR DEMAND CONTROL VENTILATION REQUIREMENTS. SELF-TAPPING, HEX HEAD SHEET ELIMINATE EXCESS AND SEE MECHANICAL SPECIFICATIONS.
<br /> AIR DEVICE SCHEDULE ANDAAT LEAST ONESCREWS ATBSCREW PER MAXIMUM SAGGING. ROOF DECK
<br /> SIDE. FOR ROUND CONNECTIONS, ROOFTOP UNIT
<br /> USE A MINIMUM OF FOUR EQUALLY _ ROBISONTYPE MATERIAL FINISH ACCESSORIES
<br /> MANUFACTURER/ SIZE BORDER TYPE SPACED #8x1/2" LONG, �: ,% SUPPORT AND DRAIN DETAIL
<br /> MODEL # SELF-TAPPING HEX-HEAD SHEET I N.T.S.
<br /> METAL SCREWS. I• ; ENGINEERING, INC
<br /> 51
<br /> 19401 40TH AVE W.,SUITE 302
<br /> CEILING DIFFUSER (CD-1) ALUMINUM SEE NOTE 1❑ AG-100 TITUS/TDC-AA 24x24 MODULE TYPE 3 wnllvw000,wA9so36
<br /> INSULATE TOPS OF NOTES: 206-364-3343 TEL
<br /> CEILING DIFFUSER (CD-2) ALUMINUM SEE NOTE 1❑ AG-100 TITUS/TDC-AA 12x12 DIM. A TYPE 1 DIFFUSERS. l l
<br /> CEILING DIFFUSER (CD-3) ALUMINUM SEE NOTE1 AG-100 TITUS/TDC-AA 6x6 DIM. '-0". REI# 424-1551
<br /> ❑ BUTT INSULATION TIGHT 2. SUPPORT DRAIN LINE SIMILAR TO PIPE SUPPORT DETAIL. RE: 2P2.1 FOR DETAIL.
<br /> CEILING DIFFUSER (CD-4) ALUMINUM SEE NOTE 1 AG-100 TITUS/TMRA-AA ❑ ® CEILING DIFFUSER, AGAINST RECTANGULAR DUCT.
<br /> FRAME STYLE SHALL
<br /> RETURN GRILLE ALUMINUM SEE NOTE2❑ -- TITUS/350FLF1 48x24 MODULE TYPE 3 MATCH CEILING. DUCT WRAP INSULATION DAMPER OPERATOR HANDLE WITH
<br /> RETURN GRILLE ALUMINUM SEE NOTE1❑ 2❑ -- TITUS/350FLF1 30x30 DUCT TYPE 1 POSITIVE LOCKING DVICE, TRIM
<br /> SCHEDULE IEVICE SHALDUCTLI NSULATION.VERLAP INSULATION AROUNDE
<br /> EOPERATOR AIR BALANCE SCHEDULE
<br /> EXHAUST REGISTER ALUMINUM SEE NOTE1❑ AG-15 TITUS/350FL 12x12 DUCT TYPE 1 TO PREVENT SWEATING. QROFESS//A
<br /> SIDEWALL GRILLE (SWG) ALUMINUM WHITE AG-15 TITUS/30OFS 6x6 DUCT TYPE 1 SECURE INNER CORE TO METAL DUCT WITH DRAWBANDS, EITHER STAINLESS STEEL WORM DRIVEN (HOSE) CLAMP TYPE OR
<br /> UV-RESISTANT NYLON DUCT TIES TYPE. SEAL JOINTS WITH MASTIC OR PRESSURE SENSITIVE ALUMINUM FOIL TAPE. FLEXIBLE AIR
<br /> GENERAL NOTES: DUCTS SHALL BE TESTED IN ACCORDANCE WITH UL-181B AND CMC 603.5 AND SHALL BE LISTED AND LABELED AS CLASS 0 OR ZONE DINING Z
<br /> 1. CONTRACTOR SHALL COORDINATE AIR DEVICE FRAMES WITH CEILING AND/OR WALL TYPE. CLASS 1. o. M-2871
<br /> 2. CFM QUANTITIES SHOWN ON MECHANICAL FLOOR PLANS. r E 0-21
<br /> NOTES: ROUND DUCT BRANCH RUNOUT CONNECTION DETAIL UNIT SUPPLY AIR RETURN AIR OUTDOOR AIR EXHAUST AIR PRESSURE
<br /> ❑1 FINISH SHALL BE COORDINATED WITH ARCHITECTURAL PLANS. Q DIFFUSER NECK SIZE SHALL BE AS DESIGNATED ON FLOOR PLANS. N.T.S. RTU-1 4000 3340 660 +660 s�q�FF AN\
<br /> L- 3F-4 - - - 450 -450 OF CA\-\
<br /> ❑2 PROVIDE REMOVABLE FACE AND KNURLED KNOB FASTENERS. ® DIFFUSER SHALL HAVE STANDARD BORDER (WITHOUT OPTIONAL OUTER CORE).
<br /> CEILING DIFFUSERS TOP TRUSS CHORD SUBTOTAL 4000 1 3340 660 450 +210
<br /> 1z/z1/Zo
<br /> NECK MAX. CONNECTING MAX. PRESSURE DROP FOR SPIN ZONE KITCHEN
<br /> DESIGNATION SIZE DESIGN CFM DUCT SIZE TAP 25' STRAIGHT FLEXIBLE DUCT REMARKS THREADED ROD ANCHOR SCREWED INTO Prototype: P4E- HV 2020 -2.0 RELEASE
<br /> AND DIFFUSER COMBINATION PROVIDE SIDE OF WOOD TRUSS TOP CHORD RTU-2 5200 4013 1187 +1187
<br /> NYLON-INSERT MAU-1 - - 1800 +1800 Prototype Issue Date: 7.14.2020
<br /> A 6" DIA. 100 6" DIA. 0.15 SEE SPECS. LOCK NUTS WITH GALVANIZED ALL-THREAD ROD
<br /> © 8" DIA. 200 8" DIA. 0.15 SEE SPECS. WASHERS (SIZED PER SMACNA) MAU-2 - - 2929 +2929 Design Bulletin Updates: --
<br /> © 10" DIA. 350 10" DIA. 0.15 SEE SPECS. F-1 - - - 2588 -2588 Date Issued: Bulletin Number:
<br /> PROVIDE SUPPORTS AT ENDS OF
<br /> <9> 12" DIA. 500 12" DIA. 0.15 SEE SPECS. FULL-ROUND ALL SPIRAL DUCTS TO PREVENT F-2 - - - 1138 -1138
<br /> OE 14" DIA. 650 14" DIA. 0.15 SEE SPECS. GALVANIZED DUCTS FROM SAGGING. F-3 - - - 2250 -2250
<br /> DUCT STRAP
<br /> SUBTOTAL 5200 4013 5916 5976 -60 1ST BLDG. SUBMITTAL
<br /> NOTE: SUPPLIERS NOT ABLE TO MEET ANY OF THE ABOVE COMBINATIONS SHALL USE THE NEXT LARGER TYPE SCHEDULED. DUCT CHASE FRAMING
<br /> FANSPROVIDE GASKETED FITTINGS AT ALL TOTALS 9200 7353 6576 6426 +150
<br /> JOINTS, SEAMS AND CONNECTIONS OF
<br /> DESIGNATION CFM S.P. RPM WHEEL DRIVE WHEEL MAX. ELECTRICAL DATA MANUFACTURER/MODEL REMARKS EXPOSED DUCTWORK. MASTICS SHALL INTAKE EXCEEDS EXHAUST FOR BUILDING PRESSURIZATION.
<br /> IN. DIA. TYPE SONES NOT BE USED ON EXPOSED DUCTWORK. LOCAL BALANCE IN THE KITCHEN IS -60 CFM.
<br /> W.G. INCHES H.P. VOLTS PH ❑1 ,❑2 ,❑3 ®,❑s
<br /> BOTTOM TRUSS CHORD
<br /> MAU-1 1,800 0.5 2091 AS REQ'D -- -- -- 1.5 208 3 CAPTIVE-AIRE A1-D.250-15D-MPU ❑1
<br /> MAU-2 2,929 0.625 1354 AS REQ'D -- -- -- 2.0 208 3 CAPTIVE-AIRE A2-D.250-20D-MPU ❑2 24VAC THERMOSTATo REVISIONS:
<br /> F-1 2,588 1.75 1324 AS REQ'D DIRECT CENT -- 2.0 208 3 CAPTIVE-AIRE DU180HFA F21 SPIRAL DUCT SUPPORT R I C G W1 W2 Y1 Y2 OCP CD 12.22.2020 1st Building Submittal
<br /> F-2 1,138 0.75 829 AS REQ'D DIRECT CENT -- 1.0 208 3 CAPTIVE-AIRE DU180HFA ❑2 N.T.S. rn 1
<br /> N 2
<br /> F-3 2,250 1.75 1290 AS REQ'D DIRECT CENT -- 1.5 208 3 CAPTIVE-AIRE DU180HFA ❑i 0 0 3
<br /> F-4 450 0.375 997 AS REQ'D DIRECT CENT 6.0 1/4 120 1 GREENHECK ❑s ®>❑s OUTDOOR AIR REQUIREMENTS - 2019 CMC/CEC 4
<br /> 5
<br /> 86
<br /> 7
<br /> ❑1 MAKE-UP AIR FAN (MAU-1) SHALL BE ELECTRICALLY INTERLOCKED WITH THE HOOD EXHAUST FAN (F-3). MINIMUM
<br /> DESIGN FLOOR AREA REQUIRED OUTSIDE 8
<br /> ❑2 DEVICE CLASSIFICATION RATE MAKE-UP AIR FAN (MAU-2) SHALL BE ELECTRICALLY INTERLOCKED WITH THE HOOD EXHAUST FAN (F-1) & (F-2). OCC. (SQ.FT.) OUTSIDE AIR REMARKS
<br /> ❑a UNIT SHALL BE INSTALLED WITH FACTORY ROOF CURB, BACKDRAFT DAMPER, DISCONNECT SWITCH LOCATED AT FAN, BIRDSCREEN,
<br /> AIR SCHEDULE 4 1
<br /> AND FAN SPEED CONTROLLER LOCATED AT FAN. RTU-1 DINING ROOMS OR DINING HALLS 50 870 7.5 CFM/PERSON 435 CFM 660 CFM SEE BELOW
<br /> OR 0.5 CFM/SQ. FT. Sheet Title:
<br /> ® TOILET ROOM EXHAUST SHALL BE INTERLOCKED WITH RTU-1 FOR CONTINUOUS OPERATION DURING ALL TIMES OF BUILDING 7.5 CFM/PERSON WIRE TO EXHAUST FAN HVAC SCHEDULES
<br /> OCCUPANCY. RTU-2 KITCHENS (COOKING) 8 560 127 CFM 600 CFM SEE BELOW
<br /> FAN SHALL BE GREENHECK G-SERIES. 0.12 CFM/SQ. FT.
<br /> 7.5 CFM/PERSON AND DETAILS
<br /> RTU-2 FOH/BOH 8 854 0.18 CFM/SQ. FT. 214 CFM 587 CFM SEE BELOW
<br /> UNIT HEATERS, ELECTRIC OUTSIDE AIR SCHEDULED ABOVE MINIMUM FOR BUILDING PRESSURIZATION. Date: 12.07.2020
<br /> Project Number: RAC19048.0
<br /> SUPPLY ENT. AIR ELEC DATA
<br /> DESIGNATION CFM OUTPUT KW TEMP. REMARKS AIR CURTAIN SCHEDULE Drawn By: _
<br /> `F• VOLTS PH AMPS
<br /> UH 1 350 1 3.3 1 50 1 208 1 16.2
<br /> 91
<br /> ❑, UNIT HEATER SHALL BE REZNOR MODEL EGEB-3 OR INDEECO MODEL UHIR-3. UNIT SHALL HAVE BUILT-IN THERMOSTAT (SET DESIGNATION MANUFACTURER MODEL CFM FPM MOTOR HP ELECTRICAL FLA WEIGHT G Rc Rh Aux Aux X/C W1 W2 Y1 Y1 Sheet Number:
<br /> AT 50°F) AND HIGH-LIMIT TEMPERATURE CONTROL WITH AUTOMATIC RESET. PROVIDE WALL-MOUNT BRACKET AND INSTALL PER
<br /> MANUFACTURER'S REQUIREMENTS. AC-1 MARS AIR LPV248-1 U 1200 1800 1/6 115V/1 P 2.4 40 LBS THERMOSTAT
<br /> AC-2 QUIKSERV SCT-4860 (LEFT) HEATED -- 2000 -- 120V/1P 3.4 30 LBS
<br /> AC-3 I QUIKSERV SCT-4860 (LEFT) HEATED -- 2000 -- 120V/1P 3.41 30 LBS LOW VOLTAGE THERMOSTAT WIRING DIAGRAM
<br /> FOR RR EXHAUST TO RTU-1 M2 , 1
<br /> NOTE: Q
<br /> 1. PROVIDE DOOR ACTIVATED SWITCH N.T.S.
<br /> 2. FOR AC-2/AC-3. SEE ARCH'S SPECS ON SHEET A9.40 M