ELECTRICAL SPECIFICATIONS <br /> THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL, COMPLETE AND READY FOR 33.22 FIRE ALARM CIRCUITS SHALL BE IDENTIFIED AT TERMINAL AND JUNCTION LOCATIONS, IN A H <br /> OPERATION, A HARDWIRED, SUPERVISED, ZONED AUTOMATIC FIRE AND SMOKE DETECTION MANNER THAT WILL PREVENT UNINTENTIONAL INTERFERENCE WITH THE SIGNALING CIRCUIT <br /> SYSTEM INCLUDING A CENTRAL CONTROL PANEL, DETECTION AND ALARM INITIATING DEVICES, DURING TESTING AND SERVICING. W oED <br /> RELAYS, WIRING, ALL IN ACCORDANCE WITH THE DRAWINGS AND APPLICABLE STANDARDS. c"i m <br /> COMPLY WITH NEC 760 (2008), NFPA 72 (2007) AND 90A (2002), AND ALL FEDERAL, 33.21 WIRING TO BE AS HEREINBEFORE SPECIFIED AND BE COPPER, 300 VOLT RATING. AUDIO x o <br /> co <br /> STATE AND LOCAL LAWS AND ORDINANCES, INCLUDING THE AMERICANS WITH DISABILITIES VISUAL APPLIANCE WIRING TO BE PVC JACKETED, 16 AWG MINIMUM SIZE, NUMBER OF x <br /> ACT. THE ELECTRICAL CONTRACTOR SHALL VERIFY THAT THE COMPLETED SYSTEM CONDUCTORS REQUIRED. SUBMIT CALCULATIONS ON LOAD AND VOLTAGE DROP. INITIATING w >< N <br /> OPERATES IN ACCORDANCE WITH THIS SPECIFICATION. SYSTEMS SHALL BE U.L. AND/OR DEVICE WIRING TO BE PVC JACKETED, 18 AWG MINIMUM SIZE. SUBMIT CALCULATIONS ON o <br /> F.M. LISTED AND APPROVED. LOAD AND VOLTAGE DROP. VOICE EVACUATION SPEAKER WIRING TO BE PVC JACKETED, 16 x o _� x <br /> AWG MINIMUM SIZE. SUBMIT CALCULATIONS ON LOAD AND VOLTAGE DROP. W L� <br /> 33.1 WHERE SHOWN ON THE DRAWINGS OR REQUIRED BY REGULATORY CODES, PROVIDE A c CZ o <br /> DIGITALLY DERIVED AUTO DIALER SYSTEM TO AUTOMATICALLY SEIZE A DEDICATED 33.24 CONTROLLED OUTPUT DEVICES SHALL BE SUPERVISED TO WITHIN THREE FEET OF THE o 0 <br /> w <br /> TELEPHONE LINE TO DIAL AND SIGNAL AN ALARM TO A REMOTE LOCATION. DEVICE CONTROLLED (AIR UNIT STARTER, KITCHEN HOOD, ETC.). `5 Q`Y' <br /> La � <br /> C4) <br /> 33.2 THE ELECTRICAL CONTRACTOR SHALL ENGAGE A FIRE DETECTION SYSTEM CONTRACTOR AS 33.25 WHERE A FIRE DETECTION SYSTEM AS SPECIFIED HEREIN AND REQUIRED FIRE PROTECTION �qk� ' <br /> A SUBCONTRACTOR TO COORDINATE THE INSTALLATION OF THE WORK AND PROVIDE SHOP SPRINKLER SYSTEM ARE INSTALLED, IT SHALL BE PART OF THIS FIRE DETECTION SYSTEM <br /> C=) ti <br /> DRAWINGS FOR REVIEW. SHOP DRAWINGS MUST BE SUBMITTED, APPROVED AND CLEARED CONTRACTOR'S WORK TO NOTIFY IN WRITING THE OWNER OF THE FACILITY OR THE OWNER'S <br /> C=) a' <br /> FROM THE FIRE MARSHAL'S OFFICE BEFORE ANY WORK IS PERFORMED. THE CONTRACTOR REPRESENTATIVE THAT THE FIRE PROTECTION SYSTEM MUST, BY APPLICABLE CODES, BE o °D <br /> CD <br /> WILL BE SOLELY RESPONSIBLE FOR ANY WORK PERFORMED BEFORE FINAL FIRE MARSHAL ADEQUATELY SUPERVISED BY A RESPONSIBLE AUTHORITY APPROVED SUPERVISORY COMPANY <br /> APPROVAL. THAT WILL PROVIDE THE CONTINUOUS MONITORING OF THE SYSTEM TO ASSURE RELIABLE <br /> OPERATION. INSTRUCTIONS SHALL INCLUDE ADVISING THE OWNER TO WRITE THE INSPECTING <br /> 33.3 THE MAIN CONTROL PANEL SHALL BE RECESSED MOUNTED AND SHALL BE LISTED BY AUTHORITY ADVISING OF THIS COMPLIANCE. <br /> UNDERWRITERS' LABORATORIES, INC. FOR FIRE PROTECTIVE SIGNALING SYSTEMS. THE MAIN <br /> CONTROL PANEL SHALL CONTAIN THE PROPER NUMBER OF ZONES AND ZONE MODULES TO <br /> PROVIDE FOR THE NUMBER OF ZONES SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN, <br /> INCLUDING SPACE CAPABILITY FOR FUTURE. PROVIDE 3 EACH 3/4" EMPTY CONDUIT IN <br /> WALL TO THE ACCESSIBLE CEILING SPACE. MAKE OF MODEL SHALL BE HONEYWELL/ES-50X Store: <br /> FIRE ALARM PANEL AND SHALL BE PROVIDED BY CONTRACTOR. KETTLEMAN & L. SACRMENTO <br /> 33.4 WHERE THE MAIN CONTROL PANEL WILL INITIATE AN EMERGENCY FORCES NOTIFICATION <br /> PROCEDURE, THE CONTRACTOR SHALL SHOW THE U.L. LISTING FOR THE CONTROL PANEL LODI CA 95242 <br /> FOR THIS FUNCTION. <br /> 33.5 THE REQUIRED SECONDARY POWER SOURCE SHALL BE PROVIDED FOR BY A U.L. LISTED Restaurant #RC576 <br /> POWER SUPPLY, CHARGER AND BATTERY SYSTEM. THE SYSTEM SHALL BE SIZED FOR ALL <br /> ZONES CONNECTED PLUS THE ZONE CAPABILITY OF THE SYSTEM, AND AN ADDITIONAL 30% <br /> SAFETY FACTOR. P4E-HV-M SCHEME A <br /> 33.6 THE REMOTE INDICATING PANEL SHALL SHOW ALL VISUAL AND AUDIBLE TROUBLE SIGNALS Professional of Record: NAME <br /> AND ZONE INDICATORS THE SAME AS THE MAIN CONTROL PANEL BUT WILL NOT HAVE THE <br /> RESET FUNCTION. REMOTE PANEL SHALL BE FOR RECESSED MOUNTING. <br /> FIRE ALARM RISER DIAGRAM 33.7 PROVIDE A SOLID STATE ACTIVE SURGE PROTECTOR FOR THE INCOMING 120V A.C. LINE. <br /> UNIT TO CLAMP SPIKES AND PEAKS TO A LEVEL BELOW THE DAMAGE THRESHOLD OF THE <br /> UNIT. UNIT TO HAVE OPERATING LIGHT TO INDICATE PROTECTION. SYSTEM TO BE U.L. <br /> LISTED FOR FIRE PROTECTION SYSTEM APPLICATION. <br /> JJ.8 THE CONTROL PANEL SHALL PROVIDE POWER FOR AND RECEIVE THE INPUT INITIATION FROM <br /> INSTALLED SMOKE DETECTORS. DETECTORS SHALL BE U.L. LISTED FOR THE APPLICATION <br /> AND BE COMPATIBLE LISTED WITH THE MAIN CONTROL PANEL. ROBISON <br /> 2 33.9 DO NOT LOCATE SMOKE DETECTORS WITHIN THREE FEET OF ANY SUPPLY OR RETURN AIR <br /> GRILLE OR DIFFUSER. UNIT SHALL BE CAPABLE OF OPERATING IN AIR CURRENTS OF UP TO ENGINEERING, INC <br /> 1-1/4"C AND WIRE 1500 FEET PER MINUTE. <br /> 19401 40Th AVE W.,SUITE 302 <br /> AS REQUIRED LYNNWOCD,WA 98036 <br /> 33.10 DETECTORS MOUNTED IN SUPPLY, RETURN OR EXHAUST AIR DUCTS SHALL BE UL LISTED 206-364-3343TEL <br /> FIRE ALARM CABLE IN CONDUIT FOR DUCT SERVICE UTILIZING AIR SAMPLING TUBES, LENGTH OF THE TUBE THE FULL WIDTH <br /> TO TELEPHONE BACKBOARD FOR OF THE DUCT. THIS DETECTOR SHALL BE PHOTOELECTRIC TYPE, LOW FLOW TYPE WITH A REI# 424-1551 <br /> (2) DEDICATED PHONE LINES. FAP/DACT TO HOOD SUPPRESSION RAP RANGE <br /> OF 100 TO TROL PANEL 4,000 <br /> FEET <br /> UL LIS ED FOR DUCT MOUNTING. <br /> DETECTOR NGHALL BE UL COMPATIBLE WITH <br /> MAKE CONNECTION TO DACT. SYSTEM CONTROL PANEL <br /> TO SPRINKLER HEAT TRACE TO AIR UNIT SHUT DOWN 33.11 DUCT DETECTORS SHALL HAVE SUPERVISED AUXILIARY CONTACTS FOR USE IN THE <br /> CONTROLLER INTERLOCK AND SHUT DOWN CONTROL SCHEMES AS REQUIRED BY THIS SECTION AND THE <br /> TO BACKFLOW PREVENER MECHANICAL SECTIONS OF THIS SPECIFICATION. <br /> TAMPER SWITCHES AND HEAT ()FESS/ <br /> TO POST INDICATOR VALVE 33.12 PROVIDE AS PART OF THE MAIN CONTROL PANEL AN AUTO TELEPHONE NUMBER DIALER QR �N <br /> TRACE CONTROL VOLTAGE. 9 <br /> CONTACTS SYSTEM. THE DIALER SYSTEM IS TO ACTIVATE UPON THE FIRE DETECTION SYSTEM ALARM <br /> MONITOR VOLTAGE ON THE AND WILL HAVE AN OUTPUT DIALER NUMBER SUCH THAT A DEDICATED NUMBER CAN BE <br /> LOAD SIDE OF THE 'A c� <br /> DIALED AND GIVEN SEPARATE DIGITAL ALARM SEQUENCES. SYSTEM MUST BE A DACT AND <br /> DISCONNECT. <br /> BE U.L. LISTED FOR THIS APPLICATION. MAKE OF MODEL SHAKL BE TELGUARD TG-7FS AND Z3 No. E-23059 m <br /> SHALL BE PROVIDED BY CONTRACTOR. <br /> � <br /> 33.13 AUTO-DIALER SHALL BE CONNECTED WITH TWO TELEPHONE LINES USING FIRE ALARM RATED EXP. 3- 1- <br /> FLOOR CABLE. CATEGORY RATED CABLE IS NOT ACCEPTABLE. qT <EC <br /> 33.14 PROVIDE A DEDICATED SOURCE OF POWER FOR THE SYSTEM AS PER NFPA 72. THE F 0 CSHLL BE AL�F� <br /> S SHALL <br /> POLE FOUNDATION DETAIL MIECHANICALLY PROTECTED. <br /> THE CIR UITTO ONLYHIS DISCONNIECTING CE MEANSANDESHIALL HAVE ABRED <br /> 3 <br /> NOT TO SCALE - FOR REFERENCE ONLY MARKING, BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND BE IDENTIFIED AS "FIRE <br /> ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL 12/21/20 <br /> BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL PANEL WITH AN ENGRAVED <br /> LABEL. <br /> : <br /> POLE BASE SHALL BE DESIGNED AND SIGNED BY STRUCTURAL 33.15 THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUIT, WIRING AND CONNECTIONS TO Prototype P4E- HV 2020 - 2.0 RELEASE <br /> ENGINEER. SPECIFICATIONS ARE TO BE VERIFIED WITH STRUCTURAL ALL EQUIPMENT BEFORE CALLING THE UNIT MANUFACTURER'S REPRESENTATIVE FOR FINAL Prototype Issue Date: 7.14.2020 <br /> & ARCHITECTURAL DRAWINGS PRIOR TO BID & INSTALLATION. CHECKOUT. ALL WIRING IS TO BE INSTALLED IN A SEPARATE CONDUIT SYSTEM, AS PER <br /> OTHER SECTIONS OF THIS SPECIFICATION, UNLESS SPECIFICALLY NOTED OTHERWISE. Design Bulletin Updates: -- <br /> POLE 33.16 ALL SPLICES AND CONNECTIONS TO BE WHOLLY CONTAINED WITHIN APPROVED AND Date Issued: Bulletin Number: <br /> ACCESSIBLE JUNCTION BOXES. ALL INPUT INITIATING DEVICES AND OUTPUT SIGNALING <br /> #6 BARE COPPER GROUND APPLIANCES ARE TO BE MOUNTED WITH BACK BOXES AS PER THE U.L. TESTING PROCEDURE -- -- <br /> WIRE HANDHOLE. PROVIDE 15A IN-LINE FUSES, FOR THAT DEVICE. NO DIRECT MOUNTED DEVICES ARE ALLOWED. HARDWIRED SYSTEMS <br /> ACCESSIBLE FROM HANDHOLE, FOR EACH SHALL NOT BE "T-TAPPED" TO SERVE INPUT INITIATING OR OUTPUT NOTIFICATION DEVICES. <br /> O PHASE CONDUCTOR. 1ST BLDG. SUBMITTAL <br /> MOUNTING NUTS, LOCK 33.17 THE SYSTEM SHALL BE ZONED AS PER DRAWINGS; INCLUDE A SEPARATE ZONE FOR EACH <br /> WASHERS AND LEVELING GROUND LUG FIRE PROTECTION ALARM SYSTEM FLOW SWITCH, AS APPLICABLE. REFER TO THE <br /> NUTS. MECHANICAL SPECIFICATIONS AND DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE <br /> BASE COVER FIRE DETECTION SYSTEM CONTRACTOR TO PROVIDE ALL COMPONENTS NECESSARY TO TIE <br /> INTO THE SYSTEMS PROVIDED BY OTHERS. THE ELECTRICAL CONTRACTOR SHALL ALSO <br /> NON-SHRINK GROUT PROVIDE ALL WIRING AS REQUIRED INCLUDING ALL ACCESSORIES DEMANDED BY THE WIRING <br /> ° <br /> I <br /> �°ii II SYSTEM FOR THE FIRE PROTECTION SYSTEM COVERED UNDER THE MECHANICAL IIII °II SPECIFICATIONS. <br /> aII II 11 'ii s CHAMFER EDGE 1 <br /> ° ii II I ALL AROUND <br /> nGRADE 33.18 USE RED COLORED MULTI CONDUCTOR FIRE PROTECTIVE SIGNALING CIRCUIT CABLES. THE <br /> 9i- ila li a_I�9� CABLE MARKING SHALL BE IN ACCORDANCE WITH TABLE 760 179 (1) OF THE NEC. THIS <br /> ir II CABLE SHALL BE USED FOR ALL INITIATING AND SIGNALING WORK AND FOR THE TELEPHONE <br /> aII <br /> . 1 �i °ii® -3/4" DIA. X 10'-0" COPPER LINES FOR ANY DACT UNITS IN THE SYSTEM. CONDUCTORS SHALL BE INSTALLED IN REVISIONS: <br /> ak- II II iba CLAD STEEL GROUND ROD ACCORDANCE WITH ARTICLE 760 OF THE NEC. CABLES THAT ARE INSTALLED WITH 12.22.2020 1st Building Submittal <br /> ei iir 11 it JI N BELOW GRADE. PORTIONS IN CONDUIT UNDERGROUND OR UNDER SLAB SHALL BE NEC RATED FOR WET 1 <br /> LOCATIONS. SUCH CABLES SHALL BE GEL FILLED OR WATER BLOCKED CONSTRUCTION AND <br /> b it JI li --EXOTHERMIC WELDED CONNECTION SHALL HAVE THE FULL LENGTH INSTALLED IN CONDUIT. CABLE SHALL BE BELDEN 2 <br /> WATERDOG SERIES, WEST PENN AQUASEAL SERIES OR EQUAL AS LISTED BY ADDENDA. 3 <br /> �- SUBMIT ALL CABLES FOR REVIEW WITH THE SHOP DRAWINGS. <br /> CONDUIT FOR WIRE 4 <br /> ENTRANCE 33.19 FIRE ALARM CIRCUITS SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. CABLES 5 <br /> SHALL BE SUPPORTED BY THE BUILDING STRUCTURE IN SUCH A MANNER THAT THE CABLE 6 <br /> WILL NOT BE DAMAGED BY NORMAL BUILDING USE. <br /> 7 <br /> CONCRETE FOUNDATION 33.20 ALL WIRING SHALL BE INSTALLED IN A SEPARATE CONDUIT SYSTEM FROM ALL OTHER 8 <br /> SYSTEMS. WIRING INSIDE WALLS AND INSTALLED IN INACCESSIBLE CEILING SPACES TO BE IN <br /> CONDUIT. WIRING INSTALLED IN ACCESSIBLE CEILINGS MAY BE ROUTED WITHOUT CONDUIT. <br /> ROUTE ALL CABLES PARALLEL OR PERPENDICULAR TO WALLS. DO NOT RUN IN A DIAGONAL <br /> a ai FASHION. <br /> 33.21 WIRING WITHOUT CONDUIT SHALL USE DEDICATED J HOOKS MOUNTED AT 4'-0" MAXIMUM Sheet Title: <br /> II <br /> APART. DO NOT ROUTE FIRE ALARM CABLES BUNDLED WITH ANY OTHER CABLING. DO NOT <br /> Ll ELECTRICAL <br /> ° a u CONCRETE FOOTING.REFER TO STRUCTURAL STRAP TO CONDUIT. USE B-LINE BCH SERIES OR CADDY CAT SERIES J-HOOKS WITH <br /> a <br /> FOR SIZE AND TYPICAL MOUNTING AS APPROPRIATE TO THE LOCATION. DO NOT USE NYLON OR PLASTIC STRAPS. SPECIFICATIONS <br /> REINFORCING. DO NOT FASTEN TO CONDUIT OR TO ANY MECHANICAL OR OTHER MOVING EQUIPMENT. <br /> MOUNT ALL SYSTEMS AS HIGH AS POSSIBLE AND ROUTED SO AS TO AVOID ACCESS POINTS <br /> TO OTHER EQUIPMENT AND PERMIT SERVICING. DO NOT ATTACH TO HANGERS USED FOR <br /> CEILING SYSTEMS, LIGHTING FIXTURES, HVAC DUCTWORK, ETC. Date: 12.07.2020 <br /> Project Number: RAC19048.0 <br /> A _ A v Drawn By: - <br /> n <br /> \� n <br /> Ao - o n <br /> ' Sheet Number: <br /> 3 CLEAR <br /> PLAN VIEW <br /> E4 . 2 <br /> Q <br /> m <br /> COPYRIGHT 2020, ROBISON ENGINEERING, INC. <br /> JESCALONA F:\_PEDRO+MCCRACKEN\_RAISING CANES\424-1551 LODI, CA R00576\DWG\E42P4.DWG 12-21-2020 08:42 <br />