Laserfiche WebLink
; <br /> SAN x�JOAQU � Environmental Health Department <br /> � <br /> C0L.IJT`o' <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> WILLIAMS TANK LINES 1 1477 TILLIE LEWIS DR, STOCKTON February 24, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 614 CFR 112.7(c) Failure to provide appropriate secondary containment, diversionary structures or equipment. <br /> OBSERVATION: Facility failed to provide an adequate containment/diversionary structures/equipment for the <br /> following containers: 1)one blue 55-gallon diesel container positioned on it's side and off the ground supported by <br /> metal framing was located outside the shop building without secondary containment, 2)two 500-gallon tanks <br /> (identified as single walled in the current SPCC plan)were observed inside the shop area, 3)one emergency <br /> generator located on bare ground next to the office building,4)one 55-gallons blue container was located on the <br /> wooden pallet inside the shop area. <br /> REGULATION GUIDANCE: (c) Provide appropriate containment and/or diversionary structures or equipment to <br /> prevent a discharge as described in§ 112.1(b), except as provided in paragraph (k)of this section for qualified <br /> oil-filled operational equipment, and except as provided in § 112.9(d)(3)for flowlines and intra-facility gathering <br /> lines at an oil production facility.The entire containment system, including walls and floor, must be capable of <br /> containing oil and must be constructed so that any discharge from a primary containment system,such as a tank, <br /> will not escape the containment system before cleanup occurs. In determining the method, design, and capacity for <br /> secondary containment, you need only to address the typical failure mode, and the most likely quantity of oil that <br /> would be discharged. Secondary containment may be either active or passive in design.At a minimum,you must <br /> use one of the following prevention systems or its equivalent: <br /> (1)For onshore facilities: <br /> (i) Dikes, berms, or retaining walls sufficiently impervious to contain oil; <br /> (ii)Curbing or drip pans; <br /> (iii)Sumps and collection systems; <br /> (iv)Culverting, gutters, or other drainage systems; <br /> (v)Weirs, booms, or other barriers; <br /> (vi)Spill diversion ponds; <br /> (vii) Retention ponds; or <br /> (viii)Sorbent materials. <br /> CORRECTIVE ACTION: Immediately ensure that SPCC addresses all secondary containment provisions and <br /> provide adequate general containment measures/diversionary structures/equipment capable of containing oil and <br /> constructed so that any discharge will not escape the containment system before cleanup occurs. Submit proof of <br /> correction to the EHD. <br /> This is a Class II violation. <br /> FA0010602 PR0523160 SCO01 02/24/2022 <br /> EHD 28-01 Rev.12/06/2021 Page 11 of 16 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />