SAN ,,] DAQ U I <br /> N Environmental Health Department <br /> c0uT IV <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> WILLIAMS TANK LINES 1 1477 TILLIE LEWIS DR, STOCKTON February 24, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 718 CFR 112.8(c)(10) Failed to promptly correct visible discharges and/or remove accumulations of oil in diked areas. <br /> OBSERVATION: The facility failed to promptly correct visible discharges of oil from onsite oil containers/tanks and <br /> promptly remove any accumulations of oil in diked areas: standing oily liquid was noted in all secondary <br /> containment pallets used for drum storage, oily liquid was noted on top of and adjacent to both 500-gallon tanks <br /> located inside the repair shop, oily staining was noted next to the fill pipe and dispenser area of the 12,000 gallon <br /> diesel tank, and standing oily liquid was noted inside the secondary containment of the"transmix"tank located next <br /> to the repair shop. <br /> REGULATION GUIDANCE: (c)(10) Promptly correct visible discharges which result in a loss of oil from the <br /> container, including but not limited to seams, gaskets, piping, pumps, valves, rivets, and bolts.You must promptly <br /> remove any accumulations of oil in diked areas. <br /> CORRECTIVE ACTION: Immediately remove all standing liquid, address all stained ground and oily discharges <br /> and manage all generated wastes according to the California Code of Regulations Title 22 hazardous waste <br /> regulations, submit proof of correction to the EHD. <br /> This is a Class II violation. <br /> 719 CFR 112.8(c)(11) Failed to locate properly or provide sufficient secondary containment for mobile/portable <br /> containers. <br /> OBSERVATION: Facility failed to position portable storage containers to prevent a discharge as described in 40 <br /> CFR 112.1(b).The facility failed to furnish a secondary means of containment, such as a dike or catchment basin, <br /> sufficient to contain the capacity of the largest single compartment or container with sufficient freeboard to contain <br /> precipitation: 1)one blue 55-gallon diesel container positioned on it's side and off the ground supported by metal <br /> framing was located outside the shop building without secondary containment,one 55-gallon blue container of lube <br /> oil was located on the wooden pallet inside the shop area without means of secondary containment. <br /> REGULATION GUIDANCE: (c)(11) Position or locate mobile or portable oil storage containers to prevent a <br /> discharge as described in§ 112.1(b). Except for mobile refuelers and other non-transportation-related tank trucks, <br /> you must furnish a secondary means of containment, such as a dike or catchment basin, sufficient to contain the <br /> capacity of the largest single compartment or container with sufficient freeboard to contain precipitation. <br /> CORRECTIVE ACTION: Position or locate all portable containers to prevent discharge, and provide adequate <br /> secondary containment for mobile or portable oil storage tanks. Provide proof or correction to the EHD. <br /> This is a Class II violation. <br /> FA0010602 PR0523160 SCO01 02/24/2022 <br /> EHD 28-01 Rev.12/06/2021 Page 15 of 16 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />