Laserfiche WebLink
Williams Tank Lines <br /> 1477 Tillie Lewis Drive <br /> Stockton, CA 95206 <br /> Primary Tank <br /> Time Pressure AP <br /> 0 5.0 psi 0 <br /> 5 5.0 psi 0 <br /> 10 5.0 psi 0 <br /> 15 5.0 psi 0 <br /> 20 5.0 psi 0 <br /> 25 5.0 psi 0 <br /> 30 5.0 psi 0 <br /> 35 5.0 psi 0 <br /> 40 5.0 psi 0 <br /> 45 5.0 psi 0 <br /> 50 5.0 psi 0 <br /> 55 5.0 psi 0 <br /> 60 5.0 psi 0 <br /> Certification testing was performed on May 7, 2020, at Williams Tank Lines located at 1477 <br /> Tillie Lewis Drive, Stockton, CA 95206.Testing was performed to Industry Standards on <br /> the 12,000 Gallon#2 Diesel fuel tank and the primary tank was tested to 5.0 psi as the tank <br /> was approximatly 1/2 full.The primarytank passed it's certification testing. No defects were <br /> observed and the #2 Diesel fuel storage system was observed to be in compliance with <br /> Industrial Standards testing requirements.Certification testing is required everyfive years. <br /> Test Device: Ashcroft T5500 SS 5 psi Pressure Gauge_ <br /> Test Gas:_Nitrogen Gas_ <br /> Test Pressure:_5.0 psi_ <br /> Test Duration:-60 minutes_ <br /> Tank Capacity:_12,000 Gallons_ <br /> Certified Tester: _Gary Reeves_ ° <br /> 8 <br /> REA#30349 "5�it�21a <br /> ICC #8019664 <br /> SP001 Level II #11111 <br /> NDT-UT Level III #001 <br /> Certified Environmental Professional " <br />