SHEET TITLE:DRAWING SHEET NO:COPYRIGHT:CHECKED BY:DRAWN BY:DATE:CAD FILE:PROJECT NO:ISSUE:MARKDATEDESCRIPTIONCordell Constructions, Larry Johnson; Phone: 408-221-8126MECHANICALNOTESM000The Oxford Kitchen andGastropub110W OAK STREETLODI, CALIFORNIA,92104.3 ALL NECESSARY ALLOWANCES AND PROVISIONS SHALL BE MADE BY CONTRACTOR FOR BEAMS. COLUMNS OR OTHER OBSTRUCTIONS OF THE BUILDING OR THE WORK OF OTHER CONTRACTORS. WHETHER OR NOT SAME IS INDICATED. WHERE NECESSARY TO AVOID OBSTRUCTIONS. THE DUCTS SHALL BE TRANSFORMED, DIVIDED OFFSET, RAISED OR LOWERED WITH THE REQUIRED FREE AREA BEING MAINTAINED IN ACCORDANCE WITH SMACNA STANDARDS.4.4 ALL RECTANGULAR DUCTWORK ELBOWS 30 DEGREE OR GREATER SHALL BE PROVIDED WITH DOUBLE THICKNESS RADIUS TURNING VANES.4.5 DUCTWORK SIZES SHOWN ARE NET CLEAR INSIDE DIMENSIONS. FOR INTERNALLY LINED DUCTS, FABRICATE SHEET METAL TO ALLOW FOR THICKNESS OF INSULATION AND MAINTAIN NET CLEAR DIMENSIONS.4.6 DUCTWORK SHALL BE SEALED WITH AN APPROVED DUCT MASTIC OR LIQUID SEALANT AS MANUFACTURED BY UNITED MCGILL CORP., OR APPROVED EQUAL. DUCT SYSTEM LEAKAGE SHALL CONFORM TO SMACNA "HVAC DUCT LEAKAGE TEST MANUAL" FOR CLASS 2’ W.C. SEAL CLASS A, LEAKAGE CLASS 24 FOR RECTANGULAR DUCTS AND CLASS 12 FOR ROUND DUCTWORK.4.7 PROVIDE FIRE DAMPERS IN HVAC AIR DISTRIBUTION SYSTEMS THAT PENETRATE FIRE RATED ASSEMBLIES IN ACCORDANCE WITH THE INTERNATIONAL BUILDING AND MECHANICAL CODES. FIRE DAMPERS SHALL BE TYPE B IN ALL DUCTWORK, IN ADDITION TO SECONDARY FIRE DAMPERS FOR CEILING, WALL AND FLOOR MOUNTED AIR DEVICES.4.8 COORDINATE SPECIFIC FIRE RESISTIVE CONSTRUCTION REQUIREMENTS WITH THE FIRE RATED ASSEMBLIES INDICATED ON ARCHITECTURAL DRAWINGS. THROUGH PENETRATIONS FIRESTOP SYSTEMS SHALL CONFORM TO UL LISTED FIRE RESISTANCE DIRECTORY OR OTHER METHODS ACCEPTABLE TO LOCAL GOVERNING CODE AUTHORITIES.4.9 PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN AND EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE INDICATED.4.10 PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE DETECTORS, FIRE DAMPERS. SMOKE DAMPERS, VOLUME DAMPERS, COILS, AND OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/ OR INSPECTION. LABEL ACCESS WITH 1/2" LETTERING.5. INSULATION5.1 INSULATION MATERIALS SHALL BE CERTAIN-TEED OR APPROVED EQUAL INSULATION MATERIALS SHALL HAVE A FLAME SPREAD RATING NOT MORE THAN 25 AND A SMOKE DEVELOPED RATING OF NOT MORE THAN 50. PROVIDE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND AS FOLLOWS:6. DUCT INSULATION1. SUPPLY/RETURN AIR DUCTWORK (CONCEALED): INSULATE WITH NOMINAL 1-INCH THICK TYPE 75 STANDARD DUCTWRAP WITH FSK FACING VAPOR BARRIER. MINIMUM 3/4-INCH INSTALLED THICKNESS WITH A 5.6 R VALUE.2. SUPPLY/RETURN AIR DUCTWORK (INTERIOR EXPOSED WHERE INDICATED): INSULATE WITH 1-INCH THICK TYPE 200 ULTRA-LITE ACOUSTICAL DUCT LINER WITH 100 PERCENT ADHESIVE COVERAGE AND MECHANICAL FASTENERS. MINIMUM INSTALLED R VALUE OF 3.1.3. SUPPLY/RETURN AIR DUCTS (CONCEALED IN ATTIC/CRAWL/ROOF CEILING SPACE): INSULATE WITH NOMINAL 3-INCH THICK TYPE 75 STANDARD DUCTWRAP WITH FSK FACING, VAPOR BARRIER. MINIMUM 2-1/4-INCH INSTALLED THICKNESS WITH 8.5 R VALUE.4. SUPPLY/RETURN/EXHAUST/OUTSIDE AIR DUCTS (OA DUCTWORK & DUCTWORK EXPOSED TO WEATHER CONDITIONS): INSULATE DUCTWORK EXTERIOR WITH SEMI-RIGID FIBERGLASS BOARD INSULATION, TYPE 1B300, 3.0 LBS/CU. FT. DENSITY, MINIMUM 2-INCH INSTALLED THICKNESS WITH 8.5 R VALUE. PROVIDE WEATHERPROOF FINISH AS MANUFACTURED BY FOSTERS MONOLAR 60 -95 COATINGS (MINIMUM OF 3 COATS) OR APPROVED EQUAL.5. PROVIDE ALL NECESSARY FOUNDATIONS, SUPPORTS, PADS AND BASES AS REQUIRED FOR MECHANICAL EQUIPMENT, PIPING, AND DUCTWORK AS PER INTERNATIONAL BUILDING AND MECHANICAL CODES. INSTALL EQUIPMENT, PIPING, AND DUCTWORK SO AS TO BE FREE FROM OBJECTIONABLE NOISE AND VIBRATIONS. CONTRACTOR SHALL COORDINATE WORK WITH STRUCTURAL AND ARCHITECTURAL DRAWINGS PRIOR TO ACTUAL WORK.7. ELECTRICAL WORK7.1 ELECTRIC MOTORS FOR MECHANICAL EQUIPMENT SHALL BE PROVIDED UNDER THE MECHANICAL WORK UNLESS OTHERWISE NOTED. ALL MOTORS SHALL BE NEMA STANDARD DESIGN FOR QUIET OPERATION AND SIZED TO PROPERLY OPERATE EQUIPMENT AT RATED LOAD. MOTORS WITH BELT DRIVES SHALL BE PROVIDED WITH ADJUSTABLE PULLEYS AND SHAFTS. ELECTRICAL POWER CONNECTIONS FOR MECHANICAL EQUIPMENT SHALL BE PROVIDED UNDER THE ELECTRICAL WORK.7.2 MOTOR STARTERS, RELAYS, AND CONTACTORS SHALL BE FURNISHED UNDER THE MECHANICAL WORK AND INSTALLED AND POWERED UNDER THE ELECTRICAL WORK. STARTERS, RELAYS. AND CONTACTORS SHALL BE COMPUTE WITH LUGS SIZED FOR SPECIFIED CONDUCTORS AND INCLUDE REQUIRED ACCESSORIES (I.E. START-STOP PUSH BUTTON, PILOT LIGHTS, H.O.A. SWITCH, AUXILIARY CONTACTS AND OVERLOAD PROTECTION), GENERAL PURPOSE NEMA TYPE 1 ENCLOSURES INDOORS, NEMA TYPE 3R ENCLOSURES OUTDOORS. SINGLE PHASE MOTOR STARTERS SHALL BE MANUAL TYPE WITH OVERLOAD PROTECTION, UNLESS OTHERWISE NOTED. THREE PHASE STARTERS SHALL BE MAGNETIC FULL VOLTAGE, NON-REVERSING, UNLESS OTHERWISE NOTED. STARTERS FOR MECHANICAL SYSTEMS SHALL BE AS MANUFACTURED BY SQUARE-D, GENERAL ELECTRIC, OR CUTLER HAMMER. STARTERS SHALL CONFORM TO NEMA STANDARDS AND NATIONAL ELECTRICAL CODE (NEC) REQUIREMENTS. STARTER CONTROL AND INTERLOCK WIRING SHALL BE PROVIDED UNDER THE MECHANICAL WORK. ALL EQUIPMENT SHALL BE FURNISHED W/ MANUFACTURER PROVIDED DISCONNECT SWITCH.7.3 DUCT SMOKE DETECTORS SHALL BE INSTALLED IN ALL AIR DISTRIBUTION SYSTEMS WITH A DESIGN CAPACITY OF 2000 CFM OR GREATER IN ACCORDANCE WITH THE INTERNATIONAL MECHANICAL CODE SECTION 606 AND NATIONAL FIRE PREVENTION CODE NFPA 72 AND 90A. DUCT SMOKE DETECTORS SHALL BE "DUAL CONTAC"’ TYPE (FOR TIE-IN TO FIRE ALARM SYSTEM AND FOR FAN SHUT-DOWN). COMPLETE WITH SAMPLING TUBE, REMOTE RESET, REMOTE PILOT INDICATOR (FOR CONCEALED APPLICATIONS), UL LISTED FOR INTENDED USE AND COMPLETELY COMPATIBLE WITH FIRE ALARM SYSTEM. DUCT SMOKE DETECTORS SHALL BE FURNISHED AND INSTALLED UNDER THE MECHANICAL WORK AND WIRED AND POWERED UNDER THE ELECTRICAL WORK.8 CONTROLS 8.1 PROVIDE AUTOMATIC TEMPERATURE CONTROL SYSTEM(S) FOR HVAC EQUIPMENT UNDER MECHANICAL WORK. CONTROL DEVICES SHALL BE PROVIDED BY UNIT MANUFACTURER, UNLESS OTHERWISE NOTED. HVAC EQUIPMENT NOT PROVIDED WITH CONTROL DEVICES SHALL BE PROVIDED WITH DEVICES AS MANUFACTURED TO MATCH BASE BUILDING CONTROLS OR APPROVED EQUAL AIR HANDLER SHALL HAVE NIGHT SET BACK CONTROLLED BY A PROGRAMMABLE THERMOSTAT. DEVICE(S) SHALL BE FULLY COMPATIBLE AND SUITABLE FOR INTENDED USE. CONTROL WIRING SHALL BE PROVIDED IN ACCORDANCE WITH THE NEC FOR 24-VOLT CONTROL SYSTEM(S). WIRING SHALL BE A MINIMUM 22 AWG, COLOR CODED AND INSTALLED IN CONDUIT WHERE SUBJECT TO PHYSICAL DAMAGE OR WHERE REQUIRED TO AVOID PLENUM SPACES. EXTEND ALL LOW VOLTAGE WIRING UNBROKEN BETWEEN EACH CONTROL DEVICE AND EQUIPMENT TERMINAL STRIP. INSTALLATION OF CONTROL SYSTEM(S), WRING. AND DEVICES SHALL BE BY A CERTIFIED CONTROLS CONTRACTOR WITH A MINIMUM OF FIVE (5) YEARS EXPERIENCE IN THE INSTALLATION AND SERVICING OF CONTROLS.8.2 UNLESS OTHERWISE INDICATED, ALL THERMOSTATS SHALL BE MOUNTED IN ACCORDANCE WITH ADA REQUIREMENTS.NEW DUCT (1ST DIMENSIONINDICATES SIDE SHOWN, INSIDECLEAR DIMENSIONS)DUCT SIZETRANSITIONRECTANGULAR/SQUAREDUCT TO ROUND DUCT SIZETransitionAIR INTOREGISTER/GRILLEAIR OUT OFREGISTER/GRILLEFLEXIBLE DUCTCONNECTORMANUAL VOLUMEDAMPERBACKDRAFT DAMPERAUTOMATIC (MOTORIZED) VOLUMEDAMPER/ SMOKE DAMPERFIREDAMPERSUPPLY DUCT TO RISEUPSUPPLY DUCT TO DROPDOWNRETURN DUCT TO RISEUPRETURN DUCT TO DROPDOWNELBOW WITH TURNINGVANESSUPPLY AIRDEVICERETURN OR EXHAUST AIRDEVICEDUCT WITH DUCTBRANCHDUCT WITH ROUND DUCTTAKE-OFFDUCT WITH CAPPEDEND12X10EXISTING TONEW CONNECTIONDOUBLE LINE DUCT W/SIZE IN INCHESCEILING MOUNTEDEXHAUST FANUNIT TAG TYPEUNIT DESIGNATED NUMBERTHERMOSTATSWITCHDUCT SMOKE DETECTORDOOR UNDERCUT2’X2‘SUPPLY DIFFUSER2’X2' RETURN GRILLEDIFFUSER TAG TYPEAIR CFM (CUBIC FEET PER MINUTE)GRILLE TAG TYPEAIR CFM (CUBIC FEET PER MINUTE)12X8AHU1TSSDUS1100R1100AF AIR FILTERAFF ABOVE FINISHED FLOORACU AIR CONDITIONING UNITAHU AIR HANDLING UNITAPD AIR PRESSURE DROPARCH ARCHITECTURALBHP BRAKE HORSEPOWERBLDG BUILDINGBLW BELOWBTUH BRITISH THERMAL UNIT PER HOURCCCFM CUBIC FEET PER MINUTECLG CEILINGCUCWDBDDCDlADIDNDODODPSDWGDXCONDENSING UNITCOLD WATERDRY BULBDIRECT DIGITAL CONTROLDIAMETERDIGITAL INPUTDOWNDAMPER OPERATORDIGITAL OUTPUTDIFFERENTIAL PRESSURE SWITCHDRAWINGDIRECT EXPANSIONMECHANICAL GENERAL NOTESSYMBOLSABBREVIATIONSINCHINCH WATER GAUGEKILOWATTLEAVING AIR TEMPERATUREPOUNDSLINEAR FEETMAXIMUM1000 BTUHMECHANICALMECHANICAL EQUIPMENT ROOMMINIMUMMOTORIZEDININ. WG.KWLATLBLFMAXMBHMECHMERMINMOTSUPPLY AIRSUPPLY AIR TEMPERATURESMOKE DETECTORSUPPLY FANSTRUCTURALTRANSFER DUCTTEMPERATURE SENSORTYPICALUNLESS NOTED OTHERWISEWATTWET BULBWATER COLUMNWIRE MESH SCREENWATER PRESSURE DROPSASATSDSFSTRUCTDTSTYPUNOWWBWCWMCWPDNOISE CRITERIANORMALLY CLOSEDNOT IN CONTRACTNORMALLY OPENNOMINALNUMBEROUTSIDE AIROUTSIDE AIR TEMPERATUREOPEN END DUCTPRESSURE DROPPRESSURE SENSORPOUND PER SQUARE INCHRETURN AIRRETURN AIR TEMPERATUREREFRIGERANTRUNNING LOAD AMPEREREVOLUTION PER MINUTENCNCNICNONOMNo.O.A.OATOEDPDPSPSIRARATREFRIGRLARPM(E)EAEATEFEQUIPESPEXTFFDFLFPMFTGALVHCHPHWEXISTINGEACHENTERING AIR TEMPERATUREEXHAUST FANEQUIPMENTEXTERNAL STATIC PRESSUREEXTERNALDEGREE FAHRENHEITFIRE DAMPERFLOORFEET PER MINUTEFEETGALVANIZEDHEATING COILHEAT PUMPHOT WATER1. GENERAL1.1 THE MECHANICAL WORK SHALL CONFORM TO APPLICABLE STATE AND LOCAL CODES AND THE REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION.1.2 THE CONTRACTOR SHALL MAKE ALL NECESSARY ARRANGEMENTS AND PAY FOR ALL PERMITS, FEES, CHARGES AND INSPECTIONS REQUIRED, AS WELL AS HAULING, RIGGING AND TRANSPORTATION CHARGES APPLICABLE TO HIS WORK.1.3 THE PROJECT SHALL BE BID ON THE BASIS OF SPECIFIED PRODUCT(S) WHICH ESTABLISH MINIMUM QUALITY REQUIREMENTS. WHERE MORE THAN ONE PRODUCT NAME IS INDICATED, BIDS SHALL BE BASED ON ONE OF THE NAMED PRODUCTS. ALL MECHANICAL EQUIPMENT SHOWN ON CONTRACT DOCUMENTS SHALL BE NEW, SHALL BE ALL LISTED AND SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE NOTED.A). WHERE USE OF AN ’ACCEPTABLE EQUAL' PRODUCT REQUIRES CHANGES TO THE BASE DESIGN IN ORDER TO INCORPORATE THE PRODUCT INTO THE PROJECT, THE CONTRACTOR SHALL SUBMIT A LAYOUT SHOWING ALL CHANGES TO ARCHITECTURAL. STRUCTURAL, ELECTRICAL, PLUMBING AND MECHANICAL REQUIREMENTS. CHANGES DUE TO USE OF ’ACCEPTABLE EQUAL’PRODUCTS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER AND THE COST OF CHANCES SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR LAYOUT SHALL ACCOMPANY PRODUCT SUBMITTAL DATA.B). SUBSTITUTIONS FOR ’ACCEPTABLE EQUAL’ PRODUCTS NOT SPECIFIED WILL BE CONSIDERED WHEN INCLUDED WITH SUBMISSION OF THE BID AND SHALL BE SUBJECT TO ACCEPTANCE BY THE ENGINEER. PROPOSALS FOR SUBSTITUTIONS SHALL INCLUDE, BUT NOT BE LIMITED TO: (1) ANY ADDED CREDIT OR COST. (2) PRODUCT IDENTIFICATION. (3) CODE COMPLIANCE. (4) REFERENCED STANDARD COMPLIANCE. (5) DESCRIPTION OF ALL CHANGES INCLUDING ARCHITECTURAL, STRUCTURAL, ELECTRICAL, PLUMBING AND MECHANICAL, REQUIRED TO INCORPORATE SUBSTITUTED PRODUCT INTO THE PROJECT. THE OWNER/ENGINEER RESERVES THE RIGHT TO REJECT PROPOSED SUBSTITUTIONS.C). WHERE ’OR EQUAL’ PRODUCTS ARE INDICATED. THE CONTRACTOR SHALL SUBMIT A LIST OF PROPOSED EQUAL SUBSTITUTE PRODUCTS WITH THE BID. THE LIST SHALL INCLUDE ADEQUATE SUPPORTING INFORMATION AS PROOF OF EQUALITY IN ORDER TO BE CONSIDERED ACCEPTABLE. NO LATER SUBSTITUTES WILL BE CONSIDERED.D). SUBSTITUTIONS SHALL PROVIDE THE SAME GUARANTEE AS SPECIFIED FOR BASE BID PRODUCTS.1.4 THE CONTRACTOR SHALL VERIFY FIELD CONDITIONS FOR POINTS OF CONNECTIONS, CAPACITIES, AND LOCATIONS OF SYSTEMS. IN ALL AREAS AFFECTED BY THE PROJECT, CUT, PATCH, REPAIR, AND/OR REPLACE ALL MATERIALS DAMAGED AS A RESULT OF WORK. ALL REPAIRED FINISHES SHALL MATCH APPROPRIATE ADJACENT FINISHES. FILL VOIDS AROUND DUCTWORK PENETRATING WALLS WITH FIRE STOPPING MATERIAL.1.5 MECHANICAL EQUIPMENT AND PRODUCTS SHALL BE LISTED AND/OR LABELED BY AN APPROVED TESTING OR INSPECTION AGENCY IN ACCORDANCE WITH LOCAL AND GOVERNING CODE REQUIREMENTS.1.6 THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF WORK INCLUDED IN THE PROJECT. DO NOT SCALE THE DRAWING. THE CONTRACTOR SHALL ESTABLISH FINAL DIMENSIONS FROM FIELD MEASUREMENTS, PRIOR TO STARTING WORK. 1.7 MECHANICAL WORK SHALL BE COORDINATED WITH THE WORK OF ALL OTHER TRADES PRIOR TO INSTALLATION, TO AVOID CONFLICTS AND ALLOCATE SPACE REQUIREMENTS.1.8 MATERIALS SHALL BE RATES FOR THE OPERATING TEMPERATURE AND PRESSURE OF THE HYDRONIC SYSTEM. MATERIALS SHALL BE SUITABLE FOR THE TYPE OF FLUID IN THE HYDRONIC SYSTEM.1.9 PROJECT PREMISES SHALL BE THOROUGHLY CLEANED AND READY FOR OCCUPANCY INCLUDING ALL FINISHES OF EQUIPMENT PROVIDED AS PART OF THE CONTRACTOR'S WORK. PROVIDE ONE NEW SET OF CLEAN AIR FILTERS FOR ALL AIR MOVING EQUIPMENT AT PROJECT CLOSEOUT.1.10 THE WORD ’PROVIDE’ AS USED IN THE PROJECT SHALL BE DEFINED AS ’"FURNISH AND INSTALL"2. PIPING2.1 PIPING SHOWN IS SCHEMATIC AND DOES NOT INDICATE EVERY OFFSET, ELBOW, UNION, VALVE, TRAP, ACCESS PANEL, ETC., THAT IS REQUIRED FOR A COMPUTE WORKING SYSTEM. PROVIDE ITEMS AND FITTINGS THAT ARE REQUIRED TO INSTALL THE PIPING SYSTEM WITHIN THE SPACE PROVIDED AND THAT ARE REQUIRED FOR A COMPUTE SYSTEM. PIPING SHALL BE PROPERLY SECURED IN ACCORDANCE WITH MSS STANDARD SP-69.2.2 MATERIALS SHALL BE RATED FOR THE OPERATING TEMPERATURE AND PRESSURE OF DOMESTIC SYSTEM. MATERIALS SHALL BE SUITABLE FOR THE TYPE OF FLUID IN THE DOMESTIC SYSTEM.2.3 PIPE SUPPORTS SHALL BE SELECTED AND INSTALLED IN ACCORDANCE WITH THE MSS SP-69 OR LOCAL CODES, WHICHEVER IS MORE STRINGENT. UTILIZE TRAPEZE HANGERS FOR PARALLEL RUNS OR PIPING, OTHER THAN SPRINKLER AND WASTE PIPING. COPPER PIPING SYSTEMS SHALL BE SUPPORTED ON COPPER OR COPPER-PLATED SUPPORTS. HANG PIPE FROM SUBSTANTIAL BUILDING STRUCTURE. PIPING SHALL NOT BE HUNG FROM OTHER PIPING, ALL RIGID HANGERS SHALL PROVIDED A MEANS OF VERTICAL ADJUSTMENT AFTER ERECTION. SHIELD SHALL BE PROVIDED BETWEEN HANGERS AND INSULATION.2.4 WELDING SHALL CONFORM TO CURRENT STANDARDS AND RECOMMENDATIONS OF THE NATIONAL CERTIFIED PIPE WELDING BUREAU, NFPA 51B, STANDARD FOR FIRE PROTECTION; AND NFPA 241,STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS.3. EQUIPMENT3.1 ALL MECHANICAL EQUIPMENT SHOWN ON CONTRACT DOCUMENTS SHALL BE NEW, AND SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE NOTED.3.2 EQUIPMENT AND PRODUCT MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS FOR INSTALLATION AND OPERATION SHALL BE FOLLOWED IN PERFORMING MECHANICAL WORK, UNLESS OTHERWISE INDICATED OR DIRECTED. MATERIALS AND METHODS USED IN THE WORK SHALL BE COMPATIBLE WITH BUILDING CONDITIONS AND COMPLY WITH THE BUILDING CODE REQUIREMENTS, WHICH SHALL BE THE BASIS FOR MINIMUM PRODUCT QUALITY. ALL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER BY SKILLED WORKMEN EXPERIENCED IN THEIR TRADE. THE WORK SHALL BE SUBJECT TO THE ACCEPTANCE OF THE OWNER OR THE DULY AUTHORIZED REPRESENTATIVE.4. DUCTWORK4.1 DUCTWORK SHALL BE FABRICATED OF GALVANIZED SHEET METAL WITH CONSTRUCTION AND INSTALLATION IN ACCORDANCE WITH SMACNA STANDARDS AND SYSTEM REQUIREMENTS. SHEET METAL GAUGES SHALL CONFORM TO THE INTERNATIONAL MECHANICAL CODE (IMC), ASHRAE STANDARDS, AND UL LISTED FIRE RESISTANCE DIRECTORY REQUIREMENTS AS APPLICABLE.4.2 DUCT COVERINGS, DUCT LININGS, TAPES, AND CORE MATERIAL SHALL HAVE A FLAME SPREAD RATING NOT OVER 25, AND SMOKE DEVELOPMENT NOT OVER 50.
|